background image

 

2. Push the test button on the individual GFCI 
module. The unit should trip. 
3. Push the reset button. The indicator light 
should come on. 
4. Repeat steps 2 & 3 for the remaining five 
modules. 
 
TROUBLE SHOOTING 
The GFCI Modules within the temporary power 
distribution unit will trip whenever one or more of 
the following abnormal conditions exist in the line 
(supply) side circuit: 
1. Either line (hot) conductor is transposed with 
the neutral conductor. 
2. Either line (hot) conductor is open 
(disconnected) 
3. There is an excessive voltage imbalance 
between line 1 and line 2 circuits. This may be 
the result of an open neutral conductor in the 
supply circuit. 
 
When the abnormal condition(s) in the supply 
circuit is corrected, the unit may be reset for 
normal use by completely removing and then 
reapplying line power. It is recommended that 
the GFI test procedure be repeated at this time.  
When a GFI module trips, attempt to reset it by 
pressing the reset switch, being careful to look 
for possible danger to personnel. If the module 
resets, the fault was momentary and has 
cleared. If it trips again immediately, the fault is 
still present and the GFI module is performing its 
safety function. To locate the fault, disconnect all 
loads and again try pressing the reset switch. 
The module should reset. Reconnect the loads 
one at a time.  The module will trip when the 
faulted load is reconnected. Inspect all tools, 
appliances and extension cords in the faulted 
load circuit, repairing or replacing any that are 
not in good condition. 
 
NOTE: Tripping of a circuit breaker in these 
models can only result from an overload or short 
circuit condition in its individual load circuit. 
When the fault in the load circuit is corrected or 
removed, the circuit breaker can be reset for  
 

 

normal use by switching handle to “OFF” position 
and then to the “ON” position. 
 
APPLICATION NOTES 
1. Tripping of individual branch circuit breakers in 
any temporary power distribution unit have no 
effect on downstream units connected through 
the 50 amp outlet.   
2. There is no overload protection for the 50 amp 
outlet. 
 
NUISANCE TRIPPING 
All cables have some capacitive leakage. In a 
120 volt system, there is a limited to the length of 
cable which can be run before sufficient leakage 
to ground will build up causing a GFI to trip. 
Individual 120 volt branch circuit load cords 
should be limited to 250 feet in length. 
 
HIGH VOLTAGE LIGHT 
Indicates the input wiring is incorrect, and to 
check the power source, 
 
CONTACT MONITOR LIGHT 
The red monitor light is a welded contact 
indicator, that is, if the monitor light is on with the 
unit tripped, it indicates the contact is welded, 
and the unit should be replaced immediately --
there is no GFCI protection. (When the TEST 
button is pressed, both the POWER light and 
MONITOR light should go out, and come back 
on when the RESET button is pressed. 
 

 

Reviews: