d) there is an adequate air supply into the room,
e) an extractor fan is not fitted in the same room as the fire.
f) there is sufficient draw in the chimney. Once the chimney is warm
a draught reading of at least 2.5 mm (0.10 inches) water gauge
(25Pa) should be obtained.
Freezing
If a boiler is fitted do not light the fire if there is any possibility that
any parts of the system may be frozen.
Chimney fires
If the chimney is thoroughly and regularly swept, chimney fires
should not occur. However, if a chimney fire does occur then turn
the control knob to the minimum setting (see Fig. 1), and tightly
close the doors of the appliance. This should cause the chimney fire
to go out in which case the control should be kept at the minimum
setting until the fire in the appliance has gone out. The chimney and
flueways should then be cleaned. If the chimney fire does not go out
c) Check for flue or chimney blockage, and clean if required.
d) Do not attempt to relight fire until cause of fume has been
identified and corrected, if necessary seek professional advise.
The most common cause of fume emission is flueway or chimney
Blackening of Door Glass
blockage. For you own safety these must be kept clean.
Differences in chimney draughts mean that the best setting of the air
controls will vary for different installations. A certain amount of
Fire Blazing Out Of Control
experimentation may be required. However, the following points
Check that:
should be noted and with a little care should enable the glass to be
a) the doors are tightly closed,
kept clean in most situations:
b) the thermostat knob is turned down to the minimum setting and
a) The airwash relies on a supply of heated air to keep the glass
the airwash is closed,
clean, therefore, when lighting the stove allow the firebed to become
well established before turning the thermostat down. It may
c) the air inlet damper is closed (at the bottom left of the appliance,
sometimes be beneficial to also keep the doors slightly ajar whilst the
see Fig. 1.) and that it is not prevented from closing completely by a
fire becomes established. This can also apply when re-fuelling.
piece of ash,
b) When re-fuelling keep the fuel back a little from the front firebars,
d) a suitable fuel is being used,
do not try to fit too much fuel into the firebox.
e) the door seals are in good condition.
c) Never completely close the airwash control - as a guide it should
Over-Firing
be at least a quarter open.
If the fire is over-firing it will cause premature failure of the internal
d) Wet wood or logs overhanging the front firebars will cause the
fire parts. Over-firing is occurring when any internal parts of the fire
glass to blacken.
begin to glow red. To prevent over-firing ensure that:
It is always more difficult to keep the glass clean when running the
a) the door seals are kept in good condition, and that the doors are
stove very slowly for long periods.
sealing correctly,
If blackening of the glass still occurs check that all flue connections
b) the thermostat on the fire is working correctly,
are well sealed. It is also important that the chimney draw is sufficient
c) a suitable fuel is being used.
and that it is not affected by down-draught. When the chimney is
warm a draught reading of at least 2.5mm (0.10 inches) water gauge
should be obtained.
Fume Emission
Warning Note: Properly installed, operated and maintained this
appliance will not emit fumes into the room. Occasional fumes
from de-ashing and re-fueling may occur. Persistent fume emission
is potentially dangerous and must not be tolerated. If fume
emission does persist then take the following immediate actions
should be taken:
b) Let the fire out and safely dispose of the fuel from the
appliance.
a) Open doors and windows to ventilate the room and then leave
the premises.
®
charnwood
OPERATING INSTRUCTIONS
SLX
2 0
MULTI-FUEL
8
Summary of Contents for SLX20
Page 1: ...SLX20 MULTI FUEL Operating Installation Instructions charnwood ...
Page 2: ......
Page 18: ... charnwood NOTES SLX20 MULTI FUEL 18 ...
Page 19: ......