C
E
T
i
s
a
t
ra
d
e
m
a
rk
o
f
C
E
T
F
ir
e
P
u
m
p
s
M
fg
L
td
.
75 Hector St., P.O. Box 90, Pierreville (Québec) Canada J0G 1J0 Telephone: 1-800-567-2719 Fax: 1-800-434-2613
www.fire-pump.com
ACCEPT ONLY THE BEST
A C E N T U R Y O F E N G I N E E R I N G F O R T H E B R A V E S T
SM-PFP-25hp-DSL-MR
INSTRUCTIONS MANUAL
DOS AND DONTS
Do…
• Read your Kubota D902 owner’s manual
• Close your drain valve on the pump casing before starting the engine
• Seal up any air that could leak into the suction side
• Charge you battery at least once every three months
• Stop your pump before fuelling
Do Not…
• Let your pump freeze up with water in it (drain the casing)
• Allow sand in the suction it will damage the wear ring and the mechanical seal (use floating strainer if water supply doubtful)
• Run your pump dry for more than 2 minutes at idle (prime as soon as possible)
• Use your pump with less than 12 in of water below the inlet of the suction hose
• Allow your pump to run without surveillance
• Run the pump with the discharge valve closed for more than 1 minute
STARTING PROCEDURE
• Place your pump on a hard, stable surface within 15° from horizontal.
• Check the oil and the fuel tank level.
• Connect your suction hose. Make sure that there is a rubber seal on the adapter and screw it tight.
• Close all the discharge valves.
• Close the drain valve (below the casing of the pump).
• Turn key to ON position. The “glow plugs” light comes on indicating glow plugs are preheating combustion chamber.
• Start the engine and let it idle.
• When “glow plugs” light goes out, turn key to “Ignition” (IG).
• Open the primer ball valve.
• Close this ball valve only when you have pressure on the suction.
• Push the priming button.
• When water comes out of the priming pump (it should take approximately 10 to 15 sec. with a 10 ft x 4¨ suction hose), release the
electric priming button. Do not operate the primer more than 20 sec.
• Open the discharge valve to allow water to run through the pump
• Adjust the RPM with the throttle to desired pressure.
N.B. 1
The exhaust system is very hot. Do not touch
N.B. 2
When you are done with the pump, always drain the pump casing