Remote Operation
5-23
BIT 6
Calibration Error
BIT 22
System parameter
Error
BIT 7
Reserve
BIT 23
Boot Up Initial Error
BIT 8
Reserve
BIT 24
FAN Start Up Error
BIT 9
Reserve
BIT 25
AD Number Error
BIT 10
Fold Back CV to CC
BIT 26
DD Number Error
BIT 11
Fold Back CC to CV
BIT 27
CD FPGA Number
Error
BIT 12
LOCP
BIT 28
Keypro In/Out
BIT 13
LOPP
BIT 29
Reserve
BIT 14
UTP
BIT 30
Cascade Conn Error
BIT 15
AD_PROTECT
BIT 31
Slave Protect Alarm
<Arg2>: ON|OFF output status at present
<Arg3>: CV or CC status at present
Query Example:
FETCh:STATus?
Return Example:
0,OFF,CV
5.6.2.6
MEASURE Subsystem
1.
MEASure:VOLTage?
Description:
Returns the voltage measured at the output of power supply.
Query Syntax:
MEASure:VOLTage?
Return Parameter:
<NRf+> [Unit=Volt]
Query Example:
MEAS:VOLT?
Return Example:
8.01
2.
MEASure:CURRent?
Description:
Returns the current measured at the output of power supply (with
sign)..
Query Syntax:
MEASure:CURRent?
Return Parameter:
<NRf+> [Unit=Amp]
Query Example:
MEAS: CURR?
Return Example:
3.01
3.
MEASure:POWer?
Description:
Returns the power measured at the output of power supply (with
sign).
Query Syntax:
MEASure: POWer?
Return Parameter:
<NRf+> [Unit=Watt]
Query Example:
MEAS: POWer?
Return Example:
5.03
5.6.2.7
PROGRAM Subsystem
1.
PROGram:MODE
Description:
Sets the program output mode.
Syntax:
PROGram:Mode <Arg>
Parameter:
<Arg>: LIST | STEP
Example:
PROGram:Mode STEP
Query Syntax:
PROGram:Mode?
Summary of Contents for 62000D Series
Page 1: ......
Page 2: ...Get more information by downloading Chroma ATE Solutions APP ...
Page 8: ...vi ...
Page 9: ...vii ...
Page 10: ...viii ...
Page 14: ......
Page 18: ......
Page 35: ...Overview 1 17 Figure 1 6 Dimension of 62000D 600 1200 1800 Models ...
Page 36: ......
Page 52: ......
Page 63: ...Manual Operation 3 11 Figure 3 13 Figure 3 14 ...
Page 109: ...Manual Operation 3 57 _EXT ON SIGNAL EXT ON DISABLE EXT ON ENABLE Output Output Figure 3 85 ...
Page 110: ......