10.5 Balancing valve DHWC
Set the valve to a specific pressure drop according to:
1. Close the valve fully (
2. Open the valve the correct numbers of turns (
See the diagram (
) for numbers of turns. In this example 2,3 turns.
3. Using a 3 mm Allen key, turn the inner spindle clockwise until stop.
4. The valve is now set.
To check the setting: Close the valve, the indicator shows 0.0. Open it to the stop position. The indicator then
shows the set value, in this case 2.3 (
The diagram shows the pressure drop for different settings and flow rates.
Four turns correspond to fully opened valve (
). Opening it further will not increase the capacity.