3.4.3 Configuration 

The Setup Configuration mode provides access to the following setup parameters: 

Label 

Description 

Range 

Default 

Menu 

Main

 

              Sub 

PROG 

Setup Configuration 

PASS 

Enter Password 

0 to 9999 

COM

Set Comm. Parameters 

Yes/No 

 

Id 

Set Unit ID 

1 to 247 

100 

FP 

Set Setpoint Parameters 

Yes/No 

 

IRn 

Set IRn Alarm parameters (n=1, 2, 3, 4) 

 

 

SEL 

IRn Alarm Setpoint 

0=OFF 

1=DO Alarm 

2=No DO Alarm

 

VAL 

IRn

 

Alarm Limit 

20 to 1000 mA 

500 

dLY 

IRn Alarm Time Delay 

0 to 20s 

5s 

PSEL 

IRn Warning Setpoint 

0=OFF 

1=DO Warning 

2=No DO Warning 

rAIo 

IRn

 

Warning Level Ratio 

0.1 to 0.8 

0.6 

PdLY 

IRn

 

Warning Time Delay 

0 to 20s 

5s 

TCn 

Set TCn Alarm parameters (n=1, 2, 3, 4) 

 

 

SEL 

TCn Alarm Setpoint 

0=OFF 

1= DO Alarm 

2=No DO Alarm   

VAL 

TCn Alarm Limit 

45 to 140°C 

100°C 

dLY 

TCn Alarm Time Delay 

0 to 40s 

0s 

PSEL 

TCn Warning Setpoint   

0=OFF 

1=DO Warning 

2=No DO Warning 

rAIo 

TCn Warning Level 

0.1 to 0.8 

0.6 

PdLY 

TCn Warning Time Delay 

0 to 40s 

0s 

DO 

Set DO parameter 

 

 

do 

DO pulse width 

0 to 6000 (x0.1) s 

1.0s 

RES FP

 

Set other Alarm parameters 

 

 

TCCP 

Enable RTD Compensation

2

 

0=OFF 

1=ON 

TCTH 

Temperature threshold

3

 

0 to 45°C 

0°C

 

IRTH 

Residual Current threshold

3

 

10 to 500mA 

20mA

 

dT 

Set Clock 

 

 

Enter the Current Date 

YY-MM-DD 

Enter the Current Time 

HH:MM:SS

 

MT

 

 

 

 

PASS SET 

Set New Password

 

 

 

nEW 

Enter New Password

 

0 to 9999 

SoE 

 

 

 

ALM SoE 

Display Alarm events 

 

 

FAIL SoE 

Display Fault events 

 

 

MT SoE 

Display Maintenance events 

 

 

Clr SoE 

Clear SOE 

Yes/No 

 

InFo 

View Device Information (Read Only) 

Yes/No 

 

Firmware Version 

For example, 1.00.00 

means the firmware 

version is V1.10.00. 

Pro 

Protocol Version 

e.g. 1.0 means V1.0 

Firmware Update Date 

e.g. 20160915 

Table 3-5 Setup Parameters 

Notes:   
1)

 

The PMC-T402 only supports the configuration of Unit ID for its Com port. The default settings 
for Baud Rate and Data Format are 9600 bps and 8E1, respectively and cannot be changed from 

the Front Panel.   

2)

 

In general, the RTD sensor comes standard with a 3m wire, and the wiring resistance may lead to 
a relatively large error, it is recommended that the RTD Sensor Compensation be used to reduce 

Summary of Contents for PMC-T402

Page 1: ...PMC T402 Temperature Iresidual Monitor User Manual Version V1 0 November 09 2017...

Page 2: ...the right to make changes without notice Please consult CET or your local representative for the latest product specifications DANGER This symbol indicates the presence of danger that may result in se...

Page 3: ...normal operation of the device hazardous voltages are present on its terminal strips and throughout the connected potential transformers PT and current transformers CT PT and CT secondary circuits are...

Page 4: ...for any damage caused by device malfunctions CET accepts no responsibility for the suitability of the device to the application for which it was purchased Failure to install set up or operate the devi...

Page 5: ...pply Wiring 15 Chapter 3 Front Panel 16 3 1 LED Indicator 16 3 2 Buttons 16 3 3 LED Display 17 3 3 1 LED Display Symbols 17 3 3 2 LED Testing 17 3 3 3 Default Display 17 3 3 4 Data Display 18 3 3 5 SO...

Page 6: ...CET Inc 6 5 6 Device Information 30 Appendix A Technical Specifications 31 Appendix B Standards of Compliance 32 Appendix C Ordering Guide 33 Contact us 34...

Page 7: ...tion Monitoring for Industrial or Commercial facilities Industrial and Commercial Electrical Power System AC Low Voltage Distribution System Condition monitoring of electrical equipment 1 2 Features E...

Page 8: ...Modbus RTU protocol 1 3 Getting more information Additional information is available from CET via the following sources Visit www cet global com Contact your local representative Contact CET directly...

Page 9: ...l that have the appropriate training and experience with high voltage and current devices The monitor must be installed in accordance with all local and national electrical codes During the operation...

Page 10: ...CET Inc 10 2 2 Dimensions 2 2 1 Main Unit Figure 2 2 Main Unit Dimensions 2 2 2 Terminal Figure 2 3 Terminal Dimensions...

Page 11: ...2 8 1 5 4 5 kgf cm M2 5 3 9 lb in 2 TCn 3 IRn 4 Power Supply 6 0 x 6 0 1 0mm2 2 5mm2 14AWG 22AWG 6 0 kgf cm M3 5 2 lb in Table 2 1 Terminal Dimensions 2 2 3 Residual Current CTs PMC MIR 46 160A 46mm F...

Page 12: ...in a dry environment with no dust and kept away from heat radiation and electrical noise source The PMC T402 supports two installation modes Panel mount and DIN Rail mount Panel Installation steps o R...

Page 13: ...that the DIN rail and the adapter are already in place o Remove the installation clips from the PMC T402 o Fit the PMC T402 through the adapter as shown in Figure 2 10 o Re install the installation cl...

Page 14: ...e following figure illustrates the RS 485 connections on the PMC T402 Figure 2 11 RS 485 Connections 2 5 Digital Output Wiring The following figure illustrates the Digital Output connections on the PM...

Page 15: ...owing figure illustrates the Temperature Input connections on the PMC T402 Figure 2 14 Temperature Input Connections Notes 1 The alarming feature of the Temperature measurement is disabled by default...

Page 16: ...s 3 2 Buttons Buttons Data Display Mode Setup Configuration Mode Alarm Fault Mode Diag Pressing this button scrolls to the next available parameter or menu item If the selected parameters is a numeric...

Page 17: ...shows the special LED display symbols Label Description A B C D E F G H I J K L M N O P Q R S T U V W Y 0 1 2 3 4 5 6 7 8 9 Table 3 3 LED Display Segments 3 3 2 LED Testing Pressing Diag button for on...

Page 18: ...iag button When there is an Alarm or a Fault event The Front Panel displays the Alarm Fault channel and the detailed information The Alarm buzzer would sound The correspond IRn TCn LED indicator and A...

Page 19: ...ng a parameter to change Press Diag or Mute to scroll to the desired sub menu or parameter Press Enter to select the sub menu or parameter Once a parameter has been selected its value will blink 3 Cha...

Page 20: ...CET Inc 20 3 4 2 Setup Menu Figure 3 5 Setup Menu...

Page 21: ...s 0s DO Set DO parameter do DO pulse width 0 to 6000 x0 1 s 1 0s RES FP Set other Alarm parameters TCCP Enable RTD Compensation2 0 OFF 1 ON 1 TCTH Temperature threshold3 0 to 45 C 0 C IRTH Residual Cu...

Page 22: ...the error if the length of the wire exceeds 3m 3 When the measurements of the Residual Current or Temperature are less than the Residual Current or Temperature Threshold the measurements will be disp...

Page 23: ...as an early warning system to alert users of potential safety hazards as well as the health of the electrical system The PMC T402 s Residual Current inputs are required to be paired with CET s PMC MIR...

Page 24: ...ion 2 2 4 and Appendix A for its dimensions and specifications The Temperature Setpoint parameters can be programmed via the Front Panel or through the communications Setup Parameter Definition Defaul...

Page 25: ...rated over communications via our free PMC Setup software or PecStar iEMS Integrated Energy Management System The Remote Control has a higher priority than the Alarm Output meaning that even if the DO...

Page 26: ...9 RO Reserved UINT16 40010 RO Global Fault Alarm Status8 UINT16 40011 RO DO Status9 UINT16 40012 RO IR1 RMS 10 UINT16 x10 mA 40013 RO IR2 RMS 10 UINT16 40014 RO IR3 RMS 10 UINT16 40015 RO IR4 RMS 10 U...

Page 27: ...lt Bit 15 Global Alarm 1 if there is either an IRn or TCn Alarm Warning 9 For the DO Status register the bit value of B0 represents the status of DO with 1 meaning Active Closed and 0 meaning Inactive...

Page 28: ...500 mA 51012 RW IR1 Alarm Time Delay UINT16 0 to 20s 5s 51013 RW IR1 Warning Level UINT16 0 1 to 0 8 0 6 Event Classification Sub Classification Event Value Description 1 1 Reserved 2 Reserved 3 1 0...

Page 29: ...INT16 45 to 140 C 100 C 51042 RW TC3 Alarm Time Delay UINT16 0 to 40s 0s 51043 RW TC3 Warning Level UINT16 0 1 to 0 8 0 6 51044 RW TC3 Warning Time Delay UINT16 0 to 40s 0s 51045 RW TC4 Setpoint UINT1...

Page 30: ...NT16 60068 60124 WO Reserved UINT16 60125 WO Buzzer Mute UINT16 60126 WO System Self Diagnostic UINT16 60127 WO Clear SOE UINT16 60128 WO Arm Reset Alarm Fault Register UINT16 60129 WO Execute Reset A...

Page 31: ...idity Atmospheric Pressure Pollution Degree 25 C to 70 C 40 C to 85 C 5 to 95 non condensing 70 kPa to 106 kPa II Mechanical Characteristics Mounting Unit Dimensions IP Rating Panel or DIN Rail 72 L 7...

Page 32: ...2001 Level III Radiated Fields IEC 61000 4 3 2006 Level 10V m Fast Transients IEC 61000 4 4 2004 Level III Surges IEC 61000 4 5 2005 Level III Conducted Disturbances IEC 61000 4 6 1995 Level III Magne...

Page 33: ...CET Inc 33 Appendix C Ordering Guide...

Page 34: ...ntact us CET Inc 8 F Westside Building 201 Terra Industrial Tradepark Che Gong Miao Shenzhen Guangdong P R China 518040 Tel 86 755 8341 5187 Fax 86 755 8341 0291 Email support cet global com Web www c...

Reviews: