iQ-T  

Digital Thermostat with Remote Sensor & Auto Adapt-PID

 

5°C-90°C 

 

Installer’s and User’s Manual 

 

Important Safety Information 

 

Read carefully the information included in this manual. 

 

Always switch off the main power when installing the thermostat. 

 

The installation should be carried out by authorized personnel. 

 

Do not use the thermostat for other applications except those that is made to be used 
i.e. hot water preparation  

 

This thermostat is not an instrument. It must not be used in life critical applications. 

 
Installation 

Install the thermostat always in an inside moisture free wall. 

 

Start from removing the thermostat base. Drill appropriate holes on the wall, then place, 
align and screw them. 
Continue with the electrical connections. 
 

Wiring

 

Remove the terminal blocks found on the rear window of the thermostat. Consult the 
electrical wiring figure on the back of the device or the next picture and make all the 
necessary wirings according to the application. 
As it happens on every electrical device this thermostat requires power to operate. Connect 
the phase “L” (1), the neutral “N” (2) of the 230VAC/50Hz electrical net. Terminal (3) is the 
commissioning output for heating or cooling system. 
On the 2-pole terminal block a sensor of RS301k5 or RS1501k5 or XRS0101k5 type must be 
connected without polarity. Sensor’s cable can be lengthen up to 50m by a separate 2 wire 
cable with minimum cross section 0.5mm2. 

Connection of any wire that carries potential of any type is prohibited for sensor’s 
terminal block. 

Once electrical connections are complete plug in the terminal blocks on the back of the 
device and reinsert the front part on the thermostat base starting from the upper side. 
 

 

 

Figure 3 Electrical connections

 

Operation

 

There are three buttons, three luminous indicators and one matrix led display on the front 
of the device. 
In the following figure the meaning and numbering of all this items is shown. 
 

 

 

(1)

 

On-Of button 

(2)

 

Installer’s menu button 

(3)

 

Decrease button 

(4)

 

Increase button 

(5)

 

Operation status indicator (On) 

(6)

 

Commissioning output enable indicator 

(7)

 

Cooling mode indicator 

(8)

 

LED display 

 

Temperature is shown on the display in Celsius degrees. 

On-Off, Delayed shut off 

When button (1) is momentarily pressed thermostat switches between On and Off states 
while showing the respective messages. In On state the (5) indicator is on and 
temperature control is performed. In Off state no temperature control is performed. 
From time to time a “ZZZ” message is passing through the display indicating the sleeping 
state of the device. 

When (1) button is contiguously pressed in On state the delayed shut off time is shown in 
predefined time steps 30min, 1h, 2h … 6h. Once the time of your choice is shown release 
button (1). Then thermostat will initiate the countdown until shut off delay will pass and 
switch to the Off state. During that process the (5) indicator is flashing.  

Setpoint adjust 

Once the increase (4) or decrease (3) button is pressed SET message is shown and after 
that the current setpoint. You can alter the setpoint by using the same keys. Few seconds 
after stop pressing any button thermostat memorizes the new setting and returns to the 
normal operation. 

Invoke Installer’s Menu 

Press contiguously (2) button to enter the installer’s menu where useful parameters for 
the operation can be found. The meaning of those parameters are explained below. 
 

Sensor malfunction detection 

This thermostat always performs sensor health test against short circuit, open circuit or 
other malfunctions that can be detected. When such fault occur thermostat shows the 
message “Err” and interrupts its operation. 

    

Installer’s Menu 

Installer’s menu can be invoked by the contiguous press of button (2). Critical operation 
parameters can be adjusted inside that menu. Alteration of those parameters is only 
advised for expert technicians. 
When entered on the installer’s menu the name (mnemonic) of the first parameter (P-n) is 
shown. 
Use the (3) and (4) keys to navigate to the parameter of your desire. Then press key (1) and 
the respective value is shown. Use the (3) or (4) keys to alter the value of the parameter. 
Value is automatically sored after a while when pressing no key or by pressing the (1) key.  
 
To exit inataller’s menu navigate to the End parameter mnemonic and press (1) key or leave 
the device without pressing any key for some time. 
 

Parameter 

Minimum 

Maximum 

Preset 

P-n 

000 

(heating 

mode) 

001 

(cooling mode) 

000 
(heating mode) 

Mod 

000 (On-Off) 

001 (Auto Adapt PID) 

000 (On-Off) 

TRI 

Measu/- 5°C 

dT 

0.1°C 

10°C 

3°C 

SHi 

SLo 

90°C 

90°C 

SLo 

5°C 

SHi 

5°C 

Pbn 

1°C 

5°C 

2°C 

HCT 

1min 

20min 

10min 

STP 

20 

10 

RST 

Restore preset values 

End 

Exit from installer’s menu 

 

P-n 

Defines if the device will perform as cooling (001) or heating (000) thermostat. 
In heating mode heating system is commissioned when temperature is below the 
setpoint (figure 2). 

 

Figure 4- Heating mode 

In cooling mode the cooling system is commissioned when temperature is over the 
setpoint (figure 3). 

(8) 

(4) 

(3) 

(2) 

(1) 

(7) 

(6) 

(5) 

Summary of Contents for iQ-T

Page 1: ... παρατεταμένα το πλήκτρο 1 και ενώ ο θερμοστάτης βρίσκεται στην κατάσταση On εμφανίζεται ο χρόνος της αυτόματης απενεργοποίησης σε προκαθορισμένα διαστήματα 30min 1h 2h 6h Όταν εμφανιστεί ο χρόνος της επιλογής σας αφήστε το πλήκτρο 1 και ο θερμοστάτης θα αρχίσει την αντίστροφη μέτρηση στο τέλος της οποίας θα μεταβεί αυτόματα στην κατάσταση Off Κατά την αντίστροφη μέτρηση ο ενδείκτης 5 αναβοσβήνει ...

Page 2: ...όλοιπα STP Βήμα ολοκλήρωσης Έχει εφαρμογή μόνο εφόσον ο θερμοστάτης λειτουργεί με τον τρόπο Auto Adapt PID Mod 001 Η παράμετρος ρυθμίζεται αυτόματα όταν τροποποιήσετε την παράμετρο HCT Είναι δυνατό όμως να τροποποιηθεί και μόνη της Όσο μεγαλύτερη είναι η παράμετρος αυτή τόσο πιο αργή είναι η διόρθωση που κάνει ο θερμοστάτης για να επιτύχει την επιθυμητή θερμοκρασία χώρου Υπερβολικά μικρή τιμή της ...

Page 3: ...erformed In Off state no temperature control is performed From time to time a ZZZ message is passing through the display indicating the sleeping state of the device When 1 button is contiguously pressed in On state the delayed shut off time is shown in predefined time steps 30min 1h 2h 6h Once the time of your choice is shown release button 1 Then thermostat will initiate the countdown until shut ...

Page 4: ...arately The bigger the value of the STP parameter the slower the temperature correction performed by the thermostat Excessively small STP values can lead to opposite control result or even loss of control RST Select this parameter in order to restore all values to the factory preset setting End Exit form installer s menu Technical Characteristics subject to alteration without prior notice Physical...