Isolated Ground Receptacle

This product incorporates an isolated ground receptacle,
identified by the orange triangle on its face. This feature may be
useful to reduce common noise in the connected equipment. Its
intended use is to reduce electrical noise (electromagnetic
interference) by purposely insulating the grounding circuit from
any metallic wiring system. The ground pin of the receptacle is
connected to the green/yellow wire and is isolated from the
metal mounting yoke of the receptacle. The accessible metal of
the product is connected to the green wire. If it is not desired to
use this feature, connect the green/yellow and green wires
together.

References

Application Guide for Isolated Ground Wiring Devices 2007,
National Electrical Manufacturers Association (NEMA)

IEEE Std 1100

-2005, “IEEE Recommended Practice for

Powering and Grounding Electronic Equipment” (Emerald
Book), Section 8.5.3.2.

IEEE Std 142™-2007, “IEEE Recommended Practice for
Grounding of Industrial and Commercial Power Systems”
(Green Book), Sections 5.5.1, 5.5.2

NFPA-70, “National Electrical Code”, Article 250.146
Connecting Receptacle Grounding Terminal to Box.

(D) Isolated Ground Receptacles. Where installed
for the reduction of electrical noise (electromagnetic
interference) on the grounding circuit, a receptacle
in which the grounding terminal is purposefully
insulated from the receptacle mounting means shall
be permitted. The receptacle grounding terminal
shall be connected to an insulated equipment
grounding conductor run with the circuit conductors.
This equipment grounding conductor shall be
permitted to pass through one or more panel boards
without a connection to the panel board grounding
terminal bar as permitted in 408.40, Exception, so
as to terminate within the same building or structure
directly at an equipment grounding conductor
terminal of the applicable derived system or service.
Where installed in accordance with the provisions of
this section, this equipment grounding conductor
shall also be permitted to pass through boxes, wire
ways, or other enclosures without being connected
to such enclosures.

Informational Note: Use of an isolated equipment
grounding conductor does not relieve the
requirement for grounding the raceway system and
outlet box.

C22.2 No. 1, “Canadian Electrical Code, Part 1”, Rule 10-906
Bonding conductor connection to circuits and equipment.

(6) A bonding jumper shall be installed to connect
the bonding conductor to the grounding terminal of
a receptacle and in such a manner that
disconnection or removal of the receptacle will not
interfere with, or interrupt grounding continuity.

(7) In the case of metallically enclosed systems
where the grounding path is provided by the metal
enclosure, a bonding jumper shall be installed to
bond the grounding terminal of the receptacle to the
enclosure.

(8) Notwithstanding Sub-rules (6) and (7), the
bonding jumper, in the case of receptacles having
grounding terminals isolated from the mounting
strap required for special equipment, shall be
permitted to be extended directly back to the
distribution panel.

INSTALLATION

The PAC525P2-/PAC526P2-/PAC526P4-/PAC526P6-/
PAC527P4-/PAC527P6-KITs are intended for use in the
PAC525, PAC526 and PAC527 Series in-wall boxes.

NOTE:

The PAC525P2-, PAC526P2-, PAC526P4-,

PAC527P4- and PAC527P6-KIT products must be
connected to a 15 Amp branch circuit.

WARNING:

IMPROPER INSTALLATION CAN RESULT IN

DEATH OR SERIOUS PERSONAL INJURY! This accessory
should be installed by qualified personnel.

Installing Power Kit Assembly

1.

Attach the grounding pigtail wire (B) to the green grounding
screw already in place within the PAC525, PAC526 or
PAC527 in-wall boxes. (See Figure 1)

Figure 1

1

Grounding screw

(B)

(PAC525P2 shown as example)

Summary of Contents for PAC525P2-KIT

Page 1: ...PAC527P4 PAC527P6 In Wall Box Power Kits Spanish Product Description German Product Description Portuguese Product Description Italian Product Description Dutch Product Description French Product Description PAC525P2 KIT PAC526P2 KIT PAC526P4 KIT PAC526P6 KIT PAC527P4 KIT PAC527P6 KIT ...

Page 2: ...ACTORY WARRANTY It is the installer s responsibility to make sure all components are properly assembled and installed using the instructions provided READ ALL INSTRUCTIONS BEFORE USING THIS PRODUCT DANGER TO REDUCE THE RISK OF ELECTRIC SHOCK 1 Always turn off power at source before installing the outlet WARNING TO REDUCE THE RISK OF BURNS FIRE ELECTRIC SHOCK OR INJURY TO PERSONS Always turn off po...

Page 3: ...T PAC527P6 KIT 3 DIMENSIONS PAC525P2 KIT PAC526P2 KIT PAC526P4 KIT PAC526P6 KIT AC LINE POWER CONDITIONER 125 V 60 Hz 15 A 4x14 AWG STRANDED WIRE W ISOLATED GROUND SURGE PROTECTION EMI RFI FILTERING POWER CONSUMPTION 0 5 WATT PAC527P4 KIT PAC527P6 KIT PAC525P2 KIT ...

Page 4: ...PAC525P2 KIT PAC526P2 KIT PAC526P4 KIT PAC526P6 KIT PAC527P4 KIT PAC527P6 KIT 4 DIMENSIONS continued DIMENSIONS INCHES MILLIMETERS PAC526P4 KIT PAC526P2 KIT DIMENSIONS INCHES MILLIMETERS ...

Page 5: ...PAC525P2 KIT PAC526P2 KIT PAC526P4 KIT PAC526P6 KIT PAC527P4 KIT PAC527P6 KIT 5 DIMENSIONS continued DIMENSIONS INCHES MILLIMETERS PAC526P6 KIT DIMENSIONS INCHES MILLIMETERS PAC527P4 KIT ...

Page 6: ... il fissaggio Bevestiging vastdraaien Serrez les fixations Loosen Fastener Aflojar elemento de fijación Befestigungsteil lösen Desapertar fixador Allentare il fissaggio Bevestiging losdraaien Desserrez les fixations Phillips Screwdriver Destornillador Phillips Kreuzschlitzschraubendreher Chave de fendas Phillips Cacciavite a stella Kruiskopschroevendraaier Tournevis à pointe cruciforme Adjust Ajus...

Page 7: ...IT PAC526P4 KIT PAC526P6 KIT PAC527P4 KIT PAC527P6 KIT 7 TOOLS REQUIRED FOR INSTALLATION PARTS A 1 PAC525P2 PAC526P2 PAC526P4 PAC526P6 OR OR OR Power kit assembly B 1 Grounding pigtail C 2 10 24 x 1 4 PAC527P4 PAC527P6 OR OR ...

Page 8: ...8 40 Exception so as to terminate within the same building or structure directly at an equipment grounding conductor terminal of the applicable derived system or service Where installed in accordance with the provisions of this section this equipment grounding conductor shall also be permitted to pass through boxes wire ways or other enclosures without being connected to such enclosures Informatio...

Page 9: ...y conductors except that it is green with or without one or more yellow stripes is to be installed as part of the circuit that supplies the outlet Refer to Table 250 122 of the National Electrical Code regarding the appropriate size of the grounding conductor NOTE Pressure terminal or pressure splicing connectors and soldering lugs used in the installation of the outlet shall be identified as bein...

Page 10: ...all box See Figure 3 Figure 3 4 Secure power kit assembly to in wall box using two 10 24 x 1 4 Phillips SEMS screws C See Figure 4 Figure 4 Outlet Box Use NOTE The PROTECTED light indicates that the surge protection circuitry is active and operational Figure 5 Tab on power kit Reverse view assembly In wall box tabs 4 C x 2 A PAC525P2 shown as example PROTECTED indicator light PAC525P2 shown as exa...

Page 11: ...PAC525P2 KIT PAC526P2 KIT PAC526P4 KIT PAC526P6 KIT PAC527P4 KIT PAC527P6 KIT 11 ...

Page 12: ... 877 894 6918 952 894 6918 Europe A Franklinstraat 14 6003 DK Weert Netherlands P 31 0 495 580 852 F 31 0 495 580 845 Asia Pacific A Office No 918 on 9 F Shatin Galleria 18 24 Shan Mei Street Fotan Shatin Hong Kong P 852 2145 4099 F 852 2145 4477 Chief a products division of Milestone AV Technologies 8800 002994 Rev01 2017 Milestone AV Technologies www milestone com 07 17 ...

Reviews: