www.cellarcool.com | Page 23

OPTIMUM  SERIES

TROUBLESHOOTING GUIDE

Unit has ice forming on the evaporator 

Possible cause

Solution

Evaporator coil is dirty

Clean coil with a vacuum. If coil is very dirty, use a spray bottle with a 
small amount of liquid dish detergent. Spray coil, let set for 5 minutes, 
then flush with fresh water.

Something is blocking the supply and/or return air

Remove blockage

Evaporator fan is not turning on

Call installing technician to troubleshoot

The temperature of the room to which the unit is exhausting has 
dropped below 50°F

Raise the temperature of the exhaust room

Unit has not gone through an Anti-Frost Cycle

Check for ice in the depth of the coil. Melt with blow drier until coil is 
warm to the touch. Soak up water with a towel.

Unit continues to ice

Observe ice formation pattern. If only part way up the coil face, unit 
could be low on refrigerant. If all the way up, the coil may be dirty or 
airflow is blocked.

Unit does not run/power up 

Possible cause

Solution

Unit is not plugged in

Make sure the unit is plugged into an outlet

No power to outlet

Contact an electrician

Line voltage is incorrect rating for unit

Check line voltage to make sure there is 110V-120V

Room at setpoint

Lower setpoint

Thermostat not calling for cooling

Lower setpoint

Faulty thermostat or wiring

Call Customer Service at 1-800-343-9463

Cellar temperature is too warm

Possible cause

Solution

Temperature of the room unit is exhausting to has exceeded 85°F

Intake temperature needs to drop below 85°F

Unit is undersized for the cellar

Order correctly sized unit

Something is blocking the supply and/or return air on evaporator or 
condenser side of the unit

Remove airflow obstruction

Unit is mounted too low in the cellar

Relocate unit so the distance from the ceiling and top of the unit is no 
more than 18”

One or more of the fans is not turning on

Call Customer Service at 1-800-343-9463

Compressor is not turning on

Call Customer Service at 1-800-343-9463

Compressor keeps cycling on overload

Make sure all fans are working and there is no airflow obstruction

Poor seal around door

Make sure there are no air gaps around the door. If door seal is 
damaged, replace it.

Controller set too high

Lower the setpoint

Evaporator coil is frosted or iced up

Observe ice formation pattern. If only part way up the coil face, unit could 
be low on refrigerant. If so, call Customer Service at 1-800-343-9463.

System runs constantly

Possible cause

Solution

Leaky door seal or poorly insulated cellar

Fix leaky door seal and insulate cellar in accordance with this manual 
(page 8)

Summary of Contents for Optimum 2200

Page 1: ...OPTIMUM SERIES OWNER S MANUAL Optimum 2200 Optimum 3300 Optimum 4400 Optimum 8800 Tech Support 1 800 343 9463 ext 801 Hours Monday through Friday 7 AM 4 PM...

Page 2: ...not responsible for printing or clerical errors CellarCool reserves the right to make corrections or improvements to the information provided and to the related hardware at any time without notice Vi...

Page 3: ...Installation Location 11 Preparing the Unit for Installation 12 Installing the Unit through the Wall 13 Condensation Drain Line 14 Liquid Measuring Thermostat System 15 System Operation 15 Controller...

Page 4: ...rCool Cooling Unit The CellarCool cooling unit is a specialized refrigeration unit designed for one purpose only to maintain the optimal temperature and humidity levels conducive to the proper storage...

Page 5: ...back Use the selector switch located on the right side of the unit to select the inlet you would like to use 5 The unit is designed to gently cool down the temperature of the cellar over time by cycl...

Page 6: ...locations on the shipping container or fully support the unit from underneath A shipment may include one or more boxes containing accessories Inspect the packaging for any obvious signs of damage or m...

Page 7: ...www cellarcool com Page 5 OPTIMUM SERIES QUICK REFERENCE GUIDE Front Side View Rear Side View Controller Control panel see page 10 for details Air sensor Probe Input Drain port Bottle probe...

Page 8: ...ere are circumstances in which a cellar design may require a larger unit due to preexisting design restrictions Certain building materials such as glass stone or concrete may seem adequate but do not...

Page 9: ...ferred for interior cellar walls and R 30 for ceilings and exterior walls Mounting the Unit The unit should be mounted within 18 inches of the ceiling in order to achieve sufficient cooling As the roo...

Page 10: ...space The system will operate more efficiently with a greater amount of air to exchange NOTE Do not attempt to mount the unit in a wall recess or attempt to camouflage or cover the unit with any sort...

Page 11: ...a specially designed ducting plenum for the unit Using any other ducting system will void the warranty NOTE If you are unsure whether you have adequate ventilation in your install location please cont...

Page 12: ...ower surges and spikes can damage sensitive electrical equipment CellarCool recommends plugging the unit into a surge protector or power conditioner in order to protect your system As outlined in our...

Page 13: ...l not to cut into the studs themselves Make the second horizontal cut from stud to stud on the line 16 inches below the first cut Once the horizontal lines have been cut make vertical cuts using the i...

Page 14: ...e mounting bracket then cut remove paper backing and secure Do the same on the opposite side of the bracket Discard any excess The foam tape will create a tight seal between the bracket and the wall M...

Page 15: ...the mounting bracket spanning the distance between the pieces of tape on the top and bottom edges of the mounting bracket then cut remove paper backing and secure Do the same on the opposite side of t...

Page 16: ...blems associated with excess condensation Failure to use the condensation drain line tube will void the warranty on the unit Condensate Evaporator The SC units come equipped with a condensate manageme...

Page 17: ...tap water 3 Place bottle probe securely into bottle as seen in Figure 1 4 Place the wine bottle in your wine cellar Ensure sensor tip is fully submerged 5 To ensure a consistent temperature place bott...

Page 18: ...or a maximum of ten minutes The unit will then return to normal operation If the evaporator is not above 26 F after the Anti Frost Cycle has ended the red error light will display in the upper right c...

Page 19: ...release the set button again While the current temperature setting is displayed press the up or down arrows to change set point When the display shows the desired temperature setting press and release...

Page 20: ...time out 1 Check the evaporator coil for ice buildup unplug the unit and allow the coil to thaw before restarting 2 Make sure the room the intake air is not less than 60 F 3 If the unit continues to...

Page 21: ...www cellarcool com Page 19 OPTIMUM SERIES OPTIMUM 2200 3300 CONTROLLER WIRING SCHEMATIC OPTIMUM 2200 3300...

Page 22: ...Page 20 CX 011420 OPTIMUM 4400 CONTROLLER WIRING SCHEMATIC OPTIMUM 4400...

Page 23: ...33mm AFL Blower YELLOW BROWN GREY Capacitor 133mm AFL Blower YELLOW BROWN GREY Capacitor Compressor BLUE WHITE BLACK BLACK BROWN BLACK BLACK BLACK WHITE WHITE POWER SUPPLY 115 VAC 60 Hz 20A POWER CORD...

Page 24: ...Page 22 CX 011420 NOTES...

Page 25: ...110V 120V Room at setpoint Lower setpoint Thermostat not calling for cooling Lower setpoint Faulty thermostat or wiring Call Customer Service at 1 800 343 9463 Cellar temperature is too warm Possible...

Page 26: ...nser coil as a possible cause of compressor overheating If problem repeats call Customer Service at 1 800 343 9463 Evaporator fan runs but compressor does not Possible cause Solution Unit is running a...

Page 27: ...ing the supplied drain line brush clean the interior drain line leading from the drip tray and drop a pan tab into the drip tray see illustration below for more details Quarterly Use a vacuum with bru...

Page 28: ...s Sizing Assistance 1 855 235 5271 Fax 209 466 4606 CellarCool offers accessories to enhance and customize your wine cooling unit Exterior Grille The exterior grille protects the unit from the weather...

Page 29: ...d in the event the Product is not repairable in the field cover normal ground freight charges within the continental United States for the repair or replacement of the Product B Five 5 Year Compressor...

Page 30: ...Owner s Manual and thereafter the End User must follow the required installation use and maintenance procedures set forth by CellarCool in CellarCool s Owner s Manual The Owner s Manual is shipped wit...

Page 31: ...t 1738 East Alpine Avenue Stockton California 95205 8 Miscellaneous Terms and Conditions A Return Policy All return inquiries must be made within thirty 30 calendar days of the original purchase of a...

Page 32: ...9463 or please send a letter via U S Mail to Customer Service CellarCool Corporation 1738 E Alpine Ave Stockton CA 95205 Email support cellarcool com Web www cellarcool com B Technical Assistance Cell...

Page 33: ...CellarCool 1738 E Alpine Ave Stockton CA 95205 1 800 343 9463 www cellarcool com...

Reviews: