background image

Cover Removal

1

3

2

Located 
at base 
of battery 
enclosure

You have now installed the Programmable Thermostat. For gas boiler applications, the factory system settings will not 
need to be changed (for other applications see below). You can now use the USER GUIDE to program the unit and 
demonstrate how it works to the homeowner.

Application 

Settings 

What to change

Using the Programmable Thermostat for Specific Applications

 

Cycle /Hour 

Minimum ON time 

Note: All parameters listed below belong to category 2 

 

 

 

– system parameters (see Installer Parameter Table)

Gas Boiler (<30kW) 

No changes required

Oil Boiler 

Set 1:Ot parameter to 4 

 

 

 

Set 2:Cr parameter to 3

Thermal Actuator 

12 

Set 2:Cr parameter to 12

Zone Valve 

No changes required

Electric Heating 

12 

Set 2:Cr parameter to 12 

(resistive load 3-5A)

Entering the Installer Mode

1.

  Press the 

OFF 

button.

2. 

Press and hold the   button and the two 

PROGRAM

 

 and   buttons together. 

3. 

The unit will display the first parameter of installer 
parameter group category 1 (from Parameter No. 1 to 
20).

4. 

Press the     or   button to change the factory 
setting. The display will flash indicating that a change 
has been made.

5. 

Press the 

 button to confirm the change. The display 

will stop flashing.

6. 

Press the     button to go to the next parameter.

7. 

Press the 

PROGRAM

   button to go to Installer 

parameter group category 2 (from Parameter No. 1 to 5).

8. 

To exit installer mode, press the 

AUTO

MAN 

or 

OFF 

button.

COPY

DAY

DATE/

DAY

1..4

AUTO

MAN

OFF

PROGRAM

MANAUTO

Mon

Tue

Wed

Thu

Fri

Sat

Sun

1

COPY

DAY

DATE/

DAY

1..4

Mon

Tue

Wed

Thu

Fri

Sat

Sun

AUTO

MAN

OFF

1 2

PROGRAM

2

2