Charnwood COUNTRY 8B WOODBURNER MkII Operating And Installation Instructions Download Page 8

Page 8

Island 07.02

suitable inhibitor should be used. The 
system must be correctly vented as 
shown in Figs. 5 and 6. The height 
differential between the header tank 
and the appliance must not exceed 
15.2 metres (50 feet).

If all four boiler tappings are used 
then, if possible, diagonal pairs should 
be connected for domestic hot water 
and central heating. Where a common 
return is used an injector tee must be 
incorporated into the system as shown 
in Fig. 7. This will ensure that a good 
domestic hot water supply is 
maintained when the central heating 
pump is operating.

The system must incorporate a gravity 
circuit which will normally heat the 
domestic hot water and an unvalved 
radiator with an output of at least 1 
kW. When the appliance is not 
connected to a domestic hot water 
system the unvalved radiator(s) on the 
gravity circuit must have an output of 
at least 1.25 kW. This is to prevent 
boiling in case of pump failure. All 
pipework in the primary circuit must 
be 28 mm diameter and the gravity 
flow pipe must rise continuously from 
the boiler to the open vent. Two 
typical systems are shown in Figures 
4. and 5.

If the appliance is used to heat a very 
small central heating system then the 
heat output to the room from the fire 
will be reduced. Fig. 4. shows the ratio 
of space heating to water heating 
which can be expected.

Fitting a radiator in the same room as 
the fire is recommended as it will 
allow greater flexibility in the way 
that the system is operated as well as 
ensuring that there is sufficient heat.

Connect the heating system to the 
boiler ensuring that the primary flow 
pipe rises continuously from the 
appliance to the vent. Fill the system 
with water and check for leaks. 

SYSTEM CONTROLS

Since the controls on the stove are 
manually operated we strongly 
recommend using high and low limit 
pipe thermostats to control the pump. 
The high limit, (anti-boiling,) 

Drain Cock

Indirect Hot Water Cylinder

Gravity Radiator

Domestic Hot Water Draw Off

Cold Water Tank

Overflow

Feed and Expansion Tank

22mm Open Vents

Overflow

Central Heating Flow

Central Heating Return

Drain Cock at Lowest Point

Gravity Return 28mm

Circulating Pump

Thermostat

Using 4 Boiler Tappings

Fig. 5. Typical Central Heating & Hot Water System

Gravity Return

(28mm Pipe)

Central Heating Return

Common Return to Boiler

(28mm Pipe)

Fig. 7. Injector Tee.

Drain Cock

Indirect Hot Water Cylinder

Domestic Hot Water Draw Off

Gravity Radiator

Cold Water Tank

Overflow

Overflow

Feed and Expansion Tank

22mm Open Vents

Central Heating Return

Drain Cock at Lowest Point

Gravity Return 28mm

Circulating Pump

Injector Tee

Central Heating Flow

Using 3 Tappings

Fig. 6. Typical Central Heating & Hot Water System

Low Limit

Low Limit Thermostat

Gravity Flow 28mm

High Limit Thermostat

High Limit Thermostat

Gravity Flow 28mm

Summary of Contents for COUNTRY 8B WOODBURNER MkII

Page 1: ... D i v i s i o n o f A J W e l l s S o n s L i m i t e d R e g i s t e r e d i n E n g l a n d N o 0 3 8 0 9 3 7 1 C H A R N W O O D B i s h o p s W a y N e w p o r t I s l e o f W i g h t P O 3 0 5 W S U n i t e d K i n g d o m T 4 4 0 1 9 8 3 5 3 7 7 9 9 F 4 4 0 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d a j w e l l s c o u k w w w c h a r n w o o d c o m ...

Page 2: ......

Page 3: ...th the optional coal kit burning it on the flat base of the stove may cause damage A little extra care is needed when burning coal please refer to the section Special Points When Burning House Coal later in the instructions Smokeless Fuel A wide variety of smokeless fuels are available many of which are suitable for use on your Country 8 Some of these are listed below Ancit Anthracite Large Nuts C...

Page 4: ... the grate and cover with approximately 2 inches of fuel Open the air slides in the doors and open the airwash control fully see Fig 1 Light the paper or fire lighters Close the doors until the fuel is well ignited then load with fuel and adjust the air controls to the required setting When relighting the stove leave the ash on the base if burning wood or peat unless it is beginning to block the s...

Page 5: ... may be necessary to find the setting most suitable for the type of fuel being used and the draw on the chimney To revive the fire empty the ashpan if burning coal or smokeless fuel poke the fire and open the air controls to maximum When the fire is burning well load on more fuel as necessary and adjust the air controls to the desired setting CLEANING AND MAINTENANCE The stove is finished with a h...

Page 6: ...ts of the system may be frozen Lack of Heat To Radiators Hot Water Check that a the fire is burning properly if not then carry out the checks under Fire Will Not Burn b the throat plate is fitted correctly see Fig 2 and that it is not distorted c the door seals are in good condition d If the hot water goes cold when the pump is turned on or if some radiators are hotter than others then the system ...

Page 7: ...d Fuel burning appliances flues and chimneys must also be observed PERFORMANCE The output of the Country 8B WB is 7 0 kW 23 800 Btu h to water and 2 5 kW 8 500 Btu h to the room These outputs are based on a 2 hourly re fuelling cycle burning seasoned hardwood logs or a 4 hourly re fuelling cycle burning smokeless fuel CHIMNEY In order for the appliance to perform satisfactorily the chimney height ...

Page 8: ...water heating which can be expected Fitting a radiator in the same room as the fire is recommended as it will allow greater flexibility in the way that the system is operated as well as ensuring that there is sufficient heat Connect the heating system to the boiler ensuring that the primary flow pipe rises continuously from the appliance to the vent Fill the system with water and check for leaks S...

Page 9: ...t should be fitted on the gravity return again as near to the boiler as possible but ensuring that it is not on the common part of the return if only one return tapping is used Set the high limit thermostat at 85 C and the low limit thermostat at 45 C Radiators may be either manually or thermostatically controlled CONNECTIONS TO FLUES There are several ways of connecting the stove to the flue Thes...

Page 10: ...Page 10 Island 07 02 Country 8B Woodburner MkII Overall DImensions 510 508 376 450 127 587 45 614 526 ø154 664 450 127 494 221 80 80 320 ...

Page 11: ...ntrol Knob 16 004 TW48 Airwash Slide 17 002 GV01 Left Hand Door 18 002 GV02 Right Hand Door 19 002 CH12B Flue Collar 20 009 CO8BWBR Firebox Boiler Assy Country 8B 21 012 TW09 BlankingPlate 22 012 BV20 A Ashpan Door Opening Tool 23 002 DY18 R H Door Knob Spindle 24 002 AY14 Door Catch Cam 25 002 DY19 Left Hand Door Knob 26 010 DY08 Fuel Retainer 27 010 AY51 ClampingPlate 28 010 NV11 Flue Spacer Rin...

Page 12: ... i s t e r e d i n E n g l a n d N o 0 3 8 0 9 3 7 1 C H A R N W O O D B i s h o p s W a y N e w p o r t I s l e o f W i g h t P O 3 0 5 W S U n i t e d K i n g d o m T 4 4 0 1 9 8 3 5 3 7 7 9 9 F 4 4 0 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d a j w e l l s c o u k w w w c h a r n w o o d c o m ...

Reviews: