Performance Data - High & medium temperature models

For additional capacity sizes and options, please contact the factory at 800-1-1881

r- models - High & medium temperature

85°F Entering Water, 105°F Condensing Temperature, 5°F Subcooling

r-

model

compressor

Suction temperature °F

15°F

0°F

5°F

0°F

5°F

0°F

SWN0075H2

KAN1-0075

BtuH

GPm

PSIG

5,090

0.9
0.2

5,860

1.0
0.3

6,700

1.2
0.4

7,620

1.3
0.5

8,620

1.5
0.7

9,740

1.7
0.8

SWN0075M2

KAE1-0075

BtuH

GPm

PSIG

6,310

1.2
0.4

7,130

1.3
0.5

8,000

1.5
0.7

-
-
-

-
-
-

-
-
-

SWN0090H2

KARA-010E

BtuH

GPm

PSIG

7,370

1.4
0.6

8,330

1.6
0.8

9,370

1.8
1.0

10,510

2.1
1.3

11,740

2.3
1.6

13,170

2.6
2.1

SWN0100H2

KAM1-0100

BtuH

GPm

PSIG

8,380

1.6
0.7

9,480

1.8
0.9

10,690

2.0
1.2

12,040

2.3
1.5

13,430

2.6
1.9

15,070

2.9
2.5

SWN0150H2

KAGA-0150

BtuH

GPm

PSIG

9,450

1.8
1.0

10,760

2.1
1.3

12,150

2.4
1.7

13,630

2.7
2.2

15,270

3.1
2.8

17,090

3.5
3.6

SWN0200H2

ERA1-0200

BtuH

GPm

PSIG

11,170

2.5
0.2

13,530

3.1
0.3

16,090

3.7
0.5

18,810

4.4
0.7

21,780

5.3
1.0

24,980

6.2
1.3

SWN0200M2

ERC1-0200

BtuH

GPm

PSIG

14,810

3.4
0.4

17,020

3.9
0.5

19,480

4.6
0.7

-
-
-

-
-
-

-
-
-

SWN0300H2

ERF1-0311

BtuH

GPm

PSIG

22,400

4.7
0.8

25,220

5.3
1.0

28,290

6.1
1.3

31,620

6.9
1.7

35,260

7.9
2.2

39,310

9.1
2.8

SWN0400H2

NRB2-0400

BtuH

GPm

PSIG

30,490

7.3
1.9

35,110

8.7
2.6

40,130

10.3

3.6

45,460

12.3

5.0

51,300

14.8

7.0

57,910

17.9
10.0

SWN0499H2

2DC3R53KE

BtuH

GPm

PSIG

35,930

7.5
1.5

40,900

8.8
2.0

46,230

10.2

2.7

52,020

11.8

3.6

58,320

13.8

4.9

65,090

16.1

6.5

SWN0500H2

2DD3R63KE

BtuH

GPm

PSIG

42,080

9.4
2.3

47,710

11.0

3.1

53,810

12.8

4.2

60,370

15.0

5.7

67,500

17.7

7.9

75,240

21.0
10.9

SWN0750H2

2DL3R78KE

BtuH

GPm

PSIG

53,450

9.0
1.5

60,320

10.3

1.9

67,750

11.6

2.5

75,700

13.2

3.1

84,310

14.9

4.0

93,690

16.9

5.1

SWN0760H2

2DA3R89KE

BtuH

GPm

PSIG

60,580

10.6

2.1

68,420

12.1

2.7

76,770

13.8

3.4

85,690

15.7

4.4

95,330

17.9

5.6

105,680

20.4

7.3

SWN0761H2

3DA3R10ME

BtuH

GPm

PSIG

74,160

13.9

3.5

83,130

15.9

4.5

92,810

18.1

5.8

103,270

20.7

7.5

114,800

23.8

9.8

127,100

27.5
13.0

SWN1000H2

3DB3R12ME

BtuH

GPm

PSIG

88,710

20.7

1.0

99,020

23.6

1.3

110,190

27.0

1.7

122,490

31.2

2.3

135,300

35.8

2.9

149,650

41.5

3.9

SWN1500H2

3DS3R17ME

BtuH

GPm

PSIG

117,310

25.6

0.8

131,200

29.3

1.1

146,060

33.5

1.4

161,950

38.3

1.8

179,890

44.2

2.3

198,850

51.1

3.0

SWN2000H2

4DA3R18ME

BtuH

GPm

PSIG

124,230

27.6

0.9

139,910

32.0

1.2

156,830

37.2

1.7

176,300

43.6

2.2

197,310

51.3

3.0

219,860

60.6

4.2

Summary of Contents for SWN0075H2

Page 1: ...CH WCUTB April 2007 Replaces CH B 41C 10 03 Water Cooled Condensing Units Technical Guide Model SWN Semi Hermetic Reciprocating Compressor ...

Page 2: ...2 5 Performance Data Medium Low Temperature R 404A R 507 6 Electrical Data 7 9 Physical Data 10 11 Nomenclature S W N 0500 H 2 C Application H High Temp M Med Temp L Low Temp E Extra Low Temp Model Size Semi Hermetic Reciprocating Water Cooled Indoor Refrigerant 2 R 22 6 R 404A R 507 Voltage B 208 230 1 60 G 230 1 60 C 208 230 3 60 D 460 3 60 ...

Page 3: ...il separator replaceable core suction filter and liquid solenoid valve More spacious pre painted electrical box Pump down switch 230 volt control circuit transformer on 460 volt models Semi hermetic reciprocating compressors Captive door fasteners Single electrical connection location Shipped with dry nitrogen charge Heavy duty base plate Plastic conduit on all wiring runs Shell and tube cleanable...

Page 4: ...sing unit is specifically designed for use in supermarket restaurant warehouse and other commercial and industrial applications The design focuses on ease of installation and maintenance along with the flexibility to fit most application requirements Standard Features Fixed low pressure switch adjustable on low temp models Fixed high pressure switch Pump down switch Compressor contactor and contro...

Page 5: ... BTUH GPM PSIG 22 400 4 7 0 8 25 220 5 3 1 0 28 290 6 1 1 3 31 620 6 9 1 7 35 260 7 9 2 2 39 310 9 1 2 8 SWN0400H2 NRB2 0400 BTUH GPM PSIG 30 490 7 3 1 9 35 110 8 7 2 6 40 130 10 3 3 6 45 460 12 3 5 0 51 300 14 8 7 0 57 910 17 9 10 0 SWN0499H2 2DC3R53KE BTUH GPM PSIG 35 930 7 5 1 5 40 900 8 8 2 0 46 230 10 2 2 7 52 020 11 8 3 6 58 320 13 8 4 9 65 090 16 1 6 5 SWN0500H2 2DD3R63KE BTUH GPM PSIG 42 0...

Page 6: ...601L6 3DA3F28KE BTUH GPM PSIG 18 260 4 5 0 5 25 200 6 3 1 0 29 190 7 4 1 4 33 600 8 6 2 0 43 680 11 8 3 6 55 760 16 5 6 8 SWN0750L6 3DB3F33KE BTUH GPM PSIG 21 670 4 3 0 4 30 030 5 9 0 7 34 760 6 8 0 9 39 800 7 7 1 1 51 560 10 1 1 9 65 840 13 1 3 1 SWN0900L6 3DF3F40KE BTUH GPM PSIG 26 440 6 1 0 1 36 440 8 4 0 2 42 210 9 8 0 2 48 620 11 3 0 3 63 210 15 1 0 6 80 750 20 1 1 0 SWN1000L6 3DS3F46KE BTUH ...

Page 7: ...0 1 3 15 0 15 SWN0200M6C 208 230 3 60 ERCA 021E 7 9 46 0 15 0 15 20 1 6 25 0 25 SWN0300H2G 230 1 60 ERF2 0310 15 6 86 0 20 0 35 20 1 6 25 5 40 40 1 12 50 0 50 SWN0300H2C 208 230 3 60 ERF1 0311 11 2 82 0 15 0 25 20 1 6 25 0 30 40 1 12 50 0 50 SWN0300H2D 460 3 60 ERF1 0311 5 2 41 0 15 0 15 10 1 3 15 0 15 20 1 6 25 0 25 SWN0310M6G 230 1 60 ERFB 031E 15 3 86 0 20 0 30 20 1 6 25 1 40 40 1 12 50 0 50 SW...

Page 8: ...0 3 60 2DL3R78KE 28 3 169 0 35 4 60 40 1 12 50 0 70 70 2 16 87 5 90 SWN0750H2D 460 3 60 2DL3R78KE 12 4 85 0 20 0 25 20 1 6 25 0 30 40 1 12 50 0 50 SWN0760H2C 208 230 3 60 2DA3R89KE 28 7 169 0 35 9 60 40 1 12 50 0 70 70 2 16 87 5 90 SWN0760H2D 460 3 60 2DA3R89KE 12 6 85 0 20 0 25 20 1 6 25 0 30 40 1 12 50 0 50 SWN0761H2C 208 230 3 60 3DA3R10ME 36 8 215 0 46 0 80 40 1 12 58 0 90 70 2 16 87 5 90 SWN0...

Page 9: ... 6 36 1 60 40 1 12 50 0 60 SWN0601L6D 460 3 60 3DA3F28KE 10 8 77 0 15 0 20 10 1 3 20 0 25 20 1 6 25 0 30 SWN0750L6C 208 230 3 60 3DB3F33KE 27 6 161 0 34 5 60 40 1 12 50 0 70 70 2 16 87 5 90 SWN0750L6D 460 3 60 3DB3F33KE 14 1 83 0 20 0 30 20 1 6 25 0 35 40 1 12 50 0 50 SWN0900L6C 208 230 3 60 3DF3F40KE 33 2 215 0 41 5 70 40 1 12 53 5 80 70 2 16 87 5 90 SWN0900L6D 460 3 60 3DF3F40KE 15 0 106 0 20 0 ...

Page 10: ...bmittal drawings for exact model dimensions Horsepower A B C D E 3 4 to 2 33 23 3 4 37 3 8 10 5 8 12 3 to 4 38 3 8 26 3 4 36 3 8 13 1 2 12 5 to 6 42 1 2 30 3 8 39 1 4 14 12 7 1 2 to 22 55 1 2 35 3 8 41 1 2 36 12 Maximum Dimensions with Options ...

Page 11: ...00H2 2DD3 050E 1 3 8 5 8 1 1 4 1 1 4 39 39 25 30 38 42 50 400 SWN0500M6 2DC3 050E 1 3 8 5 8 1 1 4 1 1 4 34 39 25 30 38 42 50 400 SWN0750H2 2DL3 075E 1 3 8 5 8 1 1 4 1 1 4 60 41 50 35 38 55 50 465 SWN0760H2 2DA3 075E 1 3 8 5 8 1 1 4 1 1 4 60 41 50 35 38 55 50 465 SWN0761H2 3DA3A075E 1 3 8 5 8 1 1 4 1 1 4 60 41 50 35 38 55 50 465 SWN1000H2 3DB3A100E 1 5 8 7 8 1 1 4 1 1 4 66 41 50 35 38 55 50 715 SWN...

Page 12: ...A Brand of Heatcraft Refrigeration Products LLC 2175 West Park Place Blvd Stone Mountain GA 30087 800 321 1881 FAX 770 465 5990 www chandlerref com CH WCUTB 0407 Version 001 ...

Reviews: