Power from
Control Panel

Terminal Strip

LMEOLR1224
12/24 Vdc EOL
Relay

IMPORTANT: 

When using 4-wire smoke detectors with this

device, the smoke detectors must be powered from a source
other than the release device, such as an approved UL1481
regulated power supply providing battery backup support.

Power from
Control Panel

Purple

N/C

N/C

C

C

(+)

(–)

(–)

(+)

(–)

(+)

(–)

(+)

3

4

+

Power from
Control Panel

NOTE

: Follow this method of attachment when using LM4W-B,

LM4WT-B, or other N/O 4-wire smoke detectors.

NOTE

: Generic version of a N/C

4-wire smoke detector is shown.

– IN/OUT

+ OUT

 + IN

– IN/OUT

+ OUT

 + IN

3

4

+

(–)

(+)

3

4

 COM

 NO

 – IN/OUT

 + OUT

 + IN

 COM

 NO

 – IN/OUT

 + OUT

 + IN

+

10k Ohm @1/2 watt
Supervisory Resistor
(LMEOLRES-10)

10k Ohm @1/2 watt
Supervisory Resistor
(LMEOLRES-10)

10k Ohm @1/2 watt
Supervisory Resistor
(LMEOLRES-10)

Terminal Strip

Terminal Strip

Power from
Control Panel

LMEOLR1224
12/24 Vdc EOL
Relay

LMEOLR1224
12/24 Vdc EOL
Relay

NOTE:

Follow this method

of attachment when using
LM2W-B, LM2WT-B, or
other 2-wire 24Vdc smoke
detectors.

24Vdc Power from
Terminal Strip

NOTE

: Follow this method of attachment when using LM4W-B,

LM4WT-B, or other N/O 4-wire smoke detectors.

IMPORTANT: 

When using 4-wire smoke detectors with this device,

the smoke detectors must be powered from a source other than the
release device, such as an approved UL1481 regulated power
supply providing battery backup support.

Alarm
Contacts
Style A
(N/O)

8

CONNECTIONS OF INITIATING DEVICES AND
ACCESSORIES

A maximum of 4 smoke detectors may be installed with this
device. Refer to NFPA 72 and NFPA 80 for instructions
concerning proper placement and detection coverage. End-of-line
devices must be installed for supervision of electrical power to 
4-wire smoke detector. When using 4-wire smoke detectors with
this device, electrical supervision must be provided by means of a
UL/ULC listed end-of-line relay.

NOTE: 

For low voltage wiring #18 AWG is recommended.

Normally Open “2-Wire,” Class B Style A Initiating Devices

Connect wiring from N/O initiating device loop to positions 3 and
4. Place the supervisory resistor (LMEOLRES-10) contained
within the accessory pack. (Figure 3). Observe proper polarity, 3
(+), 4 (–) when attaching to the release device’s terminal board. 

NOTE: 

Make certain that the Wire Jumper is placed between

positions 5 and 6.

This option is a supervised, current-limited circuit.

OR

Normally Open “4-Wire,” Class B Style A Initiating Devices

Connect wiring from N/O 4-Wire initiating device loop to
positions 3 and 4, making sure an end-of-line supervisory
resistor (LMEOLRES-10) is installed as shown in Figure 4 or 5,
depending upon the type of smoke detector being used. Observe
proper polarity, 3 (+), 4 (–) when attaching to the release device’s
terminal board.

NOTE: 

Make certain that the Wire Jumper is placed between

positions 5 and 6.

This option is a supervised, current-limited circuit.

OR

Normally Closed “4-Wire,” Class B Style A Initiating Devices

Connect wiring from N/C 4-Wire initiating device loop to
positions 5 and 6 (Figure 6). This option is a supervised,
current-limited circuit.

NOTE: 

Make certain that the 10k ohm resistor is placed between

positions 3 and 4.

NOTE: 

End-of-line devices must be installed adjacent and after

the last initiating device. Initiating device loops are supervised
and cannot be direct series or paralleled between multiple release
devices or shared with other alarm equipment. For proper wiring
configurations from multiple smoke detectors or signaling for
simultaneous closure on multiple doors, call technical support, 
1-888-528-7870. Incorrect wiring between devices may cause
damage to the release control circuit and void warranty.

OR

Relay Module Installation

as described on the following page.

W I R I N G

To prevent possible SERIOUS INJURY or DEATH:
• End-of-line devices MUST be installed for supervision of

electrical power to 4-wire smoke detector.

• DO NOT install this device on a motorized door without an

electric safety edge.

ATTENTION

AVERTISSEMENT

AVERTISSEMENT

AVERTISSEMENT

WARNING

WARNING

CAUTION

WARNING

WARNING

PRECAUCIÓN

ADVERTENCIA

ADVERTENCIA

ADVERTENCIA

FIGURE 4

FIGURE 5

FIGURE 3

FIGURE 6

Summary of Contents for LiftMaster LM21XPBB

Page 1: ...L L M M 2 2 1 1 X X P P B B B B L L M M 2 2 1 1 X X P P B B B B V V B B E EX XT TE EN ND DE ED D P PE ER RF FO OR RM MA AN NC CE E R RE EL LE EA AS SE E D DE EV VI IC CE E APPROVED The Chamberlain Gro...

Page 2: ...you must read and fully understand this manual and follow all safety instructions DO NOT attempt repair or service of your release device unless you are an Authorized Service Technician GENERAL DESCR...

Page 3: ...that the wall or mounting surface provide adequate support for the release device Refer to the door manufacturer s recommendations for use of this product with specific door being utilized Use only ha...

Page 4: ...tion of pull must be perpendicular to the side of the release device enclosure Install an eyebolt a minimum distance of 12 from the release device to adequately redirect sash chain pull 4 Install end...

Page 5: ...ncillary devices i e smoke detectors horn strobes etc To reduce the risk of SEVERE INJURY or DEATH ALL electrical connections MUST be made by a qualified individual Disconnect power at the fuse box BE...

Page 6: ...3 2 1 Voice Board Wiring Annunciator Wiring with Sleeve Low Voltage Wiring High Voltage Wiring Ground L2 L1 Power Strip Mechanical Reset Plunger Refer to wiring section for proper application of thes...

Page 7: ...consist of 22 18 AWG wiring Use only 250Vac 3 Amp 3 AG Slo Blo fuses 1 Supervised power limited circuit 20 Ohm maximum line impedance 2 Unsupervised power limited circuit 20 Ohm maximum line impedance...

Page 8: ...Wire Class B Style A Initiating Devices Connect wiring from N O initiating device loop to positions 3 and 4 Place the supervisory resistor LMEOLRES 10 contained within the accessory pack Figure 3 Obs...

Page 9: ...is in the closed position and so that it will toggle states from its N O condition switch closed when door is closed to a closed condition indicating that the door edge has made contact with desired d...

Page 10: ...lection of either message In the ON position Message 1 is activated in the OFF position Message 2 is activated Figure 12 The voice board can drive up to two 70 7V speakers Model LM8SP or speaker input...

Page 11: ...ructions Raise door and then reset the release device by pushing downward on the mechanical reset button at the top of the device Fully insert the end link through the side opening on the device and r...

Page 12: ...orrect If not the release device will not release the fusible link assembly in a fire condition Conversely the release device will always release the fusible link assembly when powered or reset CIRCUI...

Page 13: ...ATH Stand clear of path of door Disconnect ALL electrical and battery power BEFORE performing maintenance ATTENTION AVERTISSEMENT AVERTISSEMENT AVERTISSEMENT WARNING CAUTION WARNING WARNING WARNING PR...

Page 14: ...ector 24Vdc Ion 9 LM1412 Smoke Detector 12Vdc Ion 10 LMTH135 Heat Detector 135 Degree Fixed Temperature 11 LMTH194 Heat Detector 194 Degree Fixed Temperature ITEM PART DESCRIPTION 12 LMEH1224ADA Horn...

Page 15: ...24MC LMHS2475ADA 24Vdc Horn Strobe P1224MC P2R LMEH1224ADA 24Vdc Horn H12 24 LM8SP Speaker SP201R MODEL NO DESCRIPTION LMEOLRES10 10 kOhm End of Line Resistor LMEOLRES 10 LMEOLR1224 End of Line Relay...