1

 

General safety information 

 
Specified use 
The drive unit is only intended for vertically moving sectional doors with full counter-
balancing.  

 

The drive unit must be protected against moisture and aggressive environmental 
conditions (such as corrosive substances). The drive units are only suitable for indoor use. 
Appropriate protective measures must be taken for outdoor installation. The drive unit is 
not intended for hazardous areas. The values specified in the technical data of the drive 
unit must not be exceeded. The safe operation can only be ensured if used as specified.  

 

 

Target audience of these installation instructions 
These installation instructions are geared towards qualified persons trained in the handling 
of door systems. Expert knowledge, relevant skills and practical experience are what set 
apart qualified persons. They are capable of safely carrying out the tasks involving 
installation, maintenance and modernisation according to the instructions. 
 

 

Safe operation 

The safe operation of the product can only be ensured if it is used as specified. Follow the 
installation instructions. Observe all specifications, especially warnings, when installing the 
product in the overall system. GfA is not liable for damage resulting from non-observance 
of the installation instructions. The resulting overall system must be reassessed for its 
safety in accordance with applicable standards and directives (e.g. CE marking). These 
installation instructions refer only to a part of the overall system and are not sufficient as 
the sole instructions for the overall system. The installer of the system must prepare the 
instructions for the overall system.  
We recommend entering the danger area of the system only when the drive unit is at a 
standstill. 
 

 

 

Summary of Contents for 1000337710011

Page 1: ...f Installation Instructions ELEKTROMAT SE 14 15 25 40 ER Model 10003377 10011 en Status 26 03 2021 ...

Page 2: ...2 GfA ELEKTROMATEN GmbH Co KG Wiesenstraße 81 D 40549 Düsseldorf www gfa elektromaten de info gfa elektromaten de ...

Page 3: ...3 8 Limit switch connection 14 9 Emergency manual operation release 15 10 Completing commissioning inspection 17 11 Declaration of incorporation Declaration of conformity 18 Symbols Warning Potential injury or danger to life Warning Danger to life from electric current Note Important information Requirement Required action Schematic representations are based on product examples Deviations from del...

Page 4: ...nd practical experience are what set apart qualified persons They are capable of safely carrying out the tasks involving installation maintenance and modernisation according to the instructions Safe operation The safe operation of the product can only be ensured if it is used as specified Follow the installation instructions Observe all specifications especially warnings when installing the produc...

Page 5: ... third parties Warning Danger from improper use of the product Do not let children operate the product unsupervised or use as a toy Warning Danger to life from incorrect installation Work carried out improperly may result in death or severe injury from electrical current or falling parts Allow only competent people to carry out the work Disconnect all cables from the power supply Observe valid reg...

Page 6: ... holding torque 600 Nm Maximum door weight 6000 N Supply voltage 3N 400 V Operating current 1 90 A Operating frequency 50 Hz Power factor cos φ 0 50 Maximum movement per hour 16 h 1 Class of protection IP 65 Limit switch range maximum revolutions of output shaft hollow shaft 20 Temperature range 10 40 60 C 1 When using a temperature range of 40 60 C use half of maximum movements per hour ...

Page 7: ... maximum holding torques or locking torques refer to technical data Connection elements Self locking connection elements with a minimum strength of 800 N mm2 8 8 must be used Utilize the hole diameter to the full Use adequately dimensioned washers for elongated holes BAGAB00002_Z002 BAGAB00003_Z002 3 1 Permissible mounting positions BAGAC01002_Z003 ...

Page 8: ...8 Mounting Eight threads are provided for mounting Use at least 2 of these Keys are used to connect to the door shaft Use a key that is at least as long as the hollow shaft 8 x M8x16 BAGAD01001_Z002 ...

Page 9: ...manufacturer must also be observed during installation Warning Potential injury or danger to life During installation be sure to use a lifting device that has a sufficient load carrying capacity Thoroughly grease the door shaft BAGAE01001_Z003 Mount the keys Observe possible variants Ⓐ or Ⓑ BAGAE01002_Z003 ...

Page 10: ...t BAGAE01003_Z003 Tighten all connection elements M8 to 25 Nm Install all other connection elements according to the specifications of the door manufacturer BAGAE01006_Z002 25 Nm Secure the keys version Ⓑ only BAGAE01007_Z002 ...

Page 11: ...s are de energised Observe the applicable regulations and standards Make a proper electrical connection Use suitable tools Performing electrical installation Remove the cover Insert the motor plug Insert the limit switch plug BAHAC13_Z001 Completing the electrical installation Mount the cable entries and or cable glands ...

Page 12: ...12 5 Limit switch adjustment The adjustment of the final limit positions OPEN and CLOSE is described in the instructions for the door control panel ...

Page 13: ...13 6 Motor connection M1 Motor X13 Motor plug 7 Alternative motor connection M1 Motor X13 Motor plug ...

Page 14: ...14 8 Limit switch connection F10 Thermal contact X12 DES connection 1 Safety circuit 2 Channel B RS485 3 Ground 4 Channel A RS485 5 Safety circuit 6 Supply voltage ...

Page 15: ...ed to apply more than the permissible force of 390N according to DIN EN 12604 DIN EN 12453 to move the door by emergency manual operation this indicates a stalling on the drive unit or door Releasing the stalling may cause the door to drop Adopt a secure position For drive units with brake the emergency manual operation must be carried out against the closed brake Caution Components at the drive u...

Page 16: ...16 Switch on by pulling the red handle Open or close the door by hand Switch off by pulling the green handle ...

Page 17: ...secure and in proper condition Electrical wiring Check the connection cables and cabling for damage or crushing Check that the screw connections and plug connections are fitted properly with a good electric contact Limit switch Check the final limit positions by opening and closing fully The safety area must not be approached Drive unit Note Engage a qualified engineer to check the drive unit annu...

Page 18: ...ed complies with the provisions of the above mentioned directives Authorised representative to compile the technical documents is the undersigned Düsseldorf 10 08 2018 Stephan Kleine CEO Signature The following requirements from Appendix I of the Machinery Directive 2006 42 EC are met 1 1 2 1 1 3 1 1 5 1 2 2 1 2 3 1 2 6 1 3 2 1 3 3 1 3 9 1 5 1 1 5 2 1 5 4 1 5 6 1 5 7 1 5 8 1 5 9 1 5 10 1 5 11 1 5 ...

Page 19: ...19 ...