ELO-231SA.3
©1997 Central Sprinkler Company
Printed in U.S.A.
The owner is responsible for the proper
operating condition of all fire protection
devices and accessories. The NFPA
Standard 25 entitled,
“Inspection Testing
and Maintenance of Water-Based Fire
Protection Systems”, contains guidelines
and minimum maintenance requirements.
Furthermore, the local
Authority Having
Jurisdiction may have additional regula-
tions and requirements for maintenance,
testing, and inspection that must be
obeyed.
It is advisable to have sprinkler systems
inspected regularly by a qualified inspec-
tion service. Length of time between such
inspections can vary due to accessibility,
ambient atmosphere, water supply, and
site activity.
Do not attempt to reassemble or
otherwise reuse a sprinkler that has
operated. Replace any sprinkler exhibiting
corrosion or damage; always use new
sprinklers of the same type and tempera-
ture rating as replacements.
Do not attempt to replace sprinklers
without first removing the fire protection
system from service. Be certain to secure
permission from all
Authorities Having
Jurisdiction, and notify all personnel who
may be affected during system shutdown.
A fire watch during maintenance periods is
a recommended precaution.
To remove the system from service
mode, first refer to the system operating
guide and valve instruction. Drain the
water and relieve pressure in the pipes.
Remove the existing unit and install the
replacement, using only the special
sprinkler wrench. Be certain to match
model, style, orifice, and temperature
rating.
A fire protection system that has been
shut off after an activation should be
returned to service immediately. Inspect
the entire system for damage and
replace or repair as necessary. Sprin-
klers that did not operate but were
subjected to corrosive elements of
combustion or excessive temperatures
should be inspected, and replaced if
need be. The
Authority Having Jurisdic-
tion will detail minimum replacement
requirements and regulations.
Guarantee: Central Sprinkler Company
will repair and/or replace any products
found to be defective in material or
workmanship within a period of one year
from the date of shipment. Please refer
to the current Price List for further details
of the warranty.
Wet pipe systems must be protected
from freezing.
Upon completion of the installation, the
system must be tested per recognized
standards.
In the event of a thread leak, remove
the unit, apply new pipe joint compound
or tape, and reinstall.
Installation Sequence
Step 1. The unit must be installed in the
upright or pendent position.
Step 2. Use only a non-hardening pipe
joint compound or Teflon* tape. Apply
only to the male threads.
*Teflon is a trademark of the DuPont Corp.
Step 3. Hand tighten the sprinkler into
the fitting. Use a Central ELO Sprinkler
Wrench, to tighten the unit into the fitting.
A leak-tight joint requires only 7 to 14 ft.-
lbs. of torque; a tangential force of 14 to
28 lbs. delivered through a 6" handle will
deliver adequate torque. Torque levels
over 21 ft.-lbs. may distort the orifice
seal, resulting in leakage.
The sprinkler shall, per NFPA, be
oriented so the frame arms are parallel
with the branch line pipe.
Central Sprinkler Company
451 N. Cannon Avenue, Lansdale, PA 19446
Phone (215) 362-0700
FAX (215) 362-5385
Ordering Information: When placing an
order, indicate the full product name.
Please specify the quantity, model, style,
orifice size, temperature rating, type of
finish or coating, and sprinkler wrench.
Availability and Service: Central
sprinklers, valves, accessories, and other
products are available throughout the
U.S. and Canada, and internationally,
through a network of Central Sprinkler
distribution centers. You may write
directly to Central Sprinkler Company, or
call (215) 362-0700 for the distributor
nearest you.
Patents: Patents are pending.
Conversion Table:
1 inch = 25.400 mm
1 foot = 0.3048 M
1 pound = 0.4536 kg
1 foot pound = 1.36 Nm
1 psi = 6.895 kpa
= 0.0689 bar
= 0.0703 kg/cm
2
1 U.S. gallon = 3.785 dm
3
= 3.785 liters
Conversions are approximate.
OPTIMA™ is a registered trademark of
Central Sprinkler Company.
Ordering
Information
Care &
Maintenance
Sprinklers must be handled carefully.
They should not be transported or stored
where ambient temperature may exceed
100
o
F/38
o
C. For best results, store them
in a dry, cool location in the original
shipping package.
Do not install sprinklers that have been
dropped or visibly damaged. Sprinklers
should never be painted, coated, plated,
or altered in any other way from manufac-
tured condition or they may not function
properly. Any sprinklers altered in such
manner must be replaced.
ELO/ESLO/ESFR Combination
Wrench (Part #1073)
OBSOLETE