Note: Some Electric Steam Boilers are equipped with water feeder or pump. If
so, the shutoff valve must be installed upstream from the water feeder or
pump.
The shutoff valve should be in the closed position and remain so until the
installation is complete.
Note: For all piping connections, the use and / or type of joint compound or
sealer on the joint should be determined by referring to local codes,
accepted practices, or the requirements of the installing contractor.
Hot / Boiler Water Outlet
The next step in the installation process is to connect the hot / boiler water system
piping to the hot / boiler water outlet port. The exact location of this port for the
specific unit, as well as outlet pipe diameter or flange size, can be determined from
the C.A.D. Drawing supplied with the Submittal Sheet.
A manual shutoff valve and automatic check valve should be installed downstream
on the hot / boiler water line as isolation devices in case the unit must be
disconnected from the system. The shutoff valve should be in the closed position
and remain so until the installation is complete.
Note: Refer to local codes and specifications for site specific shutoff and check
valve requirements. For all piping connections, the use and / or type of
joint compound or sealer on the joint should be determined by referring
to local codes, accepted practices, or the requirements of the installing
contractor.
Connecting the Electric Power Source
t
All installation procedures involving electric power connection should only be
performed by trained, certified electricians.
t
Hot / boiler water presents a situation that can be
very dangerous
because of the
high temperatures and pressures. Use common sense and follow all accepted and
recommended procedures when performing installation, operation, and
maintenance procedures to avoid possible injury or death.
t
The combination of electricity and water can pose a
very dangerous situation
.
Assure that all power has been
shut off / disconnected and locked out
in an
approved manner, before attempting any installation or maintenance procedures.