CET Electric Technology
20
5.7
Device Setup
5.7.1
Basic Setup
Register
Property
Description
Format
Range, Default*
6000
WO
Comm. Authorization
UINT16
0~9999
6001
RW
PF Convention
UINT16
0=IEC*, 1=IEEE, 2=-IEEE
6002
RW
THD Calculation
UINT16
0= THDf*, 1= THDr
6003
RW
Current Threshold of Device
Operating Time
UINT16
1 to 1000 (x0.001 In), 4*
6004
RW
LED Energy Pulse
UINT16
0=Disabled, 1=kWh*, 2=kvarh
6005
RW
Demand Period
UINT16
1 to 60 (min), 5*
6006
RW
No. of Windows
UINT16
1 to 15, 1*
6007
RW
Self-read Time
UINT16
0xFFFF*
6008
RW
Monthly Energy Log Self-read
Time
UINT16
100
6009
RW
Default Display
UINT16
0=kWh Import*, 1=Auto-Scroll
6010
RW
MBPW - Modbus Password
UINT16
0=Disabled*, 1=Enabled
6011
RW
Comm. Password
UINT16
0 to 9999, 9999*
6012
RW
Front Panel Password
UINT16
0 to 9999, 0000*
6013
RW
Arm before execute
UINT16
0=Disabled*, 1=Enabled
6014
RW
Time Zone
UINT16
0 to 32, 29 (GMT+10:00)*
Table 5-15 Basic Setup
Notes:
1.
The Comm. Authorization is the register to which the master software would be required to write the correct Comm. Password before
it’s allowed to perform any Modbus Read/Write operations with the PMC-230, if the MBPW (Modbus Password) register is enabled. If
the Comm. Password is correct, the master software will be able to communicate with the same PMC-230 continually until there is a
period of inactivity of 60 seconds or longer. When this happens, the master software will have to write to the Comm. Authorization
register again to re-gain access to the PMC-230. If an incorrect Comm. Password has been written to the Comm. Authorization register
for 3 consecutive times, Modbus access will be locked out for approximately 15 minutes.
2.
There are two ways to calculate THD:
THDf:
where I
1
represents the amplitude of the fundamental component and I
n
represents the amplitude of the n
th
harmonic.
THDr:
where the denominator represents the total RMS value and the numerator represents the RMS value of the harmonics from 2
nd
to 8
th
.
3.
The Self-Read Time applies to the Max. Demand Log and supports the following three options:
•
A zero value means that the Self-Read will take place at 00:00 of the first day of each month.
•
A non-zero value means that the Self-Read will take place at a specific time and day based on the formula: Self-Read Time = (Day x
100 + Hour) where 0 ≤ Hour ≤ 23 and 1 ≤ Day ≤ 28. For example, the value 1512 means that the Self-Read will take place at 12:00
pm on the 15th day of each month.
•
A 0xFFFF value means the automatic self-read operation is disabled and replaced with manual operation.
4.
The Monthly Energy Log Self-Read Time supports the following options:
•
A Zero value means that the Self-Read will take place at 00:00 of the first day of each month,
•
A non-zero value means that the Self-Read will take place at a specific time and day based on the formula: Self-Read Time = (Day x
100 + Hour) where 0 ≤ Hour ≤ 23 and 1 ≤ Day ≤ 28. For example, the value 1512 means that the Self-Read will take place at 12:00
pm on the 15th day of each month.
5.
Under
Auto-Scroll
mode, the
kWh/kvarh Imp./Exp. and kVAh as well as kWh Imp./Exp. per Tariff
are displayed sequentially in 4 seconds
interval.
6.
The
MBPW
register is disabled by default and should be enabled if communication security is required.
7.
The following table lists the Time Zones supported:
Code
Time Zone
Code
Time Zone
0
GMT-12:00
17
GMT+03:30
1
GMT-11:00
18
GMT+04:00
2
GMT-10:00
19
GMT+04:30
3
GMT-09:00
20
GMT+05:00
4
GMT-08:00
21
GMT+05:30
5
GMT-07:00
22
GMT+05:45
6
GMT-06:00
23
GMT+06:00
7
GMT-05:00
24
GMT+06:30