11.2 Operation data Midi Wall 100
Primary side
Heating
DHW
Design pressure PS
16 Bar
6 bar
10 Bar
Design temperature TS
120°C
90°C
90°C
Relief pressure safety-valve
-
3 Bar
9 Bar
Volume Heat exchanger, L
2,472/1,957 L
2,575 L
2,06 L
CB60-50L
Temperature
program (°C)
Heating
Capacity CB
Plates Plates
Plates
Flow P dPp Flow S dPs
kW
type
no
primary
secondary
l/s
kPa
l/s
kPa
100-63/60-80
105
60
50
1*24 L
1*25 L
0,71
3,3 1,28
7,8
100-53/50-70 (52,95) 147,6
60
50
1*24 L
1*25 L
0,78
4,0
1,79
15,0
100-48/45-60 (46,1)
110,1
60
50
1*24 L
1*25 L
0,51
1,8
1,78
15,0
100-43/40-60 (42,3)
146,4
60
50
1*24 L
1*25 L
0,63
1,8
1,77
15,0
100-43/40-70
87,1
60
50
1*24 L
1*25 L
0,38
1,0
0,70
2,6
100-43/40-80
33,9
60
50
1*24 L
1*25 L
0,15
0,2
0,20
0,3
100-36/33-40 (33,1)
50,8
60
50
1*24 L
1*25 L
0,19
0,3
1,75
15,0
100-33/30-60
109
60
50
1*24 L
1*25 L
0,41
1,2
0,88
4,1
CB60-40L:2
Temperature
program (°C)
DHW
Capacity CB
Plates Plates
Plates
Flow P dPp Flow S dPs
kW
type
no
primary
secondary
l/s
kPa
l/s
kPa
80-23/10-60 (19,1)
157
60
40
1*10 1*9
2*10 L
0,62
23,0
0,75 29,9
80-23/10-60 (17,1)
113
60
40
1*10+1*9
2*10 L
0,43
11,8
0,54 16,2
80-23/10-55 (16,2)
141
60
40
1*10+1*9
2*10 L
0,53
17,5
0,75 30,2
80-23/10-55 (14,65)
102
60
40
1*10 +1*9
2*10 L
0,37
9,1
0,54 16,4
70-25/10-55 (19,8)
141
60
40
1*10 1*9
2*10 L
0,67 27,2 0,75 29,9
70-25/10-55(17,7)
102
60
40
1*10 +1*9
2*10 L
0,47
13,7
0,54 16,3
70-22/10-55 (19,75)
141
60
40
1*10+1*9
2*10 L
0,67
27,1
0,75
29,9
70-22/10-55 (17,7)
102
60
40
1*10+1*9
2*10 L
0,47
13,7
0,54 16,3
65-22/10-55
126
60
40
1*10+1*9
2*10 L
0,70 29,3 0,66 24,1
65-22/10-55 (20,55)
102
60
40
1*10+1*9
2*10 L
0,55
18,4
0,54 16,1