background image

HEALTH AND SAFETY

PRECAUTIONS

PERFORMANCE

Please take care when installing the
stove that the requirements of the
Health and Safety at Work Act 1974
are met.

Some types of fire cement are caustic
and should not be allowed to come
into contact with the skin. In case of
contact wash with plenty of water.

If there is a possibility of disturbing
any asbestos in the course of
installation then please use appropriate
protective equipment.

There must not be an extractor fan
fitted in the same room as the stove as
this can cause the appliance to emit
fumes into the room.

There must be an adequate air supply
into the room in which the appliance is
installed totalling at least 100 square
cm. (16 square inches) to provide
combustion air. This is particularly
necessary if the room is double glazed.

Do not light the fire before the boiler
has been connected to the system and
filled with water, as this can cause
serious damage to the boiler.

In addition to these instructions the
requirements of BS.8303 and BS.6461
Pt 1&2; 1984 must be fulfilled. Local
Authority Bylaws and Building
Regulations regarding the installation
of Solid Fuel burning appliances, flues
and chimneys must also be observed.

The output of the Country 15B is 13.0
kW (44,400 Btu/h) to water and 2.5
kW (8,500 Btu/h) to the room. The
outputs were obtained burning
smokeless fuel over a four hourly re-
fuelling cycle with the doors closed.

The heat output to the room is directly
proportional to the heat output to
water as shown in Fig. 4. This means
that if the water heating load is less
than the rated output then the room
heating will be reduced by the same
proportion. This must be borne in
mind when calculating the heating
requirements.

CHIMNEY

In order for the appliance to perform
satisfactorily the chimney height must
not be less than 4 metres measured
vertically from the outlet of the stove
to the top of the chimney. The internal
dimensions of the chimney should
preferably be 175 mm (7 inches) or
200mm (8 inches) either square or
round and MUST NOT BE LESS
THAN 150 mm (6 INCHES).

If an existing chimney is to be used it

must be swept and checked, it must be
in good condition, free from cracks
and blockages, and should not have an
excessive cross sectional area (e.g.
greater than 250mm x 250mm). If you
find that the chimney is in poor
condition then expert advice should be
sought regarding the necessity of
having the chimney lined. If it is
found necessary to line the chimney
then a lining suitable for Solid Fuel
must be used.

If there is no existing chimney then a
prefabricated block chimney or a twin
walled insulated stainless steel flue to
BS.4543 can be used either internally
or externally. These chimneys must be
fitted in accordance with the
manufacturers instructions and
Building Regulations.

Single wall flue pipe is suitable for
connecting the stove to the chimney
but is not suitable for using for the
complete chimney.

If it is found that there is excessive
draw in the chimney then a draught
stabilizer should be fitted.

It is important that there is sufficient
draw in the chimney and that the
chimney does not suffer from down-
draught. When the chimney is warm
the draw should be not less than 2.54
mm (0.10 inches) water gauge. If in
doubt about the chimney seek expert
advice.

The stove must stand on a fireproof
hearth and must be situated at least
300mm (12 inches) from any
combustible material. The positioning
of the stove and the size of the hearth
are governed by building regulations
for Class 1 appliances. These building
regulations state that the hearth must
extend in front of the stove by at least
300mm (12 inches) and to the sides of
the stove by at least 150mm (6
inches). If in doubt as to the
positioning of the stove expert advice
should be sought either from the
supplier or the local building
inspector.

The fireplace must allow good
circulation of air around the appliance
to ensure that maximum heat is
transferred to the room and also to
prevent the fireplace from
overheating. A gap of 150mm (6
inches) each side and 300mm (12
inches) above the appliance should
give sufficient air circulation. If a
wooden mantelpiece or beam is used
in the fireplace it should be a
minimum of 460mm (18 inches), and
preferably 600mm (24 inches) from
the appliance. In some situations it
may be necessary to shield the beam
or mantelpiece to protect it.

The central heating system must
comply with BS:5449 part 1.

If the system is to be a combined
heating and domestic hot water system
then a double feed indirect hot water
storage cylinder to BS:1556 part 1
should be used. In order to prevent the
build up of scale and corrosion a

HEARTH AND FIRE

SURROUND

CENTRAL HEATING

SYSTEM

INSTALLATION INSTRUCTIONS FOR THE

CHARNWOOD COUNTRY 15B

2.0

4.0

6.0

8.0

10.0

12.0

14.0

0

1.0

2.0

3.0

0

Boiler

Output

Space Output

(kW)

(kW)

Fig. 4. Performance Chart

Page 5

Country 15B 09/03

Summary of Contents for Country 15B

Page 1: ...stallation Instructions C H A R N W O O D B i s h o p s W a y N e w p o r t I s l e o f W i g h t P O 3 0 5 W S U n i t e d K i n g d o m T 4 4 0 1 9 8 3 5 3 7 7 9 9 F 4 4 0 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d a j w e l l s c o u k w w w c h a r n w o o d c o m ...

Page 2: ...At first you may find it helpful to try several fuels to find the most suitable If you are unable to obtain the fuel you want ask your supplier or an approved fuel distributor to suggest an alternative Use the door opening and ashpan tool to open and close the doors Turn the right hand door knob anti clockwise to open and clockwise to close see Fig 1 Your Charnwood stove is fitted with a multifuel...

Page 3: ...ld be emptied regularly before it becomes too full Never allow the ash to accumulate in the ashpans so that it comes in contact with the underside of the grate as this will seriously damage the grate bars The ashpans are handled using the tool provided Care should be taken to ensure that ash is cool before emptying it into plastic liners or bins To make ash removal easier there is a special availa...

Page 4: ... appliance flue outlet and the flue pipe connecting the stove to the chimney must be cleaned with a flue brush After clearing any soot from within the stove replace the throat plate see Fig 3 the front firebars and side fireplates Different types of sweep s brushes are available to suit different flueways For standard brick chimneys a wire centre sweep s brush fitted with a guide wheel is recommen...

Page 5: ... suitable fuel is being used d the fire is not fitted onto a heating system which is too large Do not light the fire if there is any possibility that any parts of the system may be frozen Check that a the fire is burning properly if not then carry out the checks under Fire Will Not Burn b the throat plate is fitted correctly see Fig 3 and that it is not distorted c the door seals are in good condi...

Page 6: ...t advice should be sought regarding the necessity of having the chimney lined If it is found necessary to line the chimney then a lining suitable for Solid Fuel must be used If there is no existing chimney then a prefabricated block chimney or a twin walled insulated stainless steel flue to BS 4543 can be used either internally or externally These chimneys must be fitted in accordance with the man...

Page 7: ... as it will allow greater flexibility in the way that the system is operated as well as ensuring that there is sufficient heat Connect the heating system to the boiler ensuring that the primary flow pipe rises continuously from the appliance to the vent Fill the system with water and check for leaks The circulating pump may be controlled by means of time switches room thermostats or outdoor thermo...

Page 8: ...ld on the clamping plate is in line with the lugs on the firebox as shown in Fig 12 Ensure the clamping plate does not prevent the throat plate from seating correctly All flue connections must be well sealed Various types and positions of soot doors are shown in figures 8 to 10 Before lighting the fire check the cold setting distance of the thermostat Remove the cover plate on the left hand side o...

Page 9: ...llowing a suitable period of time for the fire cement and mortar to dry out the stove should be lit and checked to ensure that smoke and fumes are taken from the appliance up the chimney and emitted safely Also check all joints and seals The central heating pump should be COMMISSIONING adjusted to give the correct water flow against the circuit resistance and the system should be correctly balance...

Page 10: ...Knob 10 012 FV14 1 Secondary Air Slide 45 012 FV10B 19 Thermostat Cover 11 012 FV14 2 Secondary Air Slide Guide 46 012 FV11 Serial No Label 12 012 FV14 3 Secondary Air Slide Retainer 47 012 FW34 Scraper Tool 13 012 FV14 4 Secondary Air Cover 48 010 TW33 Vert Rear Flue Connector Opt l Extra 14 004 FV15 Secondary Air Rod 49 010 BW51 Ash Carrier Optional Extra 15 002 EW15 Side Fire Plate 50 008 TH02 ...

Page 11: ... a y N e w p o r t I s l e o f W i g h t P O 3 0 5 W S U n i t e d K i n g d o m T 4 4 0 1 9 8 3 5 3 7 7 9 9 F 4 4 0 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d a j w e l l s c o u k w w w c h a r n w o o d c o m Your Local Charnwood Dealer ...

Reviews: