  Servicing of batteries should be performed or supervised by 

personnel knowledgeable of batteries and the required precautions.  
Keep unauthorized personnel away from batteries.

 

z

  When replacing batteries, replace with the same type and number of 

the sealed lead-acid batteries.   

z

  The maximum ambient temperature rating is 40

z

  This pluggable type A equipment with battery already installed by the 

supplier is operator installable and may be operated by laymen. 

z

  During the installation of this equipment it should be assured that the 

sum of the leakage currents of the UPS and the connected loads 
does not exceed 3.5mA. 

z

  Attention, hazardous through electric shock. Also with disconnection 

of this unit from the mains, hazardous voltage still may be accessible 
through supply from battery. The battery supply should be therefore 
disconnected in the plus and minus pole of the battery when 
maintenance or service work inside the UPS is necessary. 

z

  The mains socket outlet that supplies the UPS shall be installed near 

the UPS and shall be easily accessible.

 

z

  In case smoke is found coming out from the device, please cut off the 

power supply quickly and contact the distributor.

 

z

  Do not keep or use this product in any of the following environments:

 

9

 

Any area with combustible gas, corrosive substance or heavy 
dust. 

9

 

Any area with extraordinarily high or low temperature (above 
40˚C or below 0˚C) and humidity of more than 90%. 

9

 

Any area exposed to direct sunshine or near any heating 
apparatus. 

9

 

Any area with serious vibrations. 

9

 Outdoor. 

 

z

  In the event that there is fire occurring in the vicinity, please use 

dry-power extinguishers. The use of liquid extinguishers may give rise 
to the danger of electric shock. 

 

 
 

Summary of Contents for MaxPower 1000

Page 1: ...USER S MANUAL MaxPower 1000 UPS Uninterruptible Power System 28 2MAXPO0019 ...

Page 2: ...RTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for the model MaxPower 1000 that should be followed during installation and maintenance of the UPS and batteries ...

Page 3: ...ecting the utility power to UPS switch ON once a month for 24 hours to avoid a full battery discharge z Please do not use the UPS in excess of the rated load capacity z The UPS contains one two large capacity batteries So the shell shall not be opened otherwise such dangers as electric shock will be caused If any internal overhaul or replacement of the battery is required please contact the distri...

Page 4: ...sible through supply from battery The battery supply should be therefore disconnected in the plus and minus pole of the battery when maintenance or service work inside the UPS is necessary z The mains socket outlet that supplies the UPS shall be installed near the UPS and shall be easily accessible z In case smoke is found coming out from the device please cut off the power supply quickly and cont...

Page 5: ...el Power Switch 1 UPS status Indicator AC Mode Green lighting Battery Mode Green flashing 3 Fault LED Red flashing Back Panel 1 Output receptacles 2 Fuse 3 AC Input with AC fuse 4 AC Input 5 Modem Phone Line Surge Protection Option ...

Page 6: ... during shipping and the battery should be recharged prior to use Plug the unit into an appropriate power supply and allow the UPS to charge fully by leaving it plugged in for at least 10 hours with no load no electrical devices such as computers monitors etc connected 3 Placement Install the UPS unit in any protected environment that provides adequate airflow around the unit and is free from exce...

Page 7: ...ntinuously for 1 second and the UPS turns into its normal state the green light is on and the beeper is off after it performs a self diagnosis the beeper and the red and green indicator lights are on for several seconds At this time user may turn on the PC and other loads Press the switch of the UPS continuously for 1 second to turn off the UPS Note 1 For the convenience of maintenance please turn...

Page 8: ...oad of the UPS 1 Remove some non critical load 2 Battery voltage is too low 2 Charge battery 8 hours or more When power failure backup time is short 3 Battery defect due to high temperature operation environment or improper operation to battery 3 Replace with the same type of battery 1 Fuse is blown 1 Replace the same type of fuse Mains normal but LED is flashing 2 Power cord is loose 2 Reconnect ...

Page 9: ...ery Mode Green LED flashing every second Fault Red LED lighting Battery weak Vbat 24V at AC Mode Red LED flashing every 2 seconds for 30 seconds Battery Fault at AC Mode Red LED flashing three times every 2 seconds INDICATOR Overload Red LED flashing twice every second Battery Mode Sounding every 4 seconds Low Battery at Battery Mode Sounding every second Fault Continuously sounding Battery weak V...

Reviews: