![Chloride FS11007A-S3SB FilterPro Installation Handbook Download Page 7](http://html.mh-extra.com/html/chloride/fs11007a-s3sb-filterpro/fs11007a-s3sb-filterpro_installation-handbook_2602775007.webp)
FilterPro Power Filter
6
Specifications
Specifications
Specification
Part number
FS11007A-S3SB
Electrical
Topology
TVSS with filter
Voltage (V)
120
Frequency (Hz)
60
Current - max/continuous RMS (Amps)
7
Overcurrent protection
push-to-reset circuit breaker
Input (six foot attached cord)
5-15P
Output (six inch attached cord)
(3) 5-15R
Efficiency
≥
98%
UL VPR
≤
330 V
Surge let-through voltage, (any input mode)
(ANSI/IEEE C62,41 Cat A ringwave)
< 20 V, Normal Mode (L-N)
< 20 V, Common Mode (N-G)
Allowable load current crest factor
≤
4:1
Overload capacity (1 second)
1000%
Allowable load power factor
0.3 leading to 0.3 lagging
RJ-11 communications line protection
Topology
POTS and ADSL compatible
Classification
secondary protector
Surge let-through, any input mode (Volts) (10 X
1000 uS, 1500 V, 100 A wave form)
< 370 V metallic mode (T-R) & < 370 V longitudinal
mode (T-G or R-G)
Data line protection
Topology
10BaseT, 100BaseT, GigE compatible
Classification
isolated loop
Connections
EIA/TIA-568A (8-position modular jack) in and out
Surge let-through (Volts)
less than 70 V Metallic Mode (Line-Line) and less
than 360 V Longitudinal Mode (Any Line-Earth),
when input is subjected to 10 X 1000 uS, 1500 V,
100 A waveform in any input mode
Operating environment
Temperature
+32°F to +104°F (0°C to +40°C)
Humidity
5-95% RH, non-condensing
Elevation - ft (m)
10,000 (3000) ASL