Instruction Handbook                          PFP-10hp-DSL  

- 12 -

 

201

7

, C.E.T. Fire Pumps Mfg. This handbook is subject to change without notice, 

Contact your local C.E.T. dealer or C.E.T. direct to ensure you have the latest version.

 

6.

 

 

Performance 

The pump running under *normal conditions will give you these performances: 

*

Normal conditions :  geostatic height of  4’ 10” (1.5m), temperature de 59°F (15°C),  water clear of sand 

and debris, atmospheric pressure < 3280’ (1000m) from sea level 
 

 

None conformance to the instructions given in this handbook can reduce the 

performance of the pump. 

 

 

 

 

 
 

Flow (GPM / LPM) 

Pressure (PSI / Bar) 

300 / 1135 

15 / 1.0 

210 / 790 

42 / 2.9 

75 / 283 

95 / 6.6 

0 / 0 

106 / 7.3 

Summary of Contents for PFP-10hp-DSL

Page 1: ...ler or C E T direct to ensure you have the latest version Instruction Handbook Version 1 0 Model PFP 10hp DSL Your version of the pump the engine and their accessories may vary from the one seen on the illustrations Serial Number ________________________________ This pump was built by C E T Fire Pumps Mfg ...

Page 2: ...or C E T direct to ensure you have the latest version Table of contents 1 FOREWORD 3 2 SAFETY INSTRUCTIONS 4 3 DESCRIPTION 7 4 GENERAL INSTRUCTIONS 10 5 TRANSPORT AND STORAGE 11 6 PERFORMANCE 12 7 STARTING PROCEDURE 13 8 OPERATING AND STOPPING 17 9 STARTUP 18 10 MAINTENANCE 19 11 TROUBLESHOOTING GUIDE 20 12 GENERAL WARRANTY 22 13 CONTACT US 23 ...

Page 3: ...ry of experience in building fire fighting equipment If you follow the instructions given in this handbook your pump will be a useful ally for many years to come For your own safety and those around you it is important that you read and understand each part of this handbook BEFORE you start the pump Always keep this manual accessible so you can refer to it whenever the need arrives All rights rese...

Page 4: ...ffler o NEVER run the engine without a muffler or proper exhaust system o NEVER operate the engine if the fuel tank cap is removed do not fill the tank while the engine is running If fuel is spilled move machine away from the area of the spill and avoid creating any source of ignition until it has completely evaporated o NEVER run the engine in an explosive environment o NEVER touch the spark plug...

Page 5: ... hot water scald and burn hazards NEVER let the pump run for more than one minute with discharge valve s completely closed When the pump is running make sure to always leave the discharge valve slightly opened to avoid overheating of the pump If the pump runs completely closed with water flowing for a few minutes the water inside may heat up and scald or burn the operator when he opens the valve T...

Page 6: ...ched note will put at risk the security of the personnel operating near the pump The words danger warning and caution are used for levels of risk This symbol means that it is mandatory to read and understand this handbook as well as the operation manual from the engine manufacturer BEFORE you start the engine This symbol represents the risk of injury from high temperature surfaces This symbol repr...

Page 7: ...have the latest version 3 Description This portable pump is directly driven by the very high quality 9 9 hp Hatz diesel engine It is equipped with an electric starter and also has a backup recoil starter It has an integrated fuel tank of 1 3 gallons 5L The pump has a 2 5 65mm discharge and a 3 77mm suction It is equipped with an exhaust priming system guaranteed up to 20 6m ...

Page 8: ...istance aluminum alloy body It also has an axial mechanical seal The pump can operate to a maximum pressure of 160 PSI 11bar It has been designed to work at temperatures between 5 F 15 C and 104 F 40 C The manufacturer does not guarantee the performances outside of this temperature range The pump is operated with the throttle control knob on the side of the pump inlet The pump should not run on a ...

Page 9: ...ith an electrical starter Install in a properly ventilated area Recommended individual protective equipments not included Firefighting grade protective gloves conforms to EN659 or equivalent Protective glasses Hearing protection Intended use for application This pump has been designed to move water for fire fighting purposes It has been engineered to run under the constant supervision of an operat...

Page 10: ...r pump Always use a strainer at the end of the suction hose If you are not sure of the quality of the pumped water use a floating strainer to prevent drawing the sand or stone from bottom source The Hatz 1B40 engine runs on Diesel fuel conform to classifications EN590 or ASTM D 975 1D 2D and requires a quantity of 1 58qt 1 5L of oil SAE10W 30 SAE10W 40 for a running temperature range of 13 F 25 C ...

Page 11: ...cially if the engine has oil in it Storage Warning It is important to take into account the dangerous materials and components such as diesel oil and the battery Store away from heat source flames and sparks e g heater using a pilot The pump should be stored in a cool dry place away from salty air at the exception if the pump has the marinization treatment If the pump is to be stored for over 30 d...

Page 12: ...e The pump running under normal conditions will give you these performances Normal conditions geostatic height of 4 10 1 5m temperature de 59 F 15 C water clear of sand and debris atmospheric pressure 3280 1000m from sea level None conformance to the instructions given in this handbook can reduce the performance of the pump Flow GPM LPM Pressure PSI Bar 300 1135 15 1 0 210 790 42 2 9 75 283 95 6 6...

Page 13: ...o ensure you have the latest version 7 Starting procedure 7 1 Place the pump on a flat and stable surface with an angle less than 15 Place your pump as close as possible to the water source WARNING NEVER run the engine in an enclosed area Exhaust gas contains carbon monoxide an odorless and potentially deadly gas 7 2 Check the oil level 7 3 Check the fuel level ...

Page 14: ...e safety of your installation Warn the surrounding people before you start the pump It is important that you evaluate the trajectory of the hose to prevent incidents NOTE If you are pumping from a hydrant replace step 7 7 by open the valve or any other control mechanism of the hydrant to fill your pump Follow the rest of the procedure but skipping section 7 9 7 10 7 11 and 7 13 We recommend you av...

Page 15: ... the engine with the throttle cable to its maximum speed 7 11 Open slowly the discharge valve CAUTION NEVER run the pump dry for more than one 1 minute full throttle it could damage the mechanical seal Always prime the pump as fast as possible 7 12 When water comes out of the venturi it should take approximately 15 to 30 seconds when priming from 10 x 2 1 2 suction hose close the priming valve 7 1...

Page 16: ...ject to change without notice Contact your local C E T dealer or C E T direct to ensure you have the latest version WARNING NEVER run the pump at high speed with the discharge valve closed more than one 1 minute The water can heat up Upon opening the valve the operator could be burned ...

Page 17: ...r could freeze and damage them CAUTION After each use it is important to flush the inside of your pump with fresh water This will help prevent damages and wear to the pump components IF the pump has been used to pump salt water Drain the salt water completely Flush the pump with fresh water to prevent corrosion and salt crystals from forming Apply a spray silicone compound to the pumps internal co...

Page 18: ... do a functional test Functional test Connect a suction hose of 3 diameter and a length of 10 Make sure to completely submerge the end of the suction hose at least 12 Connect a discharge hose of 2 5 diameter and not more than 30 The difference of height between the inlet of the pump and the surface of the water source should not be over 6 The pump test should be done at an altitude lower than 3280...

Page 19: ...ct Dispose properly of the used oil and filters according to the local environmental regulations WARNING Never run the pump if the inlet strainer is not on or is damaged Interval Maintenance Daily First 8 hours Every 50 hours Every 100 hours Check oil level and add some if required Check for oil or fuel leakage Make sure the throttle control the discharge valve the drain valve and the priming valv...

Page 20: ... and applied the priming protocol of the pump Check for any possible air leakage in the suction hose Check the mechanical seal for leakage The engine seems to speed up and down Faulty engine Refer to the troubleshooting guide of the engine owner s manual The engine speed is too low The throttle should be in the fast position while priming For engine s speed problem refer to the engine output is lo...

Page 21: ...eposits or dust is obstructing the priming system Carefully dismantle the priming system clean it up or replace the components if necessary The difference of elevation between the end of the discharge hose and the pump is too high Reduce the elevation difference use a smaller nozzle at the end of the hose to build more pressure while reducing the flow or contact your local C E T dealer for a more ...

Page 22: ...IRE PUMPS MFG incurs no liability under this warranty or otherwise for equipment which has been abused altered or improperly maintained or for equipment which has been returned for inspection or repair more than ten 10 days after defect complained of has been or should have been discovered by the Purchaser or Equipment which is operated after the defect has been discovered 3 C E T FIRE PUMPS MFG i...

Page 23: ...ct to ensure you have the latest version 13 Contact Us For repair or questions about warranties please contact your local C E T fire pumps dealer or C E T direct at E mail service fire pump com Tel 1 450 568 2719 Fax 1 450 568 2613 C E T fire pumps MFG 75 Hector Street C P 90 Pierreville QC J0G 1J0 For more information on our products go to www fire pump com ...

Reviews: