128
Functionality
CG Drives & Automation, 01-5980-01r2
Counter 1 Reset [6512]
The selected signal is used as a reset signal for counter 1.
When the reset signal is activated (high), this will zero
counter 1, and the counter will remain at zero as long as the
reset signal is active (high).
Counter 1 Trip Value [6513]
In this menu counter 1 is set to a trip value. When the
counter value equals the trip value, the counter 1 output
signal (CTR1) is activated (high).
Counter 1 Value [6514]
This menu shows the actual value of counter 1.
Counter 2 [652]
Refer to description for Counter 1 [651].
8.6.6
Clock Logic [660]
There are two Clock functions, Clock 1 and Clock 2. Each
clock with separate settings for Time on, Time Off, Date on,
Date Off and Weekday. These clocks can be used for
activating/deactivating desired functions via Relay, digital
output or Virtual I/O ( For example creating start and stop
commands).
Clock 1 [661]
The time, date and weekday for clock 1 are set in these
submenus.
Clock 1 Time On [6611]
Time when the clock 1 output signal (CLK1) is activated.
Clock 1 Time Off [6612]
Time when the clock 1output signal (CLK1) is deactivated.
Clock 1 Date On [6613]
Date when the clock 1 output signal (CLK1) is activated.
Clock 1 Date Off [6614]
Date when the clock output signal (CLK1) is deactivated.
Note that if “Clk1DateOff ” is set to an earlier date than
“Clk1DateOn”, the result will be that the clock is not
deactivated at the set date.
NOTE: Reset input has top priority.
Default:
Off
Selection:
Same selections as in menu Relay 1 [551],
page 112.
NOTE: Value 0 means that counter output is always high.
Default:
0
Range:
0 - 10,000
NOTE: Counter 1 value is common for all parameter sets.
NOTE: The value is lost at power down.
Read-only
Default:
0
Range:
0 - 10,000
6512 C1 Reset
Stp
Off
6513 C1 Trip Val
Stp
0
6514 C1 Value
Stp
0
Read-only
Default:
0:00:00 (hours:minutes:seconds)
Range:
0:00:00–23:59:59
Default:
0:00:00 (hours:minutes:seconds)
Range:
0:00:00–23:59:59
Default:
2013-01-01
Range:
YYYY-MM-DD (year-month-day)
661 Clock 1
Stp
6611 Clk1TimeOn
Stp
0:00:00
6612 Clk1TimeOff
Stp
0:00:00
6613 Clk1DateOn
Stp
2013-01-01
Summary of Contents for emotron TSA Series
Page 1: ...Emotron TSA Softstarter Instruction manual English Valid from Software version 1 27...
Page 2: ......
Page 4: ......
Page 6: ...2 CG Drives Automation 01 5980 01r2...
Page 12: ...8 Introduction CG Drives Automation 01 5980 01r2...
Page 18: ...14 Mounting CG Drives Automation 01 5980 01r2...
Page 42: ...38 Application guidelines CG Drives Automation 01 5980 01r2...
Page 46: ...42 Getting started CG Drives Automation 01 5980 01r2...
Page 70: ...66 Main features CG Drives Automation 01 5980 01r2...
Page 142: ...138 Functionality CG Drives Automation 01 5980 01r2...
Page 158: ...154 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5980 01r2...
Page 160: ...156 Options CG Drives Automation 01 5980 01r2...
Page 168: ...164 Technical data CG Drives Automation 01 5980 01r2...
Page 202: ...CG Drives Automation 01 5980 01r2 198...
Page 203: ......