16
Anchor bolt length
Above
25mm
Note: Keep the maximum anchor
bolt length as 25mm calculated from
bottom installation foundation.
Model
Refrigerant liquid pipe
Refrigerant gas pipe
5 . 3 kW series
External diameter
φ
6.3 5 (1/ 4" )
External diameter
φ
12.7 (1/2")
7. 0 kW series
External diameter
φ
9. 5 2(3/8 " )
External diameter
φ
1 5 .88( 5 /8 " )
1 0 . 5 kWseries
External diameter
φ
9. 5 2(3/8 " )
External diameter
φ
1 5 . 8 8 ( 5 / 8 " )
2. Length and height difference of ultra-long piping of air conditioning unit
Notice
Indoor unit
O
u
td
o
o
r
A
C
B
Rated refrigerating
capacity
Value
A Pipeline length (one-way)
B Height difference(one-way)
C Pipeline bends quantity
<6.5kW
6.5
~
16kW
Maximum
length15m
Up to 10
Maximum
length8m
Maximum
length20m
Maximum
length10m
Up to 10
1. Dimension of refrigerant pipe
Install the outdoor fan
1. Installation notice:
A. Transport the machine parts in origin package state to installation location.
B. Since the outdoor unit weight deflects from center position, take care when lifting the machine parts
with sling.
C. The inclination of outdoor unit during transportation must not exceed 45
℃
(do not store in horizontal state).
2. Installation
A. When installing the outdoor unit, use bolt to fix the unit footing. (Anchor bolt will be prepared on site)
Install the refrigerant pipe and drain pipe
Note:
①
If no special conditions, select the pipe fittings of our company.
②
Due to special conditions, the thermal insulation sleeve of more than 9mm thick and with favorable
thermal insulation performance to avoid condensation when otherwise procuring the refrigerant pipe.
③
When installing the drainage hose (accessory), additionally procure the cable tray connection exhaust
pipe with inner diameter of
φ16, and bind up w
ith the thermal insulation sleeve of 9mm thick to avoid
condensation.
4.Installation of unit