8.3 Elevator Commisioning Guide
Elevator special purpose inverter series designed special for elevator application supports open
loop & close loop vector control as well as below functions:
L1
L3
U
V
W
M
R1A
R1B
R1C
DI1
Up
Brake
L2
3-Phase 380VAC
DI2
Down
DI3
High Speed
DI4
DI5
Inspection
R
2
A
R
2
B
R
2
C
KM2
KM2
DI6
Base Block
+
PB
Resistance
24V
Y1
DI7
+24V
COM
Fault
Elevator
Controller
KM1
Leveling Speed
Emergency
UPS
1-Phase 220VAC
KM3
Parameters setting:
DI Function
Parameters setting
Desription
DI1 = UP
C0.00 = 1
Forward running
DI2 = DOWN
C0.01 = 2
Reverse running
DI3 = High Speed
C0.02 = 13
Multi-step speed terminal 1
(see table 1 above)
DI4 = Leveling Speed
C0.03 = 14
Multi-step speed terminal 2
(see table 1 above)
DI5 = Inspection
C0.04 = 51
Inspection signal input
DI6 = Emergency
C0.05 = 52
Emergency signal input
DI7 = Base Block
C0.06 = 6;
C0.14 = 00010;
Base Block signal
High Speed
F1.01 = High Speed
100.0% corresponded to maximum
frequency
Leveling Speed
F1.02 = Leveling Speed
100.0% corresponded to maximum
frequency