Wiring

 

Diagrams

 

 

1P3W

 

 

3P3W

 

 

3P4W

 

   

 

 

 

1P3W with 2CTs 

3P3W with 3CTs 

  3P3W with 2CTs 

  3P4W with 3CTs 

RS-485 Wiring 

 

The PMC-340 provides one standard RS-485 port and supports the Modbus RTU protocol. Up to 32 devices can be connected on a RS-485 bus. 
The overall length of the RS-485 cable connecting all devices should not exceed 1200m. 

 

If the master station does not have a RS-485 communications port, a RS-232/RS-485 or USB/RS-485 converter with optically isolated outputs and 
surge protection should be used.   

 

Each PMC-340 comes with a 120Ω Termination Resistor. It is recommended that a single termination resistor be used at the end of the RS-485 
bus to prevent signal reflection. 

 

 

 

 

 

 

Basic Setup Parameters 

Menu 

Parameters 

Description 

Range/Options 

Default 

PW 

Password 

Enter Password 

0 to 9999 

“0” 

SYS SET 

TYPE 

Wiring Mode 

The wiring connection of the meter

1) 

DEMO/1P3W/3P3W/3P4W/ 

1P2W L-N/1P2W L-L 

3P4W 

CT1 

CT1 Ratio 

Primary CT Ratio 

1 to 30,000 (A) 

5A 

CT2 

CT2 Ratio 

Secondary CT Ratio 

1 to 5 (A) 

5A 

I1 Rev 

Phase A CT 

Reverse Phase A CT Polarity 

YES/NO 

NO 

I2 Rev 

Phase B CT 

Reverse Phase B CT Polarity 

YES/NO 

NO 

I3 Rev 

Phase C CT 

Reverse Phase C CT Polarity 

YES/NO 

NO 

COM 
SET 

ID 

Meter Address 

Meter Address 

1-247 

100 

BAUD 

Baud rate 

Data rate in bits per second 

1200/2400/4800/ 

9600/19200/38400bps 

9600 

CFG 

Comm. Port Configuration 

Data Format 

8N2/8O1/8E1/8N1/8O2/8E2 

8E1 

Notes:   

1)

 

The wiring modes 1P2W L-N and 1P2W L-L are not supported by PMC-340A

 