Fig. 7. View of
ADAConfig
software interface
6.4. DATA TRANSMISSION DIAGNOSTICS
To readout diagnostics set SW1 to configuration mode (see pt OPERATION MODE).
Correctness of transmission proceed on RS232 and Fibre-Optic interfaces can be checked by readout the errors list by
ADAConfig
s
oftware from the converter memory. Frames error counter will be increased, in case of: improper speed set compared to real speed
of data transmission. Parity error counter will be count the errors which can arise in case of misrepresent bytes in transmitted sign.
This counter will not work in case of disable control parity
To check those counters press the button
[Read transmission errors],
and to delete (zeroing of counters in the memory of the
converter) press
[Delete transmission errors].
In case of parity errors or frame errors, should be checked the ADA-7010D
converter's configuration and correctness connection of RS232 interface and to Fibre-Optic converter port.
After finishing the diagnostics, the SW1 microswitch should be set to the run mode (see pt OPERATION MODE).
6.5. FIRMWARE UPDATE
Set SW1 microswitch to configuration mode as in table below.
SW1-1
SW1-2
ON
OFF
In the configuration mode the yellow LED will blink with frequency 1Hz. Press a button
[Load New Firmware]
to change the software
delivered by manufacturer. The Select File window will open (Fig.8) and select the *.bin file then click
[Open]
- software will be load to
ADAConfig
buffer storage and will be checked. If the
ADAConfig
not detect errors in loaded file, change converter software. Process
of updating is visualized by
ADAConfig
in use
Progress Window
and after proper changing confirmed by correct message.
9