CET Electric Technology
21
5.3 Device Setup
5.3.1 Basic Setup Parameters
Register
Property
Description
Format
Range/Default*
6000
RW
Un
UINT16
1 to 1,000V, 750V*
6001
RW
I Primary
UINT16
1 to 10,000A, 100A*
6002
RW
Shunt Output
UINT16
1 to 100mV, 75mV*
6003~6029
RW
Reserved
UINT16
6030
RW
Backlight Time-Out
UINT16
0 to 60min, 3min*
Table5-5 Setup Parameters
5.3.2 I/O Setup Parameters
Register
Property
Description
Format
Range/Default*
6220
RW
DI1 Debounce
UINT16
1 to 9999ms, 20*
6221
RW
DI2 Debounce
UINT16
1 to 9999ms, 20*
Table 5-6 I/O Setup
5.3.3 Energy Pulse Setup Parameter
Register
Property
Description
Format
Range/Default*
6400
RW
Energy Pulse Output Enable
UINT16
0= Disabled, 1= Enabled*
6401
RW
Energy Pulse Constant
UINT16
0=25 imp/kWh
1=100 imp/kWh*
2=400 imp/kWh
3=1000 imp/kWh
4=3200 imp/kWh
Table 5-7 Energy Pulse Setup Parameter
5.3.4 Communication Setup Parameters
Register
Property
Description
Format
Range/Default*
6500
RW
Reserved
6501
RW
Unit ID
UINT16
1 to 247, 100*
6502
RW
Baud Rate
UINT16
0=1200, 1=2400, 2=4800
3=9600*, 4=19200
6503
RW
Comm. Config.
UINT16
0=8N2, 1=8O1, 2=8E1*
3=8N1, 4=8O2, 5=8E2
Table 5-8 Communication Setup
5.4 Time
There are two sets of Time registers supported by the PMC-D721MD – Year / Month / Day / Hour /
Minute / Second (Register # 60000 to 60002) and UNIX Time (Register # 60004). When sending time
to the PMC-D721MD over Modbus communications, care should be taken to only write one of the two
Time register sets. All registers within a Time register set must be written in a single transaction. If
registers 60000 to 60004 are being written to at the same time, both Time register sets will be updated
to reflect the new time specified in the UNIX Time register set (60004) and the time specified in registers
60000-60002 will be ignored. Writing to the Millisecond register (60003) is optional during a Time Set
operation. When broadcasting time, the function code must be set to 0x10 (Pre-set Multiple
Registers). Incorrect date or time values will be rejected by the meter. In addition, attempting to
write a Time value less than Jan 1, 2000 00:00:00 will be rejected.
Register
Property
Description
Format
Note
60000
9000
RW
High-order Byte: Year
UINT16
0-37 (Year-2000)
Low-order Byte: Month
1 to 12
60001
9001
RW
High-order Byte: Day
UINT16
1 to 31
Low-order Byte: Hour
0 to 23
60002
9002
RW
High-order Byte:
Minute
UINT16
0 to 59