
E.
Line And Zero-Crossing Detection
Please refer Figure S-4
1) Line Detection
The input voltage is full-rectified The signal passes through a voltage divider at R45
and R40//r47,feed into pin 8 of CPU. By monitoring this rectified sinusoidal voltage, the
CPU can find the unnaturalness of commercial line. The CPU has two ways to judge line
voltage loss
1.
Waveform detection:
If there is a rapid voltage drop occurs, the CPU is able to immediately detect it
and transfer to battery mode. The waveform detection has a short response time.
2.
RMS value detection:
CPU calculates input RMS value every cycles. If RMS value is not in range
of UPS specification for 3 cycles ,UPS will transfer to battery mode. The RMS
value detection has a more accurate voltage detection but it can not immediately
sense a rapid voltage transition.
2) Zero Crossing Detection
Zero Crossing Detection is used to minimize the phase difference between the
Inverter voltage and the input line voltage while UPS is switching from battery mode
to line mode. If the phase difference is too large, it can create a large amount of energy
which may damage the internal passive components such as relays.
The Zero Crossing signal is get by the following ways:
1.
Use the voltage reduced from input line voltage(by resistor R49) to drive
Q14(2222ASM).
2.
The Zero Crossing signal comes from the collector of Q14,goes to the CPU pin 1.
Refer to Figure W-2, Waveform measured from Q14 collector and line input.
When the line signal (reduced from input line) is applied to the base of Q14,the first
half cycle(positive half-wave) makes V
BE
<0 Volts , that turns off Q14. The second half
cycle (negative half-wave) causes V
BE
>0.5Volts and turns on Q14.
When Q14 is off, the +5 Volts is charging C23. Hence the V
CE
of Q14 changes from
0 to +5 Volts. As Q14 turns on, C23 discharges immediately. Thus, the line frequency
can be detected by measuring the time interval between the first falling and second falling
edge of V
CE
of Q14. Also It is used by the CPU to determine when to switch from battery
mode to line mode.
10
Summary of Contents for 400VA
Page 8: ...Figure S 1 Control Power circuit 6 ...
Page 9: ...CH1 C15 GND Figure W 1 Cold Start 7 ...
Page 11: ...Figure S 2 Charger circuit 9 ...
Page 13: ...Figure S 3 Line and Zero Crossing Detecting circuit 11 ...
Page 14: ...CH1 Line I P CH2 Q14 collector Figure W 2 Zero Crossing 12 ...
Page 16: ...Figure S 4 Inverter circuit 14 ...
Page 17: ...CH1 DS1 CH2 Output Voltage 1 200V Figure W 3 Inverter Circuit 1 15 ...
Page 18: ...CH1 DS2 CH2 Output Voltage 1 200 Figure W 4 Inverter Circuit 2 16 ...
Page 20: ...CH1 CLAMP OFF signal CH2 output voltage 1 200V Figure W 5 Clamp circuit 18 ...
Page 23: ...Figure S 5 CPU circuit 21 ...
Page 24: ...Figure S 6 Relay Circuit 22 ...
Page 25: ...CH1 C10 GND CH2 Output Voltage 1 200V Figure W 6 Relay speed up capacitor 23 ...
Page 27: ...Figure S 7 Panel circuit 25 ...
Page 33: ...Figure W 7 Battery mode examination flowchart Figure W 8 Line mode examination flowchart 30 ...