CentraLine EAGLEHAWK NX Mounting Instructions Download Page 4

EAGLEHAWK NX CONTROLLER - MOUNTING INSTRUCTIONS 

Manufactured for and on behalf of the Environmental & Energy Solutions Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:

 

 
CentraLine 
Honeywell GmbH 
Böblinger Strasse 17 
71101 Schönaich, Germany 
Phone  +49 (0) 7031 637 845 
Fax 

+49 (0) 7031 637 740 

[email protected]

 

www.centraline.com 

 

 
 
 
 
 
 
Subject to change without notice 
MU1Z-1039GE51 R0418A 

 

 

 

 

 

SPECIFICATIONS OF CONTROLLER 

Power supply 

19 … 29 VAC, 50/60 Hz, 
or 20 … 30 VDC 

Power con-
sumption 

typically DC: 7 W; max. 9 W 
typically AC: 10 VA; max. 12 VA 

Current con-
sumption 

typically DC: 300 mA; max. 375 mA 
typically AC: 400 mA; max. 500 mA 

Heat dissipation 

max. 6 W at DC power supply, 
max. 11 W at AC power supply 

Ambient tem-
perature 

0 … 40 °C (wall-mounting) 
0 … 50 °C (cabinet/door mounting) 

Storage temp. 

-20 … +70 °C 

Humidity 

5 … 95% r.h. non-condensing 

Dimensions 

See pictures 0B, 0C. 

Degree of 
protection 

IP20 (mounted on walls, with two 
accessory MVC-80-AC1 covers) 

Fire class

 

V0 

 

CABLE SPECS, PUSH-IN TERMINALS 

plug gauge

 

0.2 … 1.50 mm

2

 

solid conductor H05(07) V-K

 

stranded conductor H05(07) V-K

 

stranded conductor with wire end 
ferrules (w/o plastic collar)

 

stripping length

 

10.0 +1.0 mm

 

 

WEEE DIRECTIVE 

WEEE: Waste Electrical and 

Electronic Equipment Directive 

 

  At the end of the product life, dispose 

of the packaging and product in an 
appropriate recycling center. 

  Do not dispose of the device with the 

usual domestic refuse. 

  Do not burn the device. 

 

WIRING PUSH-IN TERMINAL PLUGS 

 

 

STANDARDS, APPROVALS, ETC. 

Purpose of the device is: multifunctional non-safety control 
intended for HVAC in home (residential, commercial, and light-
industrial) environments 
Device meets EN 60730-1, EN 60730-2-9, UL60730, and 
UL916. 
Independently mounted electronic control unit with fixed wiring.
Shock protection: Class II. 
Pollution degree: 2. 
Installation: Class 3 
Rated impulse voltage: 300 V for SELV, 2500 V for relay 
outputs 
Type of action: Type 1.C. 
Software Class: A. 
Ball-pressure test temperature: housing parts > 75 °C 
terminals > 125 °C 

NOTE:

  Keep AC mains supply/load cables separate from 

signal wiring! 
 

NETWORK SECURITY 

Honeywell hereby expressly states that the EAGLEHAWK NX is not inherently protected against cyber attacks from the Internet 
and that it is therefore intended solely for use in private, protected networks. For more information, see also section "Network 
Security" of 

EAGLEHAWK NX Controller – Product Data (EN0Z-1039GE51)

 and 

General Security Best Practices – 

Security Document (EN0Z-1040GE51)

For fixes, guidance, patches, etc., see also: 

https://www.tridium.com/en/support/products/technical-bulletins

 

 

Summary of Contents for EAGLEHAWK NX

Page 1: ... recalar o con la documentación de la instalación NL Deze handleiding moet bij de regelaar of met de documentatie van de installatie worden bewaard PL Instrukcję obsługi należy przechowywać przy urządzeniu albo w dokumentacji technicznej 0A INFO 0B DIMENSIONS CLNXEHxxx WITHOUT COVER LICENSING INFORMATION TO OBTAIN THE PURCHASED LICENSE GO TO AND THEN LOG IN ENTER YOUR HOST ID AND DOWNLOAD THE LICE...

Page 2: ... 23 2 3 1 CLICK 2 3 1 ALTERNATIVE A ALTERNATIVE B 2X CLICK J1 J8 1B DIN RAIL DISMOUNTING 2 WALL MOUNTING 3 2 1 SHD RESET C C OT OT PB a PB b CGND WMB BI1 BI2 BI3 BI4 GND PT1k PT1k UI1 UI2 UI3 UI4 UI5 UI6 UI7 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 UI8 47 RS232 HMI Tool IN DO9 DO1 DO2 DO3 IN IN4 DO4 DO5 IN5 IN6 DO6 DO7 IN7 IN8 DO8 GND AO1 AO2 AO3 3 4 5 6 7 8 9 10 11 12 ...

Page 3: ...TING 6X 5A WIRING 5B WIRING CLNXEHxxx PANTHER TIGER LION etc PANTHER TIGER LION etc PW3 PW20 PW60 etc PW3 PW20 PW60 etc CLNXEHxxx PoE ENABLED DEVICE PoE ENABLED DEVICE RJ45 CLNXEHxxx CLNXEHxxx 230 VAC 120 VAC 230 VAC 120 VAC 230 VAC 120 VAC 230 VAC 120 VAC 24 VAC 0 V 24 VAC 0 V 24 VAC 0 V 24 VAC 0 V RJ45 CLNXEHxxx GND1 GND2 485 1 485 2 485 1 485 2 n a n a n a 24 25 26 27 28 29 30 31 32 24V 0 24V 1...

Page 4: ... 0 mm WEEE DIRECTIVE WEEE Waste Electrical and Electronic Equipment Directive At the end of the product life dispose of the packaging and product in an appropriate recycling center Do not dispose of the device with the usual domestic refuse Do not burn the device WIRING PUSH IN TERMINAL PLUGS STANDARDS APPROVALS ETC Purpose of the device is multifunctional non safety control intended for HVAC in h...

Reviews: