background image

 

CPI User Manual for eConnect PDU and Electronic Lock Kit    02/20.v2                                28 

 

Monitored Pro, Switched, and Switched Pro models will also present per outlet status. The 
image below shows a Switched Pro model. Switched models do not include Current, 
Voltage, Power or Energy values. Monitored Pro models do not include Status or Control 
values.  

 

 
 
 
 
 
 
 
 
  

 

Summary of Contents for eConnect EA Series

Page 1: ...formation and descriptions of listed services and products 2020 Chatsworth Products Inc All rights reserved Chatsworth Products Clik Nut CPI CPI Passive Cooling eConnect Evolution GlobalFrame MegaFram...

Page 2: ...s 33 Cabinet Access Radius Card Settings 34 Logging Overview 35 Logging Export Logs 36 Logging Settings 37 Notification Thresholds 38 Environmental Thresholds 38 Outlet Thresholds 39 Notification Rout...

Page 3: ...the customer claims is defective CPI reserves the sole and absolute right to determine whether or not the product or any part thereof is defective In the event a product or any part thereof is determi...

Page 4: ...ionality and number of outlets PRODUCT FEATURES Vertically Mounted PDUs Physical Dimensions refer to product cut sheet at www chatsworth com Input Voltage 100 415 Volts varies by part number Output Vo...

Page 5: ...For front door Console 2 port Console 2 is a Micro USB connection Same functions as Console 1 Note This is the port used for CLI connection For CLI connection you must use a standard YOST cable Refer...

Page 6: ...f the CE Mark on equipment means that it has been designed tested and certified as complying with all applicable European Union CE regulations and recommendations This device complies with part 15 of...

Page 7: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 7 PDU MODELS Tip See how much savings you can obtain by taking advantage of the...

Page 8: ...restrictions applied to the location and about any precautions that shall be taken Access is using a TOOL or lock and key or other means of security and is controlled by the authority responsible for...

Page 9: ...ease use a breaker with corresponding rating upstream of the PDU o 20 A for PDU Input current rated 16 A o 30 A for PDU Input current rated 24 A o 40 A for PDU input current rated 32 A o 60 A for PDU...

Page 10: ...If the locking lever does not hold open use one of your fingers to hold it open as you disengage the IEC plug External Connections 1 Install the PDU into the cabinet and secure the PDU external ground...

Page 11: ...local interface can display the following information Sum of current voltage and power values for single phase PDUs Line input current and sum of voltage and power values on three phase PDUs Current...

Page 12: ...ns and functions Go to the Main Menu Note In PDUs in the Secure Array the blue icon turns green Note The home icon turns purple during a firmware upgrade Select the highlighted menu item Go to Setup m...

Page 13: ...hed to the PDU The main screen on three phase PDUs lists total voltage and power usage by equipment attached to the PDU Single phase PDU Three phase PDU From the Main menu press Left button to set up...

Page 14: ...e Environment summary screen USB Temperature and Humidity Sensor P N 14665 001 must be attached to the PDU for environmental values to display From the Main menu press Middle button to view next data...

Page 15: ...When any alarm or warning threshold is hit the Alarms summary will be displayed before the PDU Total values when the Home Icon is selected Color codes Text with Yellow background Warning condition was...

Page 16: ...ve summary screen and the LED next to the display will flash Network Configuration Select the Left Button to access the PDU Setup Menu Click on Left button to traverse down the list of options Middle...

Page 17: ...exit this screen Save updates IP information immediately Cancel makes no changes to the setup Return to the Setup Menu Use the Left Button to select IPv6 Network Click on middle button to set up IPv6...

Page 18: ...ins on minutes Brightness Controls display brightness 1 9 Input Cord Controls display orientation TOP or BOT input cord location This rotates the display 180 so that it can be easily read regardless o...

Page 19: ...ay Only one PDU may be Primary and this must be the PDU with the highest level of functionality and highest number of outlets within that functionality Choose ALTERNATE if the PDU will be a backup to...

Page 20: ...nly Will immediately delete all accounts except the default administrative user account Admin admin and reboot the main communications module Outlets will not lose power but you will lose your network...

Page 21: ...Firmware Click on middle button to update firmware for the PDU Optional Click on Left button to traverse down the list of options Middle button to select the highlighted option Right button to travers...

Page 22: ...he list of options Middle button to select the highlighted option Right button to traverse up the list of options Click on middle button to traverse back to the PDU Settings Menu Click on middle butto...

Page 23: ...ddress To access the PDU connect the Ethernet port to a network switch From Web Browser on a computer that is network accessible to the PDU type http PDU address For example the default would be http...

Page 24: ...roll down the page to the heading Time Servers Enter the IP Address of the RFC or NTP Time Server The PDU must have network access to the time server For detailed network setup see Settings Network on...

Page 25: ...reboot and the time will need to be manually reset unless you have assigned Time Server to the PDU The remainder of the manual is ordered according to the tabs on the screen displayed above so the nex...

Page 26: ...ew sub menu will show the operating range as a green bar warning range as a yellow bar and alarm range as a red bar The actual measured value will be shown as a black line overlaying the graph This al...

Page 27: ...ed Lock is not enabled Closed Door is closed Opened Door is opened Tampered Open Door is opened and lock is locked or tampered unlocked or force unlocked Lock status Not Configured Lock is not enabled...

Page 28: ...v2 28 Monitored Pro Switched and Switched Pro models will also present per outlet status The image below shows a Switched Pro model Switched models do not include Current Voltage Power or Energy value...

Page 29: ...lored rectangular alarm status symbol Critical thresholds are indicated by a red colored rectangular alarm status symbol Note The CPI alerts and notification system can be broken down into a few compo...

Page 30: ...ched Pro models Click on Outlet Overview tab to view Outlet Status on the PDU Switched and Switched Pro models you can turn outlets on or off by clicking the checkbox under the Control column The indi...

Page 31: ...specific Outlet from the Outlet tab click on the Set Up sub menu and use the drop down list to select the outlet Switched and Switched Pro models include settings for Outlet ON Delay and Outlet Cycle...

Page 32: ...ther click on the Outlet tab click on the Groups submenu then click on New Group Name the Group select PDU s and Outlets to be grouped and click on Save button To view edit or remove an existing group...

Page 33: ...ser Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 33 eConnect Cabinet Access Control Overview Only applicable for Vertical eConnect PDUs with Auxiliary Ports Go to page 35 to jump to Loggin...

Page 34: ...Access Settings Enter the Cabinet Lock Open Time 1 30 seconds The default value is 5 seconds Enter Cabinet Door Open Alarm Time 1 240 mins The default value is 10 minutes Check box to enable Front or...

Page 35: ...onnect PDU and Electronic Lock Kit 02 20 v2 35 Cabinet Access Radius Card Settings Check the Enable Radius Card Authentication box to be able to enter the server information Check the Use IPv6 box If...

Page 36: ...User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 36 Logging Overview Select Syslog Filter by checking the check box es and click on the Reload Entries button to obtain up to date informat...

Page 37: ...g Export Logs Select type of file and select the log file to be exported Click on DOWNLOAD to download selected file to the connecting computer Click on TRANSFER TO SERVER to save the file on the desi...

Page 38: ...g Settings Log Identity and Log Facilities are preset on the PDU memory system Pick any Log Local to store data locally Storage Server Input information for Data Log and Event Log to be stored remotel...

Page 39: ...ication Thresholds Branch Thresholds Input all desired limitations to be set as thresholds Click on Save Scroll down to input other thresholds Environmental Thresholds Input all desired limitations to...

Page 40: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 40 Environmental Thresholds Continued For Switched and Switched Pro models only...

Page 41: ...comes active the PDU will send an email in response to this alarm becoming active if configured to do so This configuration includes the email settings to get emails to work at all plus the configurat...

Page 42: ...fications for Outlet Temperature Humidity if applicable by checking the check box es Log Trap Email Scroll down for more notification settings Select method s of notifications for Door Lock and PDU if...

Page 43: ...ame and Location The PDU Name is displayed in the summary information at the top of each web interface screen and on the PDU s LCD screen Out of Service checkbox Check this box to deactivate the Elect...

Page 44: ...the Secure Array Share Role checkbox When linking PDUs there can also be an Alternate Primary PDU to provide a backup network connection if the Primary PDU loses its network connection Check this box...

Page 45: ...separate network connection from the Primary PDU and assumes the Primary role providing a network connection to the PDUs in the array if the Primary PDU loses connection The Alternate PDU must be equi...

Page 46: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 46 Settings Environmental Select choice of temperature unit enter name for the temperature and humidity sensors Click on Save...

Page 47: ...s Enter data for IPv4 and or IPv6 Networking Time Servers Designate a time server as the source for time after each reboot requires a network connection As an alternative you can manually set the time...

Page 48: ...er Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 48 Settings SNMP Enter data for SNMP v1 v2c or v3 settings Enter the IP Addresses you want to send traps to Click on Save to save all entere...

Page 49: ...er usually 465 or 25 Check Use TLS or Start TLS check box es to match your provider s encryption requirements Email address the email address assigned to the PDU If Authentication is required select S...

Page 50: ...nect PDU and Electronic Lock Kit 02 20 v2 50 Administration User Management Click on Create User to add a new user Input the username and password and click on Create To edit an existing user Click on...

Page 51: ...essary information Input the Smart Card ID for the Electronic Lock Kit If you don t know your Smart Card ID see Appendix on Page 61 The same information should be input for both the Primary and Altern...

Page 52: ...the necessary information and Save Note that users will need to be added under the Local User List to have Control or Admin capabilities Administration LDAP Authentication For network website authenti...

Page 53: ...wer down outlets Use this if you have connection problems Factory Defaults reset customer entered values to the original factory defaults Reset Network Resets the PDU Network information to factory de...

Page 54: ...54 Reset All Resets all fields to factory defaults To reset to factory defaults select the appropriate radial button Review the warning message Click the Apply Defaults button to apply selected defaul...

Page 55: ...to assure the computer can be reached Click on the Upgrade button to perform the upgrade To upgrade the secondary PDU s select radial button Upgrade Linked PDUs and select the PDU to be upgraded Clic...

Page 56: ...it off then back on and recheck Note that all equipment connected to the branch will lose power Check power at the source If problem persists the Main Controller Module must be replaced See Replaceme...

Page 57: ...on page 58 For eConnect PDU with Electronic Lock Kit installed Lock issue If lock status shows as Not Configured or Lost Communication Check the cable that is connecting the lock to the CAN bus module...

Page 58: ...power source before and placed on a leveled surface before controller module replacement 1 Use an antistatic strap while replacing the controller Unfasten the controller hold down screw using a T10 T...

Page 59: ...be lifted vertically away from the PDU To transfer PDU identify configuration and settings for the PDU swap the SD card on the back of the controller board from the old controller to the new controll...

Page 60: ...ler down to 45 degrees guide the CAN Bus cable with your finger to ensure the cable goes into the slot provided below the controller within the PDU 8 When the controller is resting on top of the PDU s...

Page 61: ...Compliant UL cUL Listed IEC 62368 Operating Temperature 32 149 F 0 65 C at Input Power Rating kW Operating non condensing relative Humidity 5 95 Operating Elevation 0 10000 ft 0 3000 m Storage Tempera...

Page 62: ...is appended to the syslog to show that cabinet access has been attempted by an unknown user The log entry includes the unknown smart card ID The smart card ID can then be read from the syslog and then...

Page 63: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 63...

Page 64: ...is reader although some changes may need to be made to the external card reader settings so the key codes are correct A comparison could be made between the syslog entry method described above to find...

Page 65: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 65...

Page 66: ...RFID Card Type that will be used with the Electronic Lock Kit system If the card type is one of the Desfire HiD iClass Mifare Classic or Prox please proceed to Programming the pcProx Plus reader on pa...

Page 67: ...02 20 v2 67 After selecting Card Analyzer from the menu place the ID card on the reader and press the Learn Card button The reader will then scan through several card types When a compatible card typ...

Page 68: ...r must be flashed with the proper reader settings as shown in the following steps The Card Type must be set from the drop down selector on the Format Data Format tab page Additionally the other fields...

Page 69: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 69...

Page 70: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 70 Common RFID Card Types and Reader Format Settings Desfire Card...

Page 71: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 71 HiD iClass Card...

Page 72: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 72 MiFare Classic Card...

Page 73: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 73 Prox Card Prox cards require an additional settings in the Wiegand to keystroke data format box as shown below...

Page 74: ...CPI User Manual for eConnect PDU and Electronic Lock Kit 02 20 v2 74 APPENDIX 2 Command Line Interface...

Reviews: