Page 5
For technical questions, please call 1-888-866-5797.
Item 64056
Sa
FE
ty
Op
E
ra
ti
O
n
Maint
E
nanc
E
S
E
tup
Grounding
tO prEVEnt ELEctric SHOcK anD DEatH FrOM incOrrEct GrOunDinG
WirE cOnnEctiOn:
check with a qualified electrician if you are in doubt as to whether the outlet is properly
grounded. Do not modify the power cord plug provided with the tool. never remove the
grounding prong from the plug. Do not use the tool if the power cord or plug is damaged. if damaged,
have it repaired by a service facility before use. if the plug will not fit the outlet, have a proper outlet
installed by a qualified electrician.
Double insulated tools: tools with two prong plugs
This appliance has a polarized plug (one blade is wider
than the other). To reduce the risk of electric shock,
this plug is intended to fit in a polarized outlet only one
way. If the plug does not fit fully in the outlet, reverse
the plug. If it still does not fit, contact a qualified
electrician. Do not modify the plug in any way.
Double insulated tools may be used in
either of the 120 volt outlets shown in the
illustration
Outlets for 2-Prong Plug.
Outlets for 2-prong plug
Extension cords
1.
Grounded
tools require a three
wire extension cord.
Double Insulated
tools can
use either a two or three wire extension cord.
2. As the distance from the supply outlet increases,
you must use a heavier gauge extension cord.
Using extension cords with inadequately sized wire
causes a serious drop in voltage, resulting in loss
of power and possible tool damage.
(See table a.)
3. The smaller the gauge number of the wire, the
greater the capacity of the cord. For example,
a 14 gauge cord can carry a higher current
than a 16 gauge cord.
(See table a.)
4. When using more than one extension cord
to make up the total length, make sure
each cord contains at least the minimum
wire size required.
(See table a.)
5. If you are using one extension cord for more
than one tool, add the nameplate
amperes
and use the sum to determine the required
minimum cord size.
(See table a.)
6. If you are using an extension cord outdoors, make
sure it is marked with the suffix “W-A” (“W” in
Canada) to indicate it is acceptable for outdoor use.
7. Make sure the extension cord is properly wired
and in good electrical condition. Always replace
a damaged extension cord or have it repaired
by a qualified electrician before using it.
8. Protect the extension cords from sharp objects,
excessive heat, and damp or wet areas.
taBLE a: rEcOMMEnDED MiniMuM WirE
GauGE FOr EXtEnSiOn cOrDS* (120/240 VOLt)
naMEpLatE
aMpErES
(at full load)
EXtEnSiOn cOrD
LEnGtH
25´
50´
75´ 100´ 150´
0 – 2.0
18
18
18
18
16
2.1 – 3.4
18
18
18
16
14
3.5 – 5.0
18
18
16
14
12
5.1 – 7.0
18
16
14
12
12
7.1 – 12.0
18
14
12
10
-
12.1 – 16.0
14
12
10
-
-
16.1 – 20.0
12
10
-
-
-
* Based on limiting the line voltage drop to five volts at
150% of the rated amperes.