5
6
–
+
Power from
Control Panel
Terminal Strip
LMEOLR1224
12/24 Vdc EOL
Relay
IMPORTANT:
When using 4-wire smoke detectors with this
device, the smoke detectors must be powered from a source
other than the release device, such as an approved UL1481
regulated power supply providing battery backup support.
Power from
Control Panel
Purple
N/C
N/C
C
C
(+)
(–)
(–)
(+)
(–)
(+)
(–)
(+)
3
4
–
+
Power from
Control Panel
NOTE
: Follow this method of attachment when using LM4W-B,
LM4WT-B, or other N/O 4-wire smoke detectors.
NOTE
: Generic version of a N/C
4-wire smoke detector is shown.
– IN/OUT
+ OUT
+ IN
– IN/OUT
+ OUT
+ IN
3
4
–
+
(–)
(+)
3
4
COM
NO
– IN/OUT
+ OUT
+ IN
COM
NO
– IN/OUT
+ OUT
+ IN
–
+
10k Ohm @1/2 watt
Supervisory Resistor
(LMEOLRES-10)
10k Ohm @1/2 watt
Supervisory Resistor
(LMEOLRES-10)
10k Ohm @1/2 watt
Supervisory Resistor
(LMEOLRES-10)
Terminal Strip
Terminal Strip
Power from
Control Panel
LMEOLR1224
12/24 Vdc EOL
Relay
LMEOLR1224
12/24 Vdc EOL
Relay
NOTE:
Follow this method
of attachment when using
LM2W-B, LM2WT-B, or
other 2-wire 24Vdc smoke
detectors.
24Vdc Power from
Terminal Strip
NOTE
: Follow this method of attachment when using LM4W-B,
LM4WT-B, or other N/O 4-wire smoke detectors.
IMPORTANT:
When using 4-wire smoke detectors with this device,
the smoke detectors must be powered from a source other than the
release device, such as an approved UL1481 regulated power
supply providing battery backup support.
Alarm
Contacts
Style A
(N/O)
8
CONNECTIONS OF INITIATING DEVICES AND
ACCESSORIES
A maximum of 4 smoke detectors may be installed with this
device. Refer to NFPA 72 and NFPA 80 for instructions
concerning proper placement and detection coverage. End-of-line
devices must be installed for supervision of electrical power to
4-wire smoke detector. When using 4-wire smoke detectors with
this device, electrical supervision must be provided by means of a
UL/ULC listed end-of-line relay.
NOTE:
For low voltage wiring #18 AWG is recommended.
Normally Open “2-Wire,” Class B Style A Initiating Devices
Connect wiring from N/O initiating device loop to positions 3 and
4. Place the supervisory resistor (LMEOLRES-10) contained
within the accessory pack. (Figure 3). Observe proper polarity, 3
(+), 4 (–) when attaching to the release device’s terminal board.
NOTE:
Make certain that the Wire Jumper is placed between
positions 5 and 6.
This option is a supervised, current-limited circuit.
OR
Normally Open “4-Wire,” Class B Style A Initiating Devices
Connect wiring from N/O 4-Wire initiating device loop to
positions 3 and 4, making sure an end-of-line supervisory
resistor (LMEOLRES-10) is installed as shown in Figure 4 or 5,
depending upon the type of smoke detector being used. Observe
proper polarity, 3 (+), 4 (–) when attaching to the release device’s
terminal board.
NOTE:
Make certain that the Wire Jumper is placed between
positions 5 and 6.
This option is a supervised, current-limited circuit.
OR
Normally Closed “4-Wire,” Class B Style A Initiating Devices
Connect wiring from N/C 4-Wire initiating device loop to
positions 5 and 6 (Figure 6). This option is a supervised,
current-limited circuit.
NOTE:
Make certain that the 10k ohm resistor is placed between
positions 3 and 4.
NOTE:
End-of-line devices must be installed adjacent and after
the last initiating device. Initiating device loops are supervised
and cannot be direct series or paralleled between multiple release
devices or shared with other alarm equipment. For proper wiring
configurations from multiple smoke detectors or signaling for
simultaneous closure on multiple doors, call technical support,
1-888-528-7870. Incorrect wiring between devices may cause
damage to the release control circuit and void warranty.
OR
Relay Module Installation
as described on the following page.
W I R I N G
To prevent possible SERIOUS INJURY or DEATH:
• End-of-line devices MUST be installed for supervision of
electrical power to 4-wire smoke detector.
• DO NOT install this device on a motorized door without an
electric safety edge.
ATTENTION
AVERTISSEMENT
AVERTISSEMENT
AVERTISSEMENT
WARNING
WARNING
CAUTION
WARNING
WARNING
PRECAUCIÓN
ADVERTENCIA
ADVERTENCIA
ADVERTENCIA
FIGURE 4
FIGURE 5
FIGURE 3
FIGURE 6