EM12-SP User Manual
4. Operation and Display
13
4.2 Function Code Table
If FP-00 set to a non-zero number, parameter protection is enabled. You must write in correct user password to
enter the menu.
To cancel the password protection function, enter with password and set FP-00 to 0
。
The parameter menu under the user-defined parameter mode can directly enter without password.
A is frequency inverter system parameter. Group “F” is basic function parameters .Group “U” is monitoring
function parameters.
Code
Name
Description
Default
F0: Basic function parameters
F0-00
G/P type selection
1: G type(Constant torque load models )
2: P type(Fan, water pump load models )
Model
dependent
F0-02
Command source selection
0: Keypad control (LED off)
1: Terminal control (LED on)
2: Communication control (LED blinking)
0
F0-03
Main frequency source X
selection
0:
Digital setting
(Preset
frequencyF0-08,
UP/DOWN
modifiable, no-record after power off)
1: Digital setting (Preset frequencyF0-08
,
UP/DOWN
modifiable, record after power off)
2: AI1
3: AI2
4: Keypad potentiometer
9: Communication setting
4
F0-08
Preset frequency
0.00Hz
~
maximum frequency(F0-10)
50.00Hz
F0-09
Rotation direction
0: Forward
;
FWD/REV lights off
;
1: Reverse
;
FWD/REV lights on
;
0
F0-10
Maximum frequency
50.00Hz
~
500.00Hz
50.00Hz
F0-11
Source of frequency
upper limit
0: Set by(F0-12)
1: AI1
2: AI2
3: AI3
5: Communication setting
0
F0-12
Frequency upper limit
Frequency lower limit(F0-14)
~
maximum frequency(F0-10)
50.00Hz
F0-13
Frequency upper limit offset
0.00Hz
~
maximum frequencyF0-10
0.00Hz
F0-14
Frequency lower limit
0.00Hz
~
frequency upper limit(F0-12)
0.00Hz
F0-15
Carrier frequency
0.5kHz
~
16.0kHz
Model
dependent
F0-16
Carrier frequency adjustment
with temperature
0: No
1: Yes
1
F0-17
Acceleration time 1
0.00s
~
650.00s(F0-19=2)
0.0s
~
6500.0s(F0-19=1)
0s
~
65000s(F0-19=0)
Model
dependent
F0-18
Deceleration time 1
0.00s
~
650.00s(F0-19=2)
0.0s
~
6500.0s(F0-19=1)
0s
~
65000s(F0-19=0)
Model
dependent
F0-19
Acceleration/Deceleration
time unit
0: 1s
1: 0.1s
2: 0.01s
1
F0-23
Record of digital setting
frequency of power failure
0: not record
1: record
0
F0-25
Acceleration/Deceleration time
base frequency
0: Maximum frequency (F0-10)
1: Set frequency
2: 100Hz
0
F0-26
Base frequency for UP/ DOWN
modification during running
0: Running frequency
1: Setting frequency
0
F0-27
Binding command source to
frequency source
Unit's digit: Binding keypad command to following frequency
source.
0000