3.2  Tools

 

Suitable spanners for installing cable glands. 
3mm flat blade screwdriver. 12mm flat blade screwdriver. No. 6 pozidrive 
Pliers, knife, wire strippers/cutters. 
 

3.3  Electrical Supplies  

The supply voltage and frequency should be specified when ordering.  A maximum voltage variation of +6%/-6% 
on the nominal is expected.  (The safety limit for T rating is +10%). Luminaires should not be operated 
continuously at more than +6%/-6% of the rated supply voltage of the control gear. 
 

Warning:  Luminaires are assessed and/or tested for EMC requirements. This is based on the disposition 
                 of entry cables and, where appropriate, through wiring arrangements as supplied or specified. 
                Users must take care not to introduce wiring into parts of the apparatus materially different to that    
                which could be reasonably inferred from the disposition of fixed supply terminals and specified wiring. 

 

3.4  Light Emitting Diode (LED)

 

LED’s are supplied in 3000, 6000 or 9000 Lumen options with the colour temperature of 4000K or 5000K 
(Check nameplate for colour temperature)  
 

3.5  Mounting 

Luminaires should be installed where access for maintenance is practical and in accordance with any lighting 
design information provided for the installation. The mounting attitudes are restricted to ceiling, pendant, outreach 
pole (lamps facing down or horizontally outward) and horizontal wall mount. The luminaire is mounted using the 
DIA 8.2mm mounting holes on the rear of the body.  
On mounting the luminaire by using the holes, it is the responsibility of the user to ensure that an adequate seal is 
made, to maintain the IP rating of the enclosure. Sealing Washers are provided. 
 

3.6  Cabling and Cable Glands 
3.6.1 

Cables 

The GRP models have facility for through wiring but do not have a facility for looping.  
 
The temperature conditions of the supply cable entry point are such that 70ºC (ordinary PVC) cable can be used.. 
300/500V cable ratings are adequate and no special internal construction is necessary. 
An internal earth tag can be fitted to the cable gland. 
 

Note:

  Through wiring when used, is subject to a maximum current of 16A. 

 
3.6.2 

Cable Gland Types 

The installer and user must take responsibility for the selection of cables, cable glands and seals. 
The product is dual certified for ATEX and IECEx and to comply with the certification for installation cable glands 
and sealing plugs must be ATEX or IECEx certified (or both) depending on site requirements. 
 
Cable glands and sealing plugs when installed must reliably maintain the IP rating of the enclosure. 
The cable gland must withstand an impact value of 7Nm where the risk of mechanical damage is high or 4Nm 
where the risk of mechanical damage is low. 
 
The cable should be reliably clamped externally to the apparatus or surrounding fixture within 200mm of the cable 
gland. 
 
Where brass cable glands are used in a corrosive environment cadmium or nickel plating should be used.  
20 DIA cable entry clearance holes suitable for M20 cable glands are standard.  
 

3.6.3 

Earthing 

On GRP bodied luminaires, all internal metal parts are earthed through the Metal gear tray. The Metal gear tray is 
earthed via supplied cable to incoming terminal block.  
It is the installer’s responsibility to ensure proper earth supply to the luminaire and to ensure any metal cable 
glands are properly earthed. Cable gland earth kits are available from the manufacturer.   

Summary of Contents for Sterling III

Page 1: ...ires Ex ec ATEX IECEx INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS GRP Standard body Important Please read these instructions carefully before installing or maintaining this equipment Good electrical practices should be followed at all times and this data should be used as a guide only Technical Drawing ...

Page 2: ...neral The type of protection is Ex ec and Ex tc The Zone 2 Zone 22 series LED luminaires are surface mounted or suspended utilising the two holes on the base of the body They are mainly used in harsh environments and are constructed using a corrosion resistant glass reinforced polyester body attached to an injection moulded polycarbonate diffuser by stainless steel toggle clips The control gear an...

Page 3: ...eam of dry air steam etc which could generate a propagating brush static discharge 3 1 1 Use in Combustible Dust Atmospheres Where the equipment is used in ignitable dust atmospheres reference must be made to the selection and installation standards in order that the equipment is used correctly In particular this applies to the de rating of surface temperature for use where dust clouds may be pres...

Page 4: ...an adequate seal is made to maintain the IP rating of the enclosure Sealing Washers are provided 3 6 Cabling and Cable Glands 3 6 1 Cables The GRP models have facility for through wiring but do not have a facility for looping The temperature conditions of the supply cable entry point are such that 70ºC ordinary PVC cable can be used 300 500V cable ratings are adequate and no special internal const...

Page 5: ...thly intervals and more frequently if conditions are severe The time between lamp changes could be very infrequent and this is too long a period without inspection 3 8 1 Routine Examination The equipment must be de energised before opening Individual organisations will have their own procedures What follows are guidelines based on EN IEC 60079 17 and on our experience 1 Ensure LED s are lit when e...

Page 6: ...on 5 0 Fuse Ratings With the availability of MCB s with a wide range of characteristics the individual engineer can make a better judgement of what is required Use MCB s suitable for inrush currents to reduce ratings Where MCB s are used the type with the higher short time tripping current ratio used for motor starting and lighting should be specified The inrush current can be calculated where cir...

Page 7: ... Max Surface Temperature Dust 3365 Lumen 2ft Twin 120 277Vac 127 300Vdc 26W 20 C Ta 55 C T4 76 C 6218 Lumen 4Ft Twin 120 277Vac 127 300Vdc 60W 20 C Ta 50 C T4 76 C 8953 Lumen 4Ft Twin 120 277Vac 127 300Vdc 96W 20 C Ta 45 C T4 76 C Typical Standard LED Wiring Diagram Note For other Wiring Diagrams please contact the manufacturer Table B Series Circuit No Off LED Strips Gear Type Lumen Nominal Circu...

Page 8: ...ine Änderungen erfolgt sind die einen Einfluss auf den technischen Stand des Produkts haben Terms of the directive Standard Date Certified to Standards Date Declared to Prescription de la directive Standard date certifiée à Normes date Déclaré Bestimmungen der Richtlinie Standard Datum Zertifiziert nach Standards Datum erklärt 2014 34 EU Equipment and protective systems intended for use in potenti...

Page 9: ...ch im Namen von Chalmit dass am Tag der Lieferung des Produkts der Produkte zusammen mit dieser Erklärung das Gerät die Geräte alle technischen und regulativen Anforderungen der oben aufgeführten Direktiven erfüllt Name and Date Mark Poutney 30 08 2018 Technical Manager Nom et Date Directeur technique Name und Datum Technischer Leiter Quality Assurance Notification by Baseefa Ltd Quality Managemen...

Reviews: