Installation/Wiring Instructions
Model ILP-2 Detector
These instructions are written in accordance with the
installation guidelines of NFPA No. 72,
NATIONAL FIRE
ALARM CODE.
CAUTION
Detector Device Storage
DO NOT install this detection device until all construc-
tion is completed.
DO NOT store this detection device where it can be
contaminated by dirt, dust, or humidity.
DETECTOR PLACEMENT
Although no specific spacings are set for the detectors
used for the 0 to 4000 ft/min clean air velocity applica-
tion, use 30 foot center spacing (900 sq ft), from NFPA
Standard 72 as a guide or starting point for a detector
installation layout. This spacing, however, is based on
ideal conditionssmooth ceiling, no air movement, and
no physical obstructions. In some applications, there-
fore, considerably less area is protected adequately by
P/N 315-095028-3