Mounting 

Electrical installation 

Connection to the 230 V system 

 

 

 

 

4.3.2.1

 

Fusing and terminal data

 

 

Inverter

 

 

VS30401P3

 

VS30401P8

 

VS30402P4

 

VS30403P2

 

VS30403P9

 

VS30405P6

 

VS30401P3

 

Cable installation in 
compliance with 

 

EN 60204-1 

Laying system 

 

B2 

Operation 

 

without mains choke 

Fuse 

 

 

Characteristic 

 

gG/gL or gRL 

Max. rated current 

10 

10 

16 

16 

25 

25 

25 

Circuit breaker 

 

 

Characteristic 

 

Max. rated current 

10 

10 

16 

16 

25 

25 

25 

Operation 

 

with mains choke 

Fuse 

 

 

Characteristic 

 

gG/gL or gRL 

Max. rated current 

10 

10 

16 

16 

25 

25 

25 

Circuit breaker 

 

 

Characteristic 

 

Max. rated current 

10 

10 

16 

16 

25 

25 

25 

Earth-leakage circuit 
breaker 

 

≥ 30 mA, type A or B

 

≥ 30 mA, type

 B 

Mains connection 

 

 

Connection 

 

X100 

Connection type 

 

Screw terminal 

Min. cable cross-section  mm² 

Max. cable cross-section  mm² 

2.5 

Stripping length 

mm 

Tightening torque 

Nm 

0.5 

0.7 

Required tool 

 

0.5 x 3.0 

0.6 x 3.5 

Motor connection 

 

 

Connection 

 

X105 

Connection type 

 

Screw terminal 

Min. cable cross-section  mm² 

Max. cable cross-section  mm² 

2.5 

Stripping length 

mm 

Tightening torque 

Nm 

0.5 

Required tool 

 

0.5 x 3.0 

PE connection 

 

 

Connection 

 

PE 

Connection type 

 

PE screw 

Min. cable cross-section  mm² 

Max. cable cross-section  mm² 

Stripping length 

mm 

10 

Tightening torque 

Nm 

1.2 

Required tool 

 

0.8 x 5.5 

 

 

 

 

 

 

 

Summary of Contents for Emotron VS10

Page 1: ...Emotron VS10 VS30 AC drive 0 25 2 2 kW Mounting and switch on instruction...

Page 2: ...This page intentionally left blank...

Page 3: ...al data 13 4 3 2 1 Fusing and terminal data 15 4 3 3 3 phase mains connection 400 V 16 4 3 3 1 Fusing and terminal datas 17 4 3 4 Connection to the IT system 18 4 3 5 CANopen Modbus connection 19 4 3...

Page 4: ...instructions 1 2 Notations and conventions 1 2 1 Product code examples VS10 23 1P7 20 CM VS10 40 1P7 20 CM VS 10 23 1P7 20 CM Series 1 phase 230V Rated current 1 7A IP20 CANopen Modbus VS 30 40 1P7 20...

Page 5: ...not exceed 110 VDC Observe all specifications of the corresponding documentation supplied This is the precondition forsafe and trouble free operation and for obtaining the product features specified...

Page 6: ...fied on the inverter High leakage current Carry out fixed installation and PE connection in compliance with EN 61800 5 1 or EN 60204 1 Hot surface Use personal protective equipment or wait until devic...

Page 7: ...switch CANopen Modbus Shield connection Control connection Motor connection X105 IT screw Interface X16 Diagnostic Module Inverter status LEDs Earth ground connection PE Shield connection CANopen Modb...

Page 8: ...notes Dangerous electricalvoltage Possible consequence death or severeinjuries All works on the inverter must only be carried out in the deenergised state After switching off the mains voltage wait f...

Page 9: ...9 Mounting Mechanical installation 4 4 2 Mechanical installation Dimensions VS10 VS30 0 25 kW 0 37 kW All dimensions in mm...

Page 10: ...10 4 Mounting Mechanical installation Dimensions VS10 VS30 0 55 kW 0 75 kW All dimensions in mm...

Page 11: ...11 Mounting Mechanical installation 4 Dimensions VS30 1 1 kW 2 2 kW All dimensions in mm...

Page 12: ...mA F1 Q1 L L L1 L2 3 N PE 3 N PE AC 400 V L1 L2 3 N PE 3 N PE AC 208 V 240 V L1 L2 N PE 2 N PE AC 208 V 240 V 1 N PE AC 170 V 264 V 45 Hz 65 Hz F1 F2 Q1 2 PE AC 170 V 264 V 45 Hz 65 Hz F1 F3 Q1 2 PE A...

Page 13: ...25 25 Circuit breaker Characteristic B Max ratedcurrent A 10 10 16 16 25 25 25 Earth leakage circuit breaker 30 mA type A or B Mains connection Connection X100 Connection type Screw terminal Min cable...

Page 14: ...39 has to beused The user must prove that the EN 61800 3 requirements for conformity are fulfilled Fig 2 Wiring example S1 Run Stop Fx Fuses Q1 Mains contactor Dashed line Options F1 Q1 L1 L2 L3 N PE...

Page 15: ...Circuit breaker Characteristic B Max ratedcurrent A 10 10 16 16 25 25 25 Earth leakage circuit breaker 30 mA type A or B 30 mA type B Mains connection Connection X100 Connection type Screw terminal Mi...

Page 16: ...ExxxFinverters Fig 3 Wiring example S1 Run Stop Fx Fuses Q1 Mains contactor Dashed line o tions 100 mA L L1 L2 3 N PE 3 N PE AC 400 V F1 F3 Q1 3 PE AC 340 V 528 V 45 Hz 65 Hz CANopen Modbus Modbus AC...

Page 17: ...16 16 16 Circuit breaker Characteristic B Max ratedcurrent A 10 10 10 16 16 16 Earth leakage circuit breaker 30 mA type B Mains connection Connection X100 Connection type Screw terminal Min cable cros...

Page 18: ...nd potential if the IT screws are not removed Consequence the monitoring functions of the IT systemrespond Before connection to an IT system be absolutely sure to remove the IT screws VS10231P7 VS1023...

Page 19: ...1 5 Stripping length mm 10 Tightening torque Nm Required tool 0 4 x 2 5 4 3 5 3 Basic network settings Configuring network basicsettings 1 Use toggle switch on front of the inverter to select CANopen...

Page 20: ...nstructions and safetyclearances 5 2 Before initial switch on Prevent injury to persons and damage to property Check the following before switching on the mains voltage Is the wiring complete and corr...

Page 21: ...ion 1 Switch on mains voltage 2 Observe LED status displays RDY and ERR on the front of the inverter a If the blue RDY LED is blinking and the red ERR LED is off the inverter is ready for operation Th...

Page 22: ...gain X3 DI3 LOW Speed characteristic example DI1 Drive follows frequencysetpoint AI1 V 10 0 DI4 Speed setpoint selection via X3 AI1 active t In this example X3 AI1 is connected to GND t Preset frequen...

Page 23: ...y double reinforcedinsulation EN 61800 5 1 Protective measures against Short circuit Earth fault Earth fault strength depends on the operatingstatus Overvoltage Motor stalling Motorovertemperature I x...

Page 24: ...ge 2K3 25 70 C EN 60721 3 2 Transport 3K3 10 55 C EN 60721 3 3 Operation Operation at a switching frequency of 8 or 16 kHz above 40 C reduce rated output current by 2 5 C Site altitude 0 1000 m a m s...

Page 25: ...ins choke A 3 6 4 8 7 1 8 8 11 9 13 9 16 9 Output current 2 kHz A 3 2 4 2 6 7 9 6 4 kHz A 1 7 2 4 3 2 4 2 6 7 9 6 8 kHz A 1 7 2 4 3 2 4 2 6 7 9 6 16 kHz A 1 1 1 6 2 1 2 8 4 4 7 6 4 Power loss W 15 20...

Page 26: ...Hz 65 Hz Rated mains current without mains choke A 4 5 7 7 6 10 14 3 16 7 22 5 with mains choke A 3 6 4 8 7 1 8 8 11 9 13 9 16 9 Mains voltage range 3 PE AC 170 V 264 V 45 Hz 65 Hz Rated mains curren...

Page 27: ...h mains choke A 1 4 2 2 6 3 3 7 5 3 Output current 2 kHz A 1 8 2 4 3 2 3 9 5 6 4 kHz A 1 3 1 8 2 4 3 2 3 9 5 6 8 kHz A 1 3 1 8 2 4 3 2 3 9 5 6 16 kHz A 0 9 1 2 1 6 2 1 2 6 3 7 Power loss W 24 31 40 51...

Page 28: ...03 2016 13504491 2 0 01 6210 01R3 CG DRIVES AUTOMATION M rsaregatan 12 Box 222 25 SE 250 24 Helsingborg Sweden 46 42 16 99 00 Info info se cgglobal com Order order se cgglobal com...

Reviews: