C300R User Manual 

Page 13 

C300R RACKMOUNT INSTALLATION  

 

 

 

This series of UPS can be placed horizontally and vertically, with the LCD screen rotating 90 degrees.  

 

STEP ONE 

Ensure the master input breaker switch is OFF 

 

STEP TWO  

Installing the UPS in a rack position: 

 

Install the L bracket to the unit 

 

 

 

Install the unit to the rack cabinet in a suitable U-space (Pre-install rail kit) 

 

 

Slide the UPS into the rack rails and lock it into the rack enclosure 

 

Tighten the screws.  The UPS is now ready for cabling unless you are installing EBMs. 

 

 

STEP FOUR 

If not installing additional EMBs skip straight to step six. 

 

Using the same method as assembling the UPS in rack form, assemble the EBM into the rack mounting above or below the UPS 

 

 

Connect the earth line between mounting point A & B 

 

 

Remove the display panel, and unscrew the internal screws 

 

 

A QUICK START VIDEO GUIDE FOR THE C300RR RACKMOUNT/TOWER MODEL IS AVAILABLE AT 

WWW.CERTAUPS.COM/MEDIA

 

 

Summary of Contents for C300R

Page 1: ...LATION AND USER GUIDE THE C300R SERIES An uninterruptible power supply UPS incorporating line interactive technology which eliminates all mains power disturbances www certaups com For assistance please contact your local CertaUPS partner ...

Page 2: ...NSTALLATION 11 C300R TOWER INSTALLATION 11 C300R RACKMOUNT INSTALLATION 13 C300R SERIES STARTUP AND SHUTDOWN 15 STARTING THE UPS WITH MAIN POWER PRESENT 15 STARTING THE UPS FROM BATTERY 15 UPS SHUTDOWN WITH MAINS POWER 15 UPS SHUTDOWN WITHOUT MAINS POWER 16 C300R SERIES OPERATION 16 LCD DESCRIPTION 17 SETTINGS MENU 18 COMMUNICATION PORTS 19 RS232 USB 19 EPO CONNECTION 19 INTERFACE CARDS OPTIONAL 1...

Page 3: ... REPLACING THE EBM 22 RECYCLING A UPS 23 TROUBLESHOOTING 24 ALARMS FAULTS 24 SILENCING THE ALARM 25 TESTING THE BATTERIES 25 TECHNICAL DATA 26 BLOCK DIAGRAM 26 ELECTRICAL SPECIFICATION 26 OPERATING ENVIROMENT 26 RUNTIMES 27 DIMENSIONS AND WEIGHTS 27 ...

Page 4: ... 120 lb Forklift Before any handling please ensure that the following precautions are taken QUALIFIED PERSONNEL Any persons servicing the UPS must be qualified and knowledgeable in UPS technology and batteries CLOTHING Rubber gloves and safety boots to be worn POWER OFF Ensure all mains power is disconnected before starting work TOOLS always use insulated tools Do not lay tools down near the Ups o...

Page 5: ...der in which they appear within this manual DO Check that the indicators on the rating plate correspond to the AC powered system and to the actual electrical consumption of all the equipment to be connected to the UPS DO Ensure the socket outlet is installed near the PLUGGABLE equipment and is easily accessible DO Store the UPS in a dry environment Additional considerations To reduce the risk of f...

Page 6: ...Phase output THE TECHNOLOGY The C300R UPS series uses line interactive technology which ensures that clean and stable power is always provided A line interactive UPS operating in line mode will always provide a consistent supply voltage of AC power to the load This is done by using an automatic voltage regulator to maintain a steady output voltage while supplied via mains power and a battery and i...

Page 7: ...C NMC SNMP Network management card C 300REL Relay card specific to C300R series C EMP Environmental monitoring probe C NMC required C MOD1 Modbus interface RS485 2 4 wire RTU MBSTOWER 1 3 Maintenance bypass switch UPS STANDARDS DESCRIPTION STANDARD UPS Safety IEC EN 62040 1 EMC IEC EN 62040 2 Hazardous Substances IEC EN 50581 PLEASE FIND UPS PRODUCT DIAGRAMS AND FULL TECHNICAL SPECIFICATIONS ON PA...

Page 8: ...lear of condensation The UPS EBM is heavy Follow any special precautions provided on the carton Unpack the equipment and remove shipping carton and all the packaging materials DO NOT lift the using the front panel and rear panel C300R PACKAGING C300R BOX CONTENTS CHECKLIST C300R Series UPS C12 Input Cable C13 Output Cable USB A to B Software CD Quick Start Guide Warranty Card PLEASE ENSURE ALL SAF...

Page 9: ...ient temperature before turning on The UPS needs to be fully charged to achieve full autonomy C300R TOWER INSTALLATION Tools required Insulated screwdriver Correctly rated and fused loose cable STEP ONE Ensure utility power is switched off STEP TWO Carefully place the UPS within the stands STEP THREE Pull out the LCD panel and carefully rotate it taking care not to damage the cable STEP FOUR If no...

Page 10: ... step six To connect to multiple EBMs use the same method as assembling the EBM into the rack mounting To install multiple EBMs connect an Earth line between the UPS and the first EBM and then connect a second Earth line between the first EBM and the second EBM Take off the front panel as instructed in the previous steps This then enables you to connect the battery terminal A from the UPS to the E...

Page 11: ...l rail kit Slide the UPS into the rack rails and lock it into the rack enclosure Tighten the screws The UPS is now ready for cabling unless you are installing EBMs STEP FOUR If not installing additional EMBs skip straight to step six Using the same method as assembling the UPS in rack form assemble the EBM into the rack mounting above or below the UPS Connect the earth line between mounting point ...

Page 12: ...e first EBM and then connect a second Earth line between the first EBM and the second EBM Take off the front panel as instructed in the previous steps This then enables you to connect the battery terminal A from the UPS to the EBM terminal B shown below Then connect the battery terminal D from the first EBM to the battery terminal E of the second EBM The user then needs to reassemble the front pan...

Page 13: ... mode without output interruption to the UPS STARTING THE UPS FROM BATTERY Before using this feature the UPS must have been powered by utility power with output enabled at least once to ensure the unit is adequately charged After connecting the UPS to the External battery module EBM should wait for 10s before pressing the button to allow for pre charging the auxiliary power supply Battery start ca...

Page 14: ...second Function Test Press and hold the button for 3 seconds Battery Test Press and hold the button for 10 seconds Select Button Press the Select button to scroll through the settings one by one Flash The UPS is on Standby mode The following table shows the indicator status and description ITEM DESCRIPTION FUNCTION Input frequency and voltage Indicates the value of input frequency and voltage Inpu...

Page 15: ... is too high above maximum operating conditions NORM The UPS is operating under normal conditions Equipment is being powered from the mains supply not from the UPS batteries AVR The UPS is operating in AVR mode bATT The UPS is providing power to equipment from the UPS batteries This will occur if there s a problem with the mains supply UPS will follow shutdown procedures established using the WinP...

Page 16: ...n to select the value of the setting Press and hold the Enter button for one second the UPS will then return to settings mode Press and hold the Enter button for 3 seconds or the power button for 0 5 seconds to exit settings mode LCD DISPLAY DISPLAY MEANING SETTINGS OPV Output voltage mode selection 220 220V 230 230V 240 240V AVR Input type selection 000 Normal range mode 001 Wide range mode 002 G...

Page 17: ...utdown initiated by the UPS in the event of a power failure EPO CONNECTION The EPO Emergency Power Off connection allows the UPS to be powered off by changing the state of a normally closed circuit Normally closed Normally EPO connector is closed with a wire on the rear panel Once the connector is open the UPS will stop output until the EPO status is disabled INTERFACE CARDS OPTIONAL The Network M...

Page 18: ...ord logs for analysis Multi language support English Italian Turkish Spanish French Portuguese Polish Thai Germanic Russian and Japanese Requires a GSM modem not supplied WinPower installation STEP ONE Go to https www certaups com downloads download winpower STEP TWO Choose the operating system you need and follow the instruction described on the website to download the software STEP THREE When do...

Page 19: ...ns power Place the UPS on a flat stable surface with the front of the cabinet facing you Remove the UPS front cover Disconnect the internal battery connectors Replace the UPS front cover To avoid damage and to prevent DOA s always use a reputable courier for all equipment transportation STORING THE UPS Where UPS equipment is stored for a long period of time the batteries must be recharged every si...

Page 20: ... Remove watches rings or other metal objects Use tools with insulated handles Do not lay tools or metal parts on top of batteries Wear rubber gloves and boots REPLACING THE EBM For the C300RR rotation module If a Power distribution unit PDU is connected to the UPS turn the Mains Bypass Switch MBS to bypass and switch off the input it is then safe to replace the EBM s If a PDU is not connected to t...

Page 21: ...posal of batteries is required Refer to your regulations for disposal requirements DO NOT open or modify the battery or batteries Released electrolyte is toxic and harmful to the skin and eyes DO NOT discard the UPS or the UPS batteries in the general waste This product contains sealed lead acid batteries and must be disposed of responsibly For more information contact your local recycling centre ...

Page 22: ...ent temperature FNLK The UPS fan is locked Contact your service representative bTWK The batteries are weak and require recharging or replacing Contact your service representative SITE Site wiring fault Check input wiring for fault FANF UPS has confirmed fan failure Contact your service representative HIGH Battery over voltage overcharged Confirm correct EBM is installed the UPS will switch to batt...

Page 23: ...circuit Contact your service representative NTCO Inverter NTC open Contact your service representative EPO Emergency power off EPO connection has changed state SILENCING THE ALARM Press the button for one second Seconds to silence the alarm Check the alarm condition and perform the applicable action to resolve the condition If an alarm status changes the alarm will need to be silenced again TESTIN...

Page 24: ...900W 1500VA 1350W 2000VA 1800W 3000VA 2700W Voltage 220Vac 230Vac 240Vac Frequency 50 60Hz Waveform Pure Sinewave BATTERIES Model No C300R 010 B C300R 015 B C300R 020 B C300R 030 B Voltage 36V 36V 72V 72V Capacity 7ah x 6 7 ah x 6 9 ah x 6 9 ah x 6 OPERATING ENVIRONMENT Ambient Temperature 0 C to 40 C Full load no de rating 40 C to50 C output power derated to 50 load Charger current derated 50 Ope...

Page 25: ...ns 44 Mins 108 Mins C300R 020 B C300R BB72VP 2 35 Mins 50 Mins 92 Mins 204 Mins C300R 030 B NA 0 1 Mins 2 Mins 4 Mins 15 Mins C300R 030 B C300R BB72VP 1 9 Mins 15 Mins 27 Mins 60 Mins C300R 030 B C300R BB72VP 2 21 Mins 30 Mins 50 Mins 118 Mins Calculated to 20 C DIMENSIONS AND WEIGHTS Model No Dimensions W H D mm Net Weight kg C300R 010 B 438 x 86 5 x 436 17 8 C300R 015 B 438 x 86 5 x 436 17 8 C30...