The Model CHEC Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:

NOTES

When properly installed, there is a
nominal 5/32 inch (4,0 mm) air gap
between the lip of the Cover Plate and
the ceiling, as shown in Figure 2. This
air gap is necessary for proper opera-
tion of the sprinkler. If the wall is to be
repainted after the installation of the
Sprinkler, care must be exercised to
ensure that the new paint does NOT
seal off any of the air gap.

Factory painted Cover Plates MUST
NOT be repainted. They should be re-
placed, if necessary, by factory
painted units.

Do not pull the Cover Plate relative to
the Enclosure. Separation may result.

Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down
the affected fire protection system
must be obtained from the proper
authorities and all personnel who may
be affected by this action must be no-
tified.

Page 4 of 6

TFP265

Response

Coverage

Minimum

Minimum

Deflector-

Sprinkler

Lateral

Rating

Area

(1)

,

Flow

(2)

,

Pressure

(2)

,

To-Ceiling

Temperature

Minimum

Ft. x Ft. (m x m)

GPM (LPM)

PSI (BAR)

Distance

(3)

, In. (mm)

Rating, °F

Spacing

(4)

,

Ft. (m)

Quick

16 x 14 (4,9 x 4,3)

26 (98)

10.6 (0,73)

4 to 12 (100 to 300)

135 or 155

10 (3,1)

Quick

16 x 16 (4,9 x 4,9)

26 (98)

10.6 (0,73)

4 to 12 (100 to 300)

135 or 155

10 (3,1)

Quick

16 x 18 (4,9 x 5,5)

29 (110)

13.1 (0,90)

4 to 12 (100 to 300)

135

10 (3,1)

Quick

16 x 20 (4,9 x 6,1)

36 (136)

20.3 (1,40)

4 to 12 (100 to 300)

135

10 (3,1)

Quick

16 x 22 (4,9 x 6,7)

36 (136)

20.3 (1,40)

4 to 12 (100 to 300)

135

10 (3,1)

TABLE A

UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA

NOTES

1. Backwall (where sprinkler is located) by sidewall (length of throw).

2. Requirement is based on minimum flow in GPM from each sprinkler. The indicated residual pressures are based on the nominal
K-factor.

3. The centerline of the sprinkler waterway is located 7/16 inch (11,1 mm) below the deflector (Ref. Figure 2).

4. Minimum spacing is for lateral distance between sprinklers located along a single wall. Otherwise adjacent sprinklers (i.e., sidewall
sprinklers on an adjacent wall, on an opposite wall, or pendent sprinklers) must be located outside of the maximum listed protection
area of the extended coverage sidewall sprinkler being utilized.

FIGURE 3

W-TYPE 7 SPRINKLER

WRENCH

FIGURE 4

PROTECTIVE CAP

RECESS

WRENCH

WITH SPRINKLER

ENGAGEMENT

IN TO ENSURE

WRENCHING AREA

PUSH WRENCH

CAP

PROTECTIVE