Cerberus ILP-2 Installation/Wiring Instructions Download Page 5

DETECTOR MOUNTING

To ensure proper installation of the detector into the base,

be sure the wires are properly dressed:

1. Position all wires flat against the base.

2. Take up all slack in the outlet box.

3. Route wires away from connector terminals.

4. When mounting the detector base, and routing wires

through the cutouts in the air shield, make sure the

shield is sealed against air leaks. Open the shield

cutouts only as much as require

d.

INSTALLATION OF DETECTOR HEAD

1. Align notch in detector cover to raised surface on outer

ring of base; refer to Figure 2.

2. Push detector into base and rotate clockwise to make

electrical connections. The detector automatically

stops and locks into place.

3. To remove, push detector up

into the base while rotating

the detector counterclock-

wise. Continue to rotate

counterclockwise until stop is

reached; then pull downward

to disengage from base.

Figure 2

Installing Detector Head

6

Summary of Contents for ILP-2

Page 1: ...st or humidity DETECTOR PLACEMENT Although no specific spacings are set for the detectors used for the 0 to 4000 ft min clean air velocity applica tion use 30 foot center spacing 900 sq ft from NFPA S...

Page 2: ...n ics extensive experience in the design of the system assures the best detector placement Sound engineer ing judgment by qualified personnel must be followed DB 3S DB X3RS DB 3S DB X3RS To avoid nuis...

Page 3: ...warehouses auditoriums etc do affect detector response and should be considered SPECIAL CEILING CONSTRUCTION FACTORS Ceiling obstructions can change the natural movement of air and combustion product...

Page 4: ...the nameplate is 2 5 ft For application sensitivity setting refer to the MXL MXLV OPERATION INSTALLATION AND MAINTENANCE MANUAL P N 315 092036 or the MXL IQ OPERATION INSTALLATION AND MAINTENANCE MANU...

Page 5: ...is sealed against air leaks Open the shield cutouts only as much as required INSTALLATION OF DETECTOR HEAD 1 Align notch in detector cover to raised surface on outer ring of base refer to Figure 2 2 P...

Page 6: ...detector in the wrong base DETECTOR SYSTEM CONFIGURATION ILP 2 with MXL Control Panels When the ILP 2 is used with MXL MXLV MXL IQ systems it can be programmed to optimize environmen tal response usin...

Page 7: ...T Only qualified service personnel should test The minimum test schedule may be found in the current edition of NFPA 72 Chapter 7 ILP 2 with MXL Family Control Panels The MXL Control Panel must be pla...

Page 8: ...I 32 Programmer Tester Refer to the OPERA TIONS MANUAL P N 315 090077 DETECTOR CLEANING System MXL automatically indicates the trouble mes sage INPUT DEVICE REQUIRES SERVICE for any detector whose smo...

Page 9: ...t 5 Use a small soft brush to loosen dust in the crevices Vacuum any dust from the lower photochamber Do not use cleaners or solvents on the lower photochamber Another method for cleaning the photocha...

Page 10: ...positioning the visible LED correctly Replace the detector in the base 9 Clean all other Model ILP 2 detectors following Steps 2 through 8 10 Recheck the sensitivity of the detector 11 If the sensiti...

Page 11: ...IBLE CONTROL EQUIPMENT Refer to the MXL MXLV OPERATION INSTALLATION AND MAINTENANCE MANUAL P N 315 092036 or the MXL IQ OPERATION INSTALLATION AND MAINTE NANCE MANUAL P N 315 093624 The ILP 2 is only...

Reviews: