CellarPro 1800XT Owner'S Manual Download Page 21

 

 

 

 

 

20

 

The Cooling Unit Is Dripping 

The cooling unit is designed to remove excess moisture from inside the cellar, which 

collects in the drip pan of the cooling unit.  

Excess moisture can occur when the cooling unit runs constantly, when the Minimum 

Set Point is too low and/or when the cellar doesn’t have a good seal from the outside 
environment. To eliminate overflow in the drip pan, do the following: 

1.

 

Raise the Minimum Set Point of the cooling unit to 14.4°C or above. 

2.

 

Make sure the cellar has good seals, especially at the door(s), and repair any 
leaks immediately. 

3.

 

If your wine cooling unit came with a condensate fitting and drain line, make 
sure you properly setup the condensate trap (Chapter II). 

If the cooling unit continues to drip, contact us at 1.877.726.8496 for further 
assistance.  

 

 

The HA2 Alarm has been triggered 

The cooling unit is designed to measure the temperature of the condenser coils and, 
if the temperature exceeds 60

°

C for more than 2 hours, the HA2 alarm will display on 

the control panel. 

If this alarm happens when you first receive and start operating your CellarPro 
cooling unit, check for appropriate installation and ventilation (Chapter II).  Also, 
make sure that there aren’t any obstructions to the intake and/or exhaust vents.  If 
your wine cabinet has a grill, remove the grill and/or any other obstructions above 
(top vent) or behind (back vent) the cellar.   

If the alarm happens in conjunction with hot ambient conditions, we recommend 
doing the following: 

1.

 

Raise the Minimum Set Point to 15.6

°

C until temperatures cool down 

2.

 

Increase the Fon setting  

If the cooling has been operating for several months without any problems and the 
alarm happens “out of the blue”, check the condenser coils and clean if necessary. 

If the HA2 alarm continues to be triggered, contact us at 1.877.726.8496 for further 
assistance. 

Summary of Contents for 1800XT

Page 1: ......

Page 2: ...have questions please don t hesitate to contact your dealer or CellarPro directly We can be reached during normal business hours at 1 877 726 8496 You also may contact us anytime via email at info ce...

Page 3: ...2 This page left blank...

Page 4: ...3 T a b l e o f C o n t e n t s I Prior to Installation 4 II Installation Instructions Wine Cellars 5 III Operating Instructions 12 IV Troubleshooting 19 V Limited Warranty 22...

Page 5: ...display Make sure that the exhaust panel is installed in the correct position it should cover either the TOP or the REAR exhaust vent o TOP VENT CONFIGURATION If the hot air will be discharged through...

Page 6: ...its The unbold numbers in black are within the capacity for the 1800XT 60Hz but not for the 1800XT 50Hz The numbers in red are beyond the capacity of both cooling units Cellar Temp 12 8 C 15 6 C BTUH...

Page 7: ...of the cooling units Insulation CellarPro cooling units are designed to be installed inside wine cellars that have proper insulation moisture barriers and an airtight seal from the environment outside...

Page 8: ...modification does not replace the requirement for a cellar to have proper insulation moisture barriers and airtight seals from the environment outside the cellar If your cooling unit has the wine cel...

Page 9: ...he cellar the cooling unit pulls the warm air through the evaporator coils and removes the heat from the warm air Once cooled the cold air is discharged from the bottom of the cooling unit and circula...

Page 10: ...below the cooling unit as follows Once the cooling unit is installed all cracks and gaps between the cooling unit and the cellar should be sealed We provide butyl tape shipped in the cavity of the exh...

Page 11: ...cellar and exhaust space The hot air exhaust cannot be ducted without an inline fan to augment the airflow inside the duct Rear vent configuration most common in this configuration the panel is attach...

Page 12: ...ts at 50Hz and 198 254V single phase environments at 60Hz The cooling unit uses approximately 2 0 amps during its on cycle The power plug provided is Nema 6 15P 15A 250V Plug Male with a screw cover p...

Page 13: ...of the cellar environment Therefore it is not uncommon for the cooling unit to run nonstop for up to a week initially depending on the temperature inside the cellar the size of the cellar and the tem...

Page 14: ...the range of 12 8 15 6 C CellarPro cooling units are designed to maintain appropriate levels of humidity ranging from 50 to 70 percent inside wine cellars In order to increase or decrease humidity in...

Page 15: ...ing unit is factory preset with a Minimum Set Point of 14 4 C and a Temperature Differential of 2 2 C This means that the cooling unit will turn on when the display rises above 16 6 C 14 4 C 2 2 C and...

Page 16: ...ifferential is unchanged Quick Chill Button To activate the Quick Chill mode press the Up Quick Chill button for three seconds To deactivate Quick Chill press Quick Chill button for three seconds agai...

Page 17: ...EMPERATURE DIFFERENTIAL The factory preset for this setting is 2 2 This setting determines the Temperature Differential and therefore the temperature at which the cooling unit will cycle on The recomm...

Page 18: ...A2 alarm as described below If you d like to turn on this protection mechanism please call us toll free at 877 726 8496 P3 60 C for more than 2 hours The condenser probe is measuring temperatures that...

Page 19: ...oo high above 60 C for 2 hours Check for appropriate installation ventilation ambient conditions and cooling capacity Chapter II Clean the condenser coils see Maintenance in Chapter IV Check for obstr...

Page 20: ...oaded in the cellar the cooling unit will run continuously even up to a week until the temperature inside the cellar falls below the Set Point After the temperatures inside the wine cellar reach equil...

Page 21: ...riggered The cooling unit is designed to measure the temperature of the condenser coils and if the temperature exceeds 60 C for more than 2 hours the HA2 alarm will display on the control panel If thi...

Page 22: ...lay on the control panel To reduce the alarm temperature setting do the following 1 Depress the Set and Down button for three seconds until the display reads HY 2 Depress the Set and Down button again...

Page 23: ...by any cause beyond the control of CellarPro shall not be considered defects in material or workmanship and are not covered by the warranty The limited warranty does not cover any parts or labor to co...

Reviews: