CZ3055
Isolator
The
frequency
transducer
,
frequency
signal
will
be
set
according
to
the
user
to
convert
the
linear
range
4
~
20mA
(
or
0
~
20mA
)
output
.
The
product
has
one
relay
alarm
output
.
This
product
need
be
supplied
independently
,
and
the
power
supply
,
input
and
output
are
isolated
from
each
other
.
1
2
Number
of
channels: 1
Supply
voltag: 20
~
35V DC
Current
consumption: (24V
power supply,20mA
output
Relay closure
)
≤
90mA
Input:
Signal type:
1) 3-wire
PNP/NPN
sensor
output:
Sensor
distribution: 14V
DC, current:
<
20mA
Input
frequency: 0.1Hz
~
100kHz
2) Frequency
input
signal:
Input
frequency: 0
.
1Hz
~
100kHz
Maximum
input
voltage: 30Vp-p
Minimum
input
level:
2V, (2Hz
~
100KHz)
2V, (0.1Hz
~
100KHz)
3) Proximity
switch, dry
contact
switch
input:
Sensor distribution: approx
≈
8V; short-circuit
current: approx
≈
8mA
Input
frequency: 0.1Hz
~
100kHz
Output:
Current: 0
~
20mA/4
~
20mA
Load
resistance:
≤
400
Ω
Voltage: 0
~
5V/1
~
5V
Load
resistance:
≥
300k
Ω
Transfer
accuracy: 0
.
1
%
F
.
S
.
Temperature
drift: 0.01
%
F
.
S
./℃
Relay
characteristics:
Response
time:
≤
20ms
Drive
ability: 250V
AC/2A
or
30V
DC/2A
Load
type: Resistive
load
Pulse
width:
≥
2
μ
s
Input
signal
fault
detection
function:
If the input signal exceeds the top measuring range set,output current 22mA(or
output voltage 5.5V), the relay aets as the input, SPH LED ON, faceplate display “full”.
If the input signal fallen below the measuring range set, output current 3mA (or
output voltage 0.75V), the relay aets as the input, SPL LED ON, faceplate display
“nfull”.
If the input signal fault and input signal can’t transmission,output current2mA(or
output voltage 0.5V),the relay aets as the input, SPH.SPL ON,faceplate display “no in”.
input signal model is: in2.H/in2.r:
If the input loop-current I
<
0.1mA, proximity switch alarm(break line), output current
2mA,the relay aets as the input,SPH.SPL LED ON, faceplate display “inopn”.
If the input loop-current I
>
6mA, proximity switch alarm(shout circuit)output current
2mA, the relay aets as the input, SPH.SPL LED ON, faceplate display “insot”.
Note: If input signal top limit overflows or lower limit overflows or input signal
faults, the output current can be configured to any value of 0~24mA (0~6V for
voltage) separately.
Start delay time: 0~9999s
When the output relay is set to alarm
mode
with
under-speed, the
instrument
will not output an alarm signal during the launch delay time after power on due to the
under speed of input signal
.
Input
fault
response
time: 0.1~999.9s
The input signal pattern choice:
in H:Frequency input for NAMUR(2
、
3
、
4-wire sensor, dry contact
switch,incremental encoders)at Hz.
in r: Frequency input for NAMUR(2
、
3
、
4-wire sensor, dry contact
-1
switch,ncremental encoders) at min .
in2 H: Switching input for NAMUR,with input wirebreak and input short-circuit
recognition. at Hz.
in2 r: Switching input for NAMUR,switching input for NAMUR,with input wirebreak
-1
and input short-circuit recognition.at min .
-1
Not: If users need to switch measurement display unit, (Hz or min ), you need to
set measuring range
、
alarm
、
alarm hystersis and so on.
The LED indicator light instructions:
SPH: If the input signal exceeds the top alarm(contains dead band) LED ON.
SPL: If input signal fallen below the alarm(contains dead band) LED ON.
SPH
、
SPL ON: Input signal fault.
RAL ON: Output relay closure.
User
Manual
YEAR
YEAR
WARRANTY
WARRANTY
Please read the instruction manual carefully before use the product,
and please safekeeping.
Caution
Please check whether the product type on the package accords
to the ordering contract;
Read this manual carefully before installation or using. If there is
something unclear,please dial technic support hotline-400 881 0780;
Supply voltage is 24VDC, 220VAC is forbidden;
Users are not allowed to dismantle or repair the Isolator otherwise
it will induce malfunction.
Add: Building 6, 201 Minyi Road, Caohejing Hi-Tech Park
Songjiang New Industrial Park, Shanghai 201612, P.R. China
Tel : +86-21-64513350 Fax : +86-21-64846984
Email
:
chenzhu
@
chenzhu
-
inst
.
com
http://www.chenzhu-inst.com