06
Maintenance
4
1.Check the circuit breaker on a regular basis during operation;
2.After the circuit breaker cuts off the overload or short-circuit current,
the fault should be eliminated before closing the circuit breaker.
Troubleshooting method
Symptoms
Cause analysis
Table 3 Analysis and troubleshooting of common faults
5
Environmental Protection
In order to protect the environment, the product or product parts
should be disposed of according to the industrial waste treatment process,
or be sent to the recycling station for assortment, dismantling and recycling
according to local regulations.
Cannot close
the circuit
breaker by
handle.
Short circuit at load end
Fault occurs to the operating
mechanism.
The rated current of the
circuit breaker does not
match the load current
Eliminate the fault
Replace the product
Replace with product of proper
specifications
Temperature
is too high.
The wire is loose or not
properly fixed by wiring
screws.
The cross-sectional area of
the selected wire is too small
Tighten the wiring screws
Replace with wire of proper
specifications
No power
The wire strip length is too
short.
The wire is loose or not
properly fixed by wiring
screws.
Re-strip the wire
Tighten the wiring screws