MAINTENANCE
27
© 2015 Champion Power Equipment
Part No. 101306 Rev. A
RETURN TO SERVICE AFTER
STORAGE
1. Make sure the utility power to the transfer switch is off.
2. The engine control module switch and the ATS control
module switch should be in the OFF position.
3. Check the engine oil level. Add oil if needed.
4. Recharge the batteries to 100% state of charge. If the
batteries will not fully charge, replace the batteries.
!
WARNING
!
Always connect the positive
(+) battery cable
fi
rst. After the
positive cable is connected, then
the negative (-) battery cable can
be attached. This minimizes the
possibility of electrical contact.
5. Connect the positive (+) battery cable to the positive
(+) battery terminal
fi
rst and then connect the negative
battery cable to the negative (-) battery terminal.
6. Clean and wipe down the generator with mild soap and
water.
7. Turn the fuel shutoff valve to the ON position.
8. Turn the engine control module switch to the manual
position. The engine should start. Run the engine for 15
minutes to allow it to warm up. The fuel system might
require more than one start cycle to fully pressurize the
fuel system for operation.
9. Make sure there are not any active fault codes.
10. Turn the engine control module switch to the OFF position
to shut off the engine.
11. Turn the ATS module switch to the AUTO position.
12. Turn on the utility power to the transfer switch. The utility
LEDs on the ATS module should be lit.
13. Turn the engine control module switch to the ATS position.
14. Set the exercise time.
See EXERCISE SWITCH on pages
16 and 17.