Champion Power Equipment 100519 Operator'S Manual Download Page 18

100519 - 6250W OPEN FRAME INvERTER

OPERATION

18

 

WARNING

Pouring gasoline too fast through the fuel screen may result 
in gasoline splashing over the generator and operator while 
filling.

 

NOTICE

The generator engine works well with 10% or less ethanol 
blend gasoline. When using ethanol-gasoline blends there 
are some issues worth noting:

 

Ethanol-gasoline blends can absorb more water than 
gasoline alone. 

 

These blends can eventually separate, leaving water or 
a watery goo in the tank, fuel valve and carburetor. The 
compromised gasoline can be drawn into the carburetor 
and cause damage to the engine and/or potential 
hazards. 

 

If a fuel stabilizer is used, confirm that it is formulated to 
work with ethanol-gasoline blends.

 

Any damages or hazards caused by using improper 
gasoline, improperly stored gasoline, and/or 
improperly formulated stabilizers, are not covered by 
manufacturer’s warranty. 

It is advisable to always shut off the gasoline supply and 
run the engine to starvation after each use. See Storage 
instructions for extended non-use.

Grounding

Your generator must be properly connected to an appropriate 
ground to help prevent electric shock.

 

WARNING

Failure to properly ground the generator can result in 
electric shock.

A ground terminal connected to the frame of the generator has 
been provided (see 

Controls and Features

 for terminal location). 

For remote grounding, connect of a length of heavy gauge 
(12 AWG minimum) copper wire between the generator ground 
terminal and a copper rod driven into the ground. We strongly 
recommend that you consult with a qualified electrician to 
ensure compliance with local electrical codes.

Neutral Floating*

 

Neutral circuit 

IS NOT

 electrically connected to the frame/

ground of the generator.

 

The generator (stator winding) is isolated from the frame 
and from the AC receptacle ground pin.

 

Electrical devices that require a grounded receptacle pin 
connection will not function if the receptacle ground pin is 
not functional.

Neutral Bonded to Frame*

 

Neutral circuit 

IS

 electrically connected to the frame/ground 

of the generator.

 

The generator system ground connects lower frame 
cross-member below the alternator. The system ground is 
connected to the AC neutral wire.

* See your model’s control panel for specified type of grounding.

OPERATION

Generator Location

NEVER operate the generator inside any building, including 
garages, basements, crawlspaces and sheds, enclosure or 
compartment, including the generator compartment of a 
recreational vehicle. Please consult your local authority. In 
some areas, generators must be registered with the local 
utility. Generators used at construction sites may be subject 
to additional rules and regulations. Generators should be on 
a flat, level surface at all times. (Even while not in operation) 
Generators must have at least 5 ft. (1.5 m) of clearance from 
all combustible material. In addition to clearance from all 
combustible material, generators must also have at least 3 ft. 
(91.4 cm) of clearance on all sides to allow for adequate cooling, 
maintenance and servicing. Generators should never be started 
or operated in the back of a SUV, camper, trailer, in the bed of 
a truck (regular, flat or otherwise), under staircases/stairwells, 
next to walls or buildings, or in any other location that will not 
allow for adequate cooling of the generator and/or the muffler. 
DO NOT contain generators during operation. Allow generators 
to properly cool before transport or storage.

Place the generator in a well-ventilated area. DO NOT place the 
generator near vents or intakes where exhaust fumes could 
be drawn into occupied or confined spaces. Carefully consider 
wind and air currents when positioning generator.

Failure to follow proper safety precautions may void 
manufacturer’s warranty.

 

WARNING

Do not operate or store the generator in rain, snow, or wet 
weather.

Using a generator or electrical appliance in wet conditions, 
such as rain or snow, or near a pool or sprinkler system, 
or when your hands are wet, could result in electrocution.

Summary of Contents for 100519

Page 1: ...ns important safety precautions which should be read and understood before operating the product Failure to do so could result in serious injury This manual should remain with the product Specificatio...

Page 2: ...the Engine 19 Connecting Electrical Loads 20 Do Not Overload Generator 20 GFCI 21 Eco Economy Mode 21 12V DC Automotive Style Outlet 21 Stopping the Engine 22 Operation at High Altitude 22 Moving the...

Page 3: ...s exercise common sense and always err on the side of caution when operating the product to ensure no accident property damage or injury occurs We want you to continue to use and be satisfied with you...

Page 4: ...g parts can entangle hands feet hair clothing and or accessories Traumatic amputation or severe laceration can result Keep hands and feet away from rotating parts Tie up long hair and remove jewelry D...

Page 5: ...result When starting engine pull the starter cord slowly until resistance is felt and then pull rapidly to avoid kickback DO NOT start or stop the engine with electrical devices plugged in and turned...

Page 6: ...m the gasoline tank Only fill or drain gasoline outdoors in a well ventilated area DO NOT pump gasoline directly into the generator at the gas station Always use an approved fuel container to transfer...

Page 7: ...K 109 Colors LPN 1110 L OP Rev B Size 46 x 46 mm Artwork Notes 3mm corner radius 2mm safe margin white to be printed shown in 50 process magenta Revision Changes Changed Octane rating from 85 to 87 20...

Page 8: ...re operation Electric Shock Failure to use in dry conditions and to observe safe practices can result in electric shock Improper connections to a building can allow current to backfeed into utility li...

Page 9: ...you to more safely operate the product SYMBOL MEANING ON STOP or OFF Choke Pull choke knob to CHOKE position Run Push choke knob to RUN position AC Reset Output OK Overload ECO Economy Mode Switch SY...

Page 10: ...ed by or for outside parties without the explicit consent of Champion Power Equipment K 376 186 152 CG1 2945 Colors Starting the Engine DANGER Move generator outside and far away from windows doors an...

Page 11: ...to lift or carry the unit 3 Fuel Valve Used to turn fuel supply on and off to engine 4 Air Filter Protects the engine by filtering dust and debris from the intake air 5 Recoil Starter Used to manuall...

Page 12: ...down and not run Check oil level 9 Circuit Breakers Push Reset Protects the generator against electrical overloads RECEPTACLES A z 12V DC 8 Amp Automotive May be used to supply electrical power for op...

Page 13: ...rtz Example 60 0 hertz Run Time R Run time of the generator for the current session Example 6 hours Total Run Time Total run time of the generator since first operation Example 16 hours Intelligauge F...

Page 14: ...accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment do...

Page 15: ...r NOTICE DO NOT attempt to run generator without first removing the shipping support brackets Damage to the generator as a result of not removing the brackets will void the warranty 1 BEFORE filling t...

Page 16: ...chart for recommended oil type 20 0 20 40 60 Ambient temperature Recommended Engine Oil Type 80 100 120 28 9 F C 17 8 6 7 4 4 15 6 26 7 37 8 48 9 10W 30 5W 30 Full Synthetic 10W 40 5W 30 1 Place the...

Page 17: ...n expand after filling A minimum of in 6 4 mm of space left in the tank is required for gasoline expansion although more than in 6 4 mm is recommended Gasoline can be forced out of the tank as a resul...

Page 18: ...n will not function if the receptacle ground pin is not functional Neutral Bonded to Frame Neutral circuit IS electrically connected to the frame ground of the generator The generator system ground co...

Page 19: ...come in single or multi outlet styles They re designed to protect against virtually all short duration voltage fluctuations Starting the Engine 1 Make certain the generator is on a flat level surface...

Page 20: ...enerator during an outage please notify your electric utility company immediately and remember to plug your appliances directly into the generator Do not plug the generator into any electric outlet in...

Page 21: ...he receptacle to restore the flow of electricity If the indicator light does not come back on or if the GFCI cannot be reset then it must be replaced B C A Eco Economy Mode The Eco Mode switch can be...

Page 22: ...enerator Stopping the Engine 1 Turn off and unplug all electrical connected loads Never start or stop the generator with electrical devices plugged in or turned on 2 Let the generator run at no load f...

Page 23: ...slightly off the ground until balanced on the wheels 3 While maintaining balance roll the generator to the desired location NEVER tilt sideways while moving the generator Failure to follow these inst...

Page 24: ...evel DO NOT screw in the dipstick while checking Cleaning and Adjusting the Spark Plug 1 Remove the spark plug cable from the spark plug 2 Use a spark plug socket tool not included or a 13 16 in 21 mm...

Page 25: ...is equipped with a spark arrestor Adjusting the Governor WARNING Tampering with the factory set governor will void your warranty The air fuel mixture is not adjustable Tampering with the governor can...

Page 26: ...o the OFF 5c Use the drain bolt on the carburetor to empty any excess gasoline from the carburetor into an appropriate container Use a funnel and appropriate hose if necessary under the carburetor dra...

Page 27: ...emoving from storage 1 Be sure the engine switch is in the OFF position 2 Add gasoline to the generator according to Add Fuel Gasoline 3 Turn the fuel valve to the ON position 4 After 5 minutes check...

Page 28: ...ature Recommended Engine Oil Type 80 100 120 28 9 F C 17 8 6 7 4 4 15 6 26 7 37 8 48 9 10W 30 5W 30 Full Synthetic 10W 40 5W 30 NOTICE Temperature will affect engine oil and engine performance Change...

Page 29: ...Generator is overloaded Review load and adjust See Connecting Electrical Loads Dirty air filter Clean or replace air filter Choke in wrong position Move choke until it stops under RUN position or pus...

Page 30: ...beyond the product s limits modified installed improperly or connected incorrectly to any electrical component Normal maintenance is not covered by this warranty and is not required to be performed a...

Page 31: ...condition exits CPE will repair your small off road engine SORE and equipment at no cost to you including diagnosis parts and labor MANUFACTURER S WARRANTY COVERAGE This Emissions Control System is w...

Page 32: ...shall be warranted for the period of time prior to the first scheduled replacement point for that part If the part fails prior to the first scheduled replacement the part shall be repaired or replace...

Page 33: ...Mounting Brackets Carburetor Purge Port Connector TO OBTAIN WARRANTY SERVICE You must take your CPE engine or the product on which it is installed along with your warranty registration card or other p...

Reviews: