chatron miiBIO Quick Start Manual Download Page 9

9

• 

STOP / RESET - inverter stop, error / fault clearing;

• 

MF.K- performs a pre-selected function.

Table No. B1 - list of parameterized functions in solar inverters

 

 

 

description

inv. 1

inv. 2 Definition

F0

 

Basic functions of the 

inverter

 

 

 

 

F0-00 Binary curve selection

1

2

For fan

 

F0-02 Inverter control

1

1

Terminal Control

 

F0-03 Inverter control

 

6

Outside speed control

 

F0-17

Binary curve selection

20

20

For fan

 

F0-18 Inverter control

35

20

Terminal Control

F1

 

Motor parameter assign-

ment functions

 

 

 

 

F1-01 Rated motor power

1,5

1,2

 

 

F1-02 Rated motor voltage

410

380

 

 

F1- 03 Rated motor current

2

1,5

 

F4

 

Parameter setting 

functions of the inverter 

inputs

 

 

 

 

F4-00 Digital input # 1

1

1

RUN Command Entry

 

F4-01 Digital input # 2

 

12

RUN Command Entry

 

F4-02 Digital input # 3

 

13

RUN Command Entry

F5

 

Parameter setting 

functions of the inverter 

outputs

 

 

 

 

F5-02 Relay # 1

1

 

Active when inverter is running

 

F5-03 Relay # 2

1

 

Active when inverter is running

F9   

Parameter assignment 

functions for inverter 

faults

 

 

 

 

 

 

 

 

 

FC  

Inverter control func-

tions

 

 

 

 

FC-01 Percentage of speed 1

 

30

Percentage at low speed

 

FC-02 Percentage of speed 2

 

75

High Speed Percentage

FE  

Parameterizing functions 

of the solar system

 

 

 

 

FE-03 Engine type

0

0

Single-phase motor

 

FE-16 Sleepiness

370 V 250 V Voltage Disabling Inverter

 

FE-17 Activation voltage

420 V 350 V Voltage that activates inverter

 

FE-18 Activation time

3600s

0s

Time for inverter activation

UO  

Monitoring

 

 

 

 

U0-00 Frequency (Hz)

 

 

 

 

U0-02 Input Voltage

 

 

 

 

U0-03 Output Voltage

 

 

 

 

U0-04 Output Current

 

 

 

 

U0-05 Power of photovoltaic 

panels

 

 

 

 

U0-06 Input current

 

 

 

 

U0-07 Status of entries

 

 

 

 

U0-12 Open circuit input 

voltage

 

 

 

Ar

 

Alarms

 

 

 

 

Ar.01

Sleepiness

 

 

 

 

Ar.02

Low frequency pro-

tection

 

 

 

 

Ar.04

Overload protection

 

 

 

 

A4.05 Minimum power pro-

tection

 

 

 

Table No. B2 - list of error codes present in solar inverters.

Table of errors / failures

Code

description

Solution

Err01

Inverter protection

 

1. Short-circuit or earthing at the 

outlet

1. Eliminate external failures

2. The connecting cable is very

2. Install a filter on the outlet

3. Heating the IGBT

3. Check the air filter and cooling fan

4. Disappearance of terminals

4. Connect the cables properly

5. Control card failure

5. Ask for technical help

6. Power board failure

6. Ask for technical help

7. Failure of IGBTs

7. Ask for technical help

Err02 / 

04

Overload during acceleration / 

constant speed

 

1. Short-circuit or earthing at the 

outlet

1. Eliminate external failures

2. Motor parameterization is not 

performed

2. Perform the parameterization

3. The acceleration time is too short

3. Increase the acceleration time

4. The V / F curve is not the most 

appropriate

4. Perform curve adjustment

5. The voltage is too low

5. Set to normal value

6. The start of the operation is carried 

out with a rotating motor

6. Select the restart rotation or start the 

engine when it stops.

7. A charge was added during 

acceleration

7. Remove the added load

8. The power of the inverter is small

8. Select a higher power inverter

Err03

Overload during deceleration

 

1. Short-circuit or earthing at the 

outlet

1. Eliminate external failures

2. Motor parameterization is not 

performed

2. Perform the parameterization

3. The deceleration time is too short

3. Increase the deceleration time

4. The voltage is too low

4. Set to normal value

5. A load was added during dece-

leration

5. Remove the added load

6. Braking unit not installed

6. Install the braking unit

Err05 / 

06

Overvoltage during acceleration / 

deceleration

 

1. Very high input voltage

1. Set to normal value

2. An external force pulls on the 

engine during acceleration

2. Eliminate the external force or install a 

braking unit

3. The acceleration / deceleration 

time is too short

3. Increase the acceleration / decelera-

tion time

4. Braking unit not installed

4. Install the braking unit

Err07

Constant speed overvoltage

 

1. Very high input voltage

1. Set to normal value

2. An external force pulls on the 

engine during deceleration

2. Eliminate the external force or install a 

braking unit

Err08

Power unit failure

 

The input voltage is not within the 

defined range

Set the input voltage for the

Err09

Low tension

 

1. Inverter input failure

1. Clear fault

2. The input voltage is not within the 

defined range

2. Set the input voltage for the

3. Out-of-normal DC bus voltage

3. Ask for technical help

4. Rectifying Bridge Failure

4. Ask for technical help

5. Board failure

5. Ask for technical help

6. Main board failure

6. Ask for technical help

Summary of Contents for miiBIO

Page 1: ...1 miiBIO Instruction manual for installation of Biocooler Smart Solar...

Page 2: ...2 miiBIO Instruction manual for installation of Biocooler Smart Solar...

Page 3: ...hich uses photovoltaic solar energy or mains electrici ty For this purpose it uses 4 photovoltaic panels PV and a monobloc frame with the necessary elements Figure 1 Solar Biocooler system scheme The...

Page 4: ...to ON the solar inverter 1 is activa ted powering the Biocooler with photovoltaic energy When turning the selector switch to OFF the solar inverter 1 is deactivated if it has power from the network th...

Page 5: ...roofs do not provide the sun exposure or incli nation necessary for the effectiveness of the system it may be assumed that it is installed at ground level Always consider minimum ground clearance avoi...

Page 6: ...irect lightning strikes Connect all metallic structural elements of the photovol taic panels to each other and the ground bus in order to create an equipotential bond between all the elements Proper g...

Page 7: ...pment for its operation and will be powered by two sources of ener gy For a better understanding electrical schematics of the power and control circuits are presented Photovo Photovoltaic Panels DC Bo...

Page 8: ...nt of the pho tovoltaic panels into AC power in three phases with about 380 V and a nominal power of 2200W Security information Access and handling of the inverter must be carried out by suitably qual...

Page 9: ...rminals 4 Connect the cables properly 5 Control card failure 5 Ask for technical help 6 Power board failure 6 Ask for technical help 7 Failure of IGBTs 7 Ask for technical help Err02 04 Overload durin...

Page 10: ...e three phases are not balanced 2 Check the motor windings 3 Control board failure 3 Ask for technical help 4 IGBT module failure 4 Ask for technical help Err14 Overheating in the IGBT module 1 Very h...