CGEO INTERNATIONAL LIMITED CGEO-CR Installation Manual Download Page 6

Installation instructions; 

1.  Determine proper setting distance using figures from Table 1 or the readings on the 

calibration sheet.  Using a hammer drill or other suitable equipment, drill two ½" holes 
approximately 3" deep at the proper locations.  Shorter holes may be drilled if the anchors 
are cut down accordingly. 

 
2.  Assemble the Crackmeter with anchors attached.  If installing the instrument at the mid-

range position, leave the nylon tie installed (see Figure 1) that secures the transducer shaft.  
Fill the holes with grout or epoxy and push the anchors in until the tops are flush with the 
surface.  For holes drilled overhead use a quick setting grout or epoxy. 

 
3.  Secure the instrument after the grout or epoxy has set.  Remove the cotter pins from the end 

of each ball elbow joint and tighten the ball using a regular blade screwdriver.  Re-install the 
cotter pins to secure the ball locking screw.  Remove the nylon tie. 

 
4.  Check the reading with a portable readout.  Use Table 2 or the readings on the calibration 

sheet to check the position.  Installation complete. 

 

2.2.3.

 

Installation using Machine Bolt Expansion Anchors 

 

The Bolt Expansion Anchor is needed to customize, applied to quick installation or  unable to 
install groutable anchor.  The user self can also purchase  inner expansion (inner explosion type) 
bolt, make a M6 hole in bolt using for the connection of elbow joint.  

 

Expansion Anchor

 

Expansion Anchor

 

Crack

 

Setting Distance

 

 

 

Figure 6 - Installation using Machine Bolt Expansion Anchors 

Installation instructions; 

1.  Determine proper setting distance using figures from Table 1 or the readings on the 

calibration sheet.  Using a hammer drill or other suitable equipment, drill two ½" holes 
approximately 2" deep at the proper locations. 

2.  Insert the expansion anchors with the threaded ends down into the hole, and tighten. 
3.  Remove the nylon tie securing the transducer shaft.  Screw the ball stud on each end of the 

crackmeter into the respective threaded holes in the anchors.  Remove the cotter pins from 
the end of each ball elbow joint and tighten the ball using a regular blade screwdriver.  Re-
install the cotter pins to secure the ball locking screw. 

4.  Check the reading with a portable readout.  Use Table 2 or the readings on the calibration 

sheet to check the position.  Installation completes. 

 

Summary of Contents for CGEO-CR

Page 1: ...CGEO INTERNATIONAL LIMITED Model CGEO CR Vibrating Wire Crackmeter Installation Manual...

Page 2: ...ors 5 2 2 3 Installation using Machine Bolt Expansion Anchors 6 2 3 Cable Installation 7 2 4 Electrical Noise 7 2 5 Lightning Protection 7 3 TAKING READINGS 8 3 1 Operation of the CGEO PR VW Readout B...

Page 3: ...ibrating wire element The tension in the wire is directly proportional to the extension hence the opening of the joint can be determined very accurately by measuring the strain change with the vibrati...

Page 4: ...rts upon requirement 75 mm 10mm Thread Figure 3 Standard Grouting Anchor Rod When setting the gage position using a portable readout see section 3 use the ranges in Table 2 to determine the proper pos...

Page 5: ...e reading with a portable readout Use Table 2 or the readings on the calibration sheet to check the position Installation complete Note Under normal circumstance the installation of transducer itself...

Page 6: ...tion complete 2 2 3 Installation using Machine Bolt Expansion Anchors The Bolt Expansion Anchor is needed to customize applied to quick installation or unable to install groutable anchor The user self...

Page 7: ...tection The Vibrating Wire Crackmeter unlike numerous other types of instrumentation available from CGEO do not have any integral lightning protection components i e transzorbs or plasma surge arresto...

Page 8: ...t is in digits 2 Turn the unit on and a reading will appear in the front display window The last digit may change one or two digits while reading Record the value displayed If no reading displays or t...

Page 9: ...lation To convert digits to deformation the following equation applies Duncorrected R1 R0 G Equation 2 Deformation Calculation Where R1 is the current reading R0 is the initial reading usually obtaine...

Page 10: ...m Digit mm Polynomial Gage Factors A 0 000000026645441378193 B 0 0094917094213891 C 23 33732890100 Thermal Factor K 0 00853859 mm R0 Original Reading T0 Original Tempera Hereinafter Blank Figure 8 Typ...

Page 11: ...hese conditions should always be observed and recorded Seemingly minor effects may have a real influence on the behavior of the structure being monitored and may give an early indication of potential...

Page 12: ...e cable cut or crushed This can be checked with an ohmmeter Nominal resistance between the two transducer leads usually red and black leads is 180 10 Remember to add cable resistance when checking 22...

Page 13: ...342 2 83 107 9 123 77 66K 36 8006 4 1363 44 331 5 84 105 2 124 72 81K 35 7618 5 1310 45 321 2 85 102 5 125 68 30K 34 7252 6 1260 46 311 3 86 99 9 126 64 09K 33 6905 7 1212 47 301 7 87 97 3 127 60 17K...

Reviews: