27
3) Installer settings (authorization 2)
WARNING
To reach the authorization 2 sub menus:
-Turn the 230V Pack Control power off
-Whilst pressing the key, turn the power on and remain pressing for
15 s
NOTE:
After 1 minute of inactivity, the default display appears
After 10 minutes of inactivity, the authorization 2 mode is inactive.
PO Box 11 Ashton Under Lyne OL6 7TR
+44. (0) 161 621 5960 Fax +44. (0) 161 621 5966
www.atlanticboilers.com
The following settings have to be done by competent personnel
Wrong settings can generate failures in the installation and a dangerous increase of
temperatures with risks of scalding
Set the maximum alarm temperature on sensor S1
Set the minimum alarm temperature on sensor S1
Set the maximum alarm temperature on sensor SP
Set the minimum alarm temperature on sensor SP
Set the maximum length of the anti-legionella cycle
Switch on/off the burner lock out alarm
Factory
settings
75º C
15º C
75º C
15º C
07 H
OUI