SPECIFICATIONS 

 

MODEL 

 

 

Endure 500 

Endure 750 

Endure 1000 

Endure 2000 

CAPACITY   

VA/W 

500VA/300W 

750VA/450W 

1000VA/600W 

2000VA/1200W 

INPUT 

 

 

Voltage 

220/230/240VAC 

Voltage 
Range 

  140-300VAC   

OUTPUT 

 

 

 

 

 

 

 

 

Voltage 

220/230/240VAC 

Voltage 
Regulation(
Batt. Mode) 

+12% / -18% 

Frequency 

50Hz or 60Hz 

Frequency 
Regulation 
(Batt. Mode) 

  +/-0.1 Hz 

Output 
Waveform 

Modified Sinewave 

BATTERY 

    

 

    

 

 

 

 

 

Battery Type 

Rechargeable lead-acid battery 

DC voltage 

12V 

12V 

12V 

24V 

Charger 
Current 

10 Amp +/- 

1Amp 

10 Amp +/- 

1Amp 

10 Amp +/- 

1Amp 

10 Amp +/- 

1Amp 

Back up 
Time (at a 
PC load with 
15" monitor) 

Determined by external battery capacity 

Recharge 
Time 

Determined by external battery capacity 

TRANSFER 
TIME 

Typical 

4-8 ms typical, 14 ms max 

INDICATOR 

AC Mode 

Green lighting 

Battery 
Mode 

Yellow lighting 

Battery 
Charging 
Mode 

When battery is not full enough in line mode, green flashing every 2 

seconds 

When battery full, green lighting 

Overload 

Red flashing every 0.5 second 

Fault 

Red lighting 

AUDIBLE 
ALARM 

Battery 
Mode 

Sounding every 10 seconds 

Low Battery 

Sounding every 2 seconds 

Overload 

Sounding every 0.5 second 

Fault 

Continuously sounding 

PROTECTI
ON 

Full 
Protection 

Discharge, overcharge, and overload protection 

PHYSICAL 

Dimension, 
DXWXH 
(mm) 

402X117X222 

Net Weight 
(kg) 

4.5 

4.9 

6.5 

ENVIRONM
ENT 

Operating 
Environment 

0- 40°C, 0-90 % relative humidity (non-condensing) 

Noise Level 

Less than 50dB 

INTERFAC

Smart 
RS-232 
Option 

Support Windows family, Linux, IBM Aix, Sun Solaris, Compaq True64, 

UnixWare, FreeBSD, HP-UX, and MAC 

USB Option 

Windows family and MAC 

 

 
 
 

Summary of Contents for ENDURE 1000VA

Page 1: ...USER S MANUAL ENDURE 500VA ENDURE 750VA ENDURE 1000VA ENDURE 2000VA ...

Page 2: ...o different models The inner diameter of the copper ring terminal which is used to connect battery cables to DC terminals should be no less than 6mm 3 For battery installation and maintenance read the battery manufacturer s installation and maintenance instructions prior to operating PERSONAL PRECAUTIONS 1 Have plenty of fresh water and soap nearby in case battery acid contacts skin clothing or ey...

Page 3: ...Modem Phone line surge protection optional and overload protection Optional RS 232 and USB Communication Port WinPower free software available online for real time status monitoring and controlling Auto restart when AC utility is recovered Support Generator Input High Frequency Design with high DC AC Efficiency for higher than 85 Operation Installation Front Panel Controls and LED Indicators Shown...

Page 4: ... again to turn off UPS unit Mains Mode LED The green LED will light steadily when power mains are normal Note The green LED blinks every 2 seconds to indicate that battery is not fully charged when the unit switch on Inverter Mode LED The Yellow LED will light when power mains are abnormal and unit will work in inverter mode Fault LED Red LED will blink or light steadily when fault occurs Back Pan...

Page 5: ...nal Place the battery cable ring terminal over Endure s battery terminal Tighten the M5 nut Do not place anything between the flat part of battery terminal and the battery cable ring terminal since overheating may occur Battery Cable Connection to UPS Endure 500VA 750VA 1000VA 2000VA Caution DO NOT place anything between battery cable ring terminals and battery terminals The terminal stud is not d...

Page 6: ... match the DC voltage requirements of the UPS unit or it may damage both the UPS unit and or the batteries Parallel Connection Wiring batteries in parallel increases the total run times the batteries can operate the AC loads The more batteries connected in parallel the longer the loads can be powered from the UPS unit Series Parallel Connection Series parallel configuration increases both the batt...

Page 7: ...ical 4 8 ms typical 14 ms max INDICATOR AC Mode Green lighting Battery Mode Yellow lighting Battery Charging Mode When battery is not full enough in line mode green flashing every 2 seconds When battery full green lighting Overload Red flashing every 0 5 second Fault Red lighting AUDIBLE ALARM Battery Mode Sounding every 10 seconds Low Battery Sounding every 2 seconds Overload Sounding every 0 5 s...

Page 8: ... Overload 1 Verify that the load matches the capability specified in the specs Back up time is shortened Overload 1 Remove some non critical load Battery voltage is too low 2 Charge battery for 8 hours or more If any abnormal situations occur that are not listed above please call service personnel immediately Appendix A Models Input output cables gauge copper wire Battery cables gauge copper wire ...

Reviews: