background image

Product
Description

*For specific listing requirements, see the appropriate

information contained in this brochure.

The Omega Model C-1A Quick

Response Commercial Pendent
Automatic Sprinkler is a low profile,
aesthetically pleasing, ceiling mounted
sprinkler that offers a high degree of
protection for human life.  It operates
five to six times faster than a standard
sprinkler and features a spray pattern
that has been shown to be effective in
the control or extinguishment of fire.

The Model C-1A incorporates a

significant cost saving feature; a
special escutcheon assembly that pro-
vides for 

7

/

8

(22.2 mm)

 of field adjust-

ment resulting in an easily accom-
plished, tight fit against the ceiling.

The Model C-1A carries a Listing*

by Underwriters Laboratories for use
as a Quick Response Commercial
Sprinkler that qualifies for installation
in accordance with current NFPA 13
and NFPA 13R Standards.

The Model C-1A is available in three

standard finishes.  Its mating escutch-
eon plate is available in three stan-
dard finishes with additional special
finishes available.

Operation:  A fusible alloy pellet is

compressed by a bearing disc into a
copper housing by a ball plunger.
Heat is absorbed by the heat collect-
ing fins and conducted to the alloy
pellet.  At the rated temperature, the

Manufactured by:  Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446

1-98

C-1A

Technical
Data

3

/

8

&

 

1

/

2

"

(9.5 mm)

 

& (12.7 mm)

Orifice
Adjustable
Pendent
Automatic
Sprinkler

alloy melts, causing the ball plunger to
drop, freeing balls from the retaining
groove.  This movement allows
system water pressure to force the
orifice sealing mechanism and deflec-
tor assembly open.  Water is then
discharged in a designed flow pattern.

Omega C-1A

Quick Response Commercial
Automatic Sprinkler

Model:  C-1A
Style:

Pendent (adjustable)

Escutcheon:
Wrench:  Omega Adjustable Model A

Sprinkler Wrench

Orifice Size:  

3

/

8

(9.5 mm)

 or 

1

/

2

(12.7 mm)

K-Factor:

3

/

8

" = 2.7 

(38.6 Metric)

1

/

2

"

 

= 5.6 

(80.1 Metric)

Thread Size:  

1

/

2

(15 mm) 

N.P.T.

Temperature Rating: 145

°

F/63

°

C

160

°

F/71

°

C

200

°

F/93

°

C

Approvals:

3

/

8

(10 mm) 

 - U.L. only

1

/

2

(15 mm) 

 - U.L., ULC,

MEA (46-92-E Vol. III)

Maximum Working Pressure:

175 psi / 12.1 bar

Factory Hydro Test: 100% at

500 psi / 34.5 bar

Standard Finishes:

Sprinkler:  chrome plated, brass

plated, white painted

Escutcheon:  chrome plated, brass

plated, white painted

Adjustable Range Below Ceiling:

3

/

8

(9.5 mm) 

 to 1

1

/

4

(31.8 mm)

Highest Allowable Ambient Temp:.

100

°

F/38

°

C for 145

°

F rating

100

°

F/38

°

C for 160

°

F rating

150

°

F/66

°

C for 200

°

F rating

Length: 2

7

/

16

(61.9 mm)

Width:

1

1

/

4

(31.8 mm)

Weight: 3.2 oz. 

(91 grams)

No.1-10.0

OBSOLETE

Summary of Contents for Omega C-1A

Page 1: ...by the heat collect ing fins and conducted to the alloy pellet At the rated temperature the Manufactured by Central Sprinkler Company 451 North Cannon Avenue Lansdale Pennsylvania 19446 1 98 C 1A Technical Data 3 8 1 2 9 5 mm 12 7 mm Orifice Adjustable Pendent Automatic Sprinkler alloy melts causing the ball plunger to drop freeing balls from the retaining groove This movement allows system water ...

Page 2: ...Drop 1 x 1 2 25 mm x 15 mm NPT Reducing Coupling Dust Cover 2 5 8 66 7 mm Max 1 3 4 44 5 mm Min 2 3 8 60 3 mm Flush take out 1 1 4 31 8 mm Max 3 8 9 5 mm Min 5 8 15 9 mm Flush Finished Ceiling Line 1 9 16 39 7 mm Max 11 16 17 5 mm Min 1 5 16 33 3 mm Flush Installation Diagram Omega C 1A Commercial Quick Response Omega Adjustable Model A Sprinkler Wrench O B S O L E T E ...

Page 3: ...ge Step 5 Leave the protector cap in place until the installation is finished When the system is ready for service remove the cap Step 6 To install the escutcheon plate align it with and press it over the sprinkler body until the outer edge of the escutcheon meets the mounting surface CAUTION Special care must be taken when installing with a CPVC system Sprinklers must be installed after the CPVC ...

Page 4: ...ation additional sprinklers should be installed to maintain the protection level Do not attempt to replace sprinklers without first removing the fire protec tion system from service Be certain to secure permission from all Authori ties Having Jurisdiction and notify all personnel who may be affected during system shutdown A fire watch during maintenance periods is a recom mended precaution To remo...

Reviews: