background image

11

9

System guidance

The boiler is suitable for sealed systems only. The

maximum cold water mains pressure for the appliance is 10
bar. All fittings and pipework connected to the appliance
should be of the same standard.  If there is a possibility of
the incoming mains pressure exceeding 10 bar, particularly
at night, then a suitable pressure limiting valve must be
fitted. 

The boiler is designed to provide hot water on demand. If
there is a requirement for greater demands, for example if
the property has several bathrooms and cloakrooms, a
vented or unvented hot water storage system should be
used.

Showers

Any shower valves used with the appliance should be of a
thermostatic or pressure balanced type. Refer to the
shower manufacturer for performance guidance and
suitability.

Flushing and Water Treatment

The performance of the appliance could be impaired by
system debris or the effects of corrosion. The system must
be flushed thoroughly to remove metal filings, solder,
machining oils and other fluxes and greases before
connecting the boiler. If it is an existing system, an
appropriate flushing and descaling agent should be used.
Refer to BS 7593 (1992) for guidance. For more information
on the use of corrosion inhibitors, flushing and descaling
agents, advice can be sought from the manufacturers of
water treatment products such as:

Betz Dearborn Ltd
Foundry Lane
Widnes
Cheshire
WA8 8UD

Tel: 0151 424 5351

Fernox Manufacturing
Britannica Works
Clavering
Essex
CB11 4QZ
Tel: 01799 550811

System Controls

The boiler is electrically controlled and is suitable for most
modern electronic time and temperature controls. The
addition of such external controls can be beneficial to the
efficient operation of the system. The boiler connections for
external controls are 24V and so only controls of 24V or that
have voltage free contacts should be used.

By pass and Pump

The boiler is fitted with an automatic by pass. Although
adjustment is not necessary.

Expansion Vessel

The expansion vessel is pre-charged to 0.7 bar (10 lb/in

2

).

The vessel is suitable for systems up to 145 litres capacity.
For systems of greater capacity an additional expansion
vessel will be required. Refer to the chart below and BS
7074 pt 1 or BS 5449.

Filling Point

Provision must be made to be able to charge the system on
commissioning and to make up any subsequent pressure
loss.
The method of connection must utilise approved equipment
and must comply with the water regulations. A filling loop
can be so installed as to be hidden beneath the boiler.

20

40

60

80

100

120

Pf

140

160

180

200

220

240

0,7

0,8

0,9

1,0

1,1

1,2

1,3

1,4

1,5

1,6

1,7

1,8

1,9

2,0

80

°

C

70

°

C

60

°

C

50

°

C

40

°

C

260

Pression à froid pour le circuit chauffage (en bar)

Liters

Pressure

System capacity chart

Fig. 15

Summary of Contents for Calydra comfort 100

Page 1: ...S Fanned Flue system Installation and Operating instructions 1 2 3 0 4 bar 1 2 3 0 4 bar c Calydra comfort 80 Calydra comfort 100 C C Manufactures N Model Type Gas Council N 200906789037 31 Calydra comfort 80 Nat 47 980 22 200906790037 31 Calydra comfort 100 Nat 47 980 23 ...

Page 2: ...ional warrenty helpline 0870 243 0224 Advice on installation or servicing can also be obtained by contacting the Chaffoteaux Customer Services Department at Telford CUSTOMER SERVICES DEPARTMENT Tel 01952 222288 Fax 01952 260915 GUARANTEE The manufacturer s guarantee is for 12 months from the date of purchase The guarantee is invalidated if the appliance is not installed in accordance with the reco...

Page 3: ...on is able to provide the user with hot water immediately at the outlet of the appliance and stable temperatures at both extremely low flow rates or when several taps are opened together The TSS is a 5 litres independently controlled mini unvented storage cylinder powered by a 3 kW coil It works in conjunction with the Chaffoteaux et Maury low pressure instantaneous domestic hot water system The C...

Page 4: ...ntrol thermistor 17 Three way valve 18 TSS control thermistor 19 Domestic hot water flowswitch 20 Secondary heat exchanger 21 DHW pressure relief valve 22 Taps bracket 23 Two position Selector switch OFF O ON I 24 Domestic hot water temperature adjustment 25 Heating flow temperature control knob 26 Heating temperature indicator lights 27 Green indicator Power ON 28 Orange indicator Burner ON 29 Re...

Page 5: ...minal in mbar 20 20 Nominal in in wg 8 8 Burner pressure Nominal in mbar 11 12 8 Nominal in in wg 4 4 5 1 Burner injector diameter Natural gas G20 in mm 1 23 1 28 Calydra comfort 80 100 PROPANE L P G G31 Gas rate Maximum in kg h 2 00 2 42 Maximum in ft3 h 37 44 8 Inlet pressure Nominal in mbar 37 37 Nominal in in wg 14 8 14 8 Burner pressure Nominal in mbar 35 30 4 Nominal in in wg 14 12 2 BUTANE ...

Page 6: ...ydra comfort 80 37 5kg Calydra comfort 100 38 5kg Lift weight Calydra comfort 80 31 5 kg Calydra comfort 100 32 5kg Tails diameter I Safety valve outlet ø 15 mm J Heating flow ø 22 mm K D H W flow ø 15 mm L Gas supply ø 22 mm M Cold water inlet ø 15 mm N Heating return ø 22 mm Outer case dimensions Width 440 minimum space required 450 Height 850 Depth 380 Minimum clearances Both sides 5 mm Above c...

Page 7: ... is given to a demand for hot water This will interrupt the central heating for the duration of hot water delivery or recovery of the mini cylinder When the boiler has been in standby in Hot Water Mode for some time or when drawing DHW at flow rates of less than 2 l min the temperature in the mini cylinder will eventually decrease and the TSS control thermistor f fig 6 will call for heat Bringing ...

Page 8: ...300 mm J From a surface facing the terminal 600 mm K From a terminal facing the terminal 1200 mm L From an opening in the car port into the dwelling1200 mm M Vertically from a terminal on the same wall 1500 mm N Horizontally from a terminal on the same wall 300 mm Q Fixed by Ubbink Rolux 4 GM flue terminal It may be necessary to protect the terminal with a guard Reference should be made to the Bui...

Page 9: ...aury Ltd for first installation tails kit or to replace existing boilers such as old Chaffoteaux et Maury models Before fitting the tails onto the connecting bracket please check the correct location of the flow restrictor L fig 10 on the main inlet Safety valve drains The pressure relief valve tube is clear silicone It should terminate below the boiler over a tundish or 22 mm pipe see I fig 4 whi...

Page 10: ...ory set at 3 minutes JP3 the spade connector fig 14 allows the gas rate to be reduced to 1 3 performance by positionning spade across pins as shown fig 14 Full performance across pins as shown fig 14 After completling adjustments replace rubber cover and refit outer casing C10 C11 C38 F1 F1A J1 J2 J5 MV1 R67 R72 R73 R75 R76 R85 P3 Fig 13 Fig 12 P3 P4 P5 mini maxi P3 Detail P3 3 3 P3 1 3 J1 J2 S Co...

Page 11: ...ght from the manufacturers of water treatment products such as Betz Dearborn Ltd Foundry Lane Widnes Cheshire WA8 8UD Tel 0151 424 5351 Fernox Manufacturing Britannica Works Clavering Essex CB11 4QZ Tel 01799 550811 System Controls The boiler is electrically controlled and is suitable for most modern electronic time and temperature controls The addition of such external controls can be beneficial ...

Page 12: ...o position I Turn the boiler thermostat to maximum 25 fig 17 The boiler will light Allow the boiler to heat system Check the inlet gas pressure working pressure while boiler is operating in hot water mode Refer to technical data Check the operation of the boiler controls and safety devices see separate servicing leaflet for details Set the by pass Refer to system guidance Re flush the system to re...

Page 13: ... hot water while the heating is on it is only necessary to turn on a hot tap The heating will be interrupted momentarily while the hot water is being delivered The boiler will switch back automatically to heating when the tap is turned off Note If the boiler has been turned off for some time the first attempt to light it may result in a lockout If this happens press the reset button 30 and the boi...

Page 14: ...f times The clock uses a 24hours system e g 8 8 00 am and 18 6 00 pm ON periods are set by sliding all tappets between the ON time and the OFF time to the outer edge of the dial The tappets remaining at the centre of the dial are the OFF periods 4 To select function mode Put the selector switch B to symbol to control the boiler by the clock Put the switch B to I to select permanent operation or to...

Page 15: ...e detection without burner working Besides freezing pump Besides freezing burnerr Lack of water circulation Primary water circulation defect Thermistor sanitary open Thermistor sanitary bypassed Thermistor inlet heating open Thermistor inlet heating bypassed Extractor on and pressure regulator at rest Extractor off and pressure regulator at rest Thermistor cylinder open Thermistor cylinder bypasse...

Page 16: ...cepts no liability for any errors or omission in the information contained in this document Manufacturer Chaffoteaux Maury France Commercial subsidiary MTS GB Limited MTS Building Hughenden Avenue High Wycombe Bucks HP13 5FT Telephone 01494 755600 Fax 01494 459775 internet www chaffoteaux co uk E mail info mtsgb ltd uk Technical Support Help Line 01952 222288 ...

Reviews: